RX Manual 04/04 Rev. 6 OPERATING INSTRUCTIONS<br />
3.1 CONT<strong>RO</strong>LS AND INDICATORS<br />
3.0 OPERATING INSTRUCTIONS<br />
The controls and indicators used in the operation of the system are outlined in the MC10<br />
<strong>RO</strong> Controller manual located in the Appendix. The operator must be thoroughly familiar<br />
with the controls and their respective functions for proper operation and in order to<br />
maintain the quality of the product and eliminate unnecessary shutdowns.<br />
3.2 INITIAL STARTUP OF REVERSE OSMOSIS SYSTEM<br />
CAUTION<br />
CAUTION<br />
CAUTION<br />
Verify that all <strong>RO</strong> pressure vessel end cap retaining “U” pins are in place<br />
and secure.<br />
Do not run the motor for more than 30 seconds backwards or irreversible<br />
pump damage may result.<br />
The membrane feed pressure should not be allowed to exceed 250 psig at<br />
any time during operation.<br />
A. The operator should verify that appropriate pretreatment is in place and operating<br />
satisfactorily. Inappropriate or inoperative pretreatment can damage the<br />
membranes.<br />
B. Make all water, electrical, and drain connections according to installation<br />
instructions.<br />
C. Divert the outlet of the product water to a convenient drain.<br />
D. Turn on the feed water and the electrical power. With product water diverted to<br />
drain, fully open the reject throttling valve and close the reject recirculation<br />
throttling valve.<br />
E. Place the controller in the DIRECT FEED mode (refer to the Reverse Osmosis<br />
Controller manual in the Appendix for detailed instructions). Press the SYSTEM<br />
START button on the controller keypad to start the system, after a fifteen-second<br />
delay the pump should start.<br />
F. Check for proper pump rotation. (Please refer to the Pump Information, included<br />
in the Appendix of this manual for information concerning motor rotation and any<br />
other electrical requirements.)<br />
G. Set the reject recirculation flow to zero, but do not exceed 250 psig pressure to<br />
the membranes. Open the reject valve further if necessary to avoid over<br />
pressuring the system.<br />
CAUTION<br />
Do not use reject recirculation option for the first 4 hours of operation to<br />
speed flush up of the system.<br />
<strong>USF</strong>ilter 3-1