Using the IAQPoint<br />

Programming Menus<br />

A confirmation screen is briefly displayed and the zero calibration begins.<br />

*Menu*<br />

In Calib<br />

A success or failure message is displayed and the screen returns to the<br />

main menu option.<br />

CO2 Set Zero<br />

SUCCESS<br />

Calibrating the CO2 Sensor<br />

This option allows users to calibrate the sensor’s span.<br />

Note: When calibrating a duct mounted unit, the unit must be removed<br />

from its base to ensure proper calibration.<br />

• Before starting the calibration (using the programming menus),<br />

connect the regulator to the gas cylinder.<br />

• Adjust the flow rate to 0.1 L/min.(for the 2000 ppm range)<br />

• Connect the tubing from the regulator to the sensor, as shown in the<br />

image at left.<br />

Start exposing the sensor to the calibration gas at least<br />

10 minutes before starting and throughout the calibration<br />

process.<br />

• Let the gas flow for at least 10 minutes before starting the calibration.<br />

• Scroll to the “CO 2 Set Span” main menu option and press Enter to<br />

select.<br />

* Menu *<br />

CO2 Set Span<br />

• The next screen allows you to specify the span calibration gas<br />

concentration value.<br />

Set Span Gas<br />

2000<br />

26 IAQPoint User <strong>Manual</strong>