90DM4 CALIBRATION PROCEDURE<br />

CALIBRATING THE SPAN (UNITS WITH DISPLAY)<br />

Access to the 90DM4 programming is achieved through push buttons located on the back of the device,<br />

accessible through an oblong cut-out. The left hand button opens access to programming functions and<br />

validates selections (equivalent to an Enter button). The right hand button scrolls through main<br />

programming screens and increases values when in a specific programming screen.<br />

Hold the unit (facing you) in both hands<br />

Place both index fingers through the cut-out until they touch the left and right push buttons,<br />

respectively.<br />

Press the left button to access the programming menus.<br />

1. Turn on the regulator. The calibration gas is now flowing into the unit. Wait for 10 minutes minimum to<br />

allow the reading to stabilize.<br />

2. Press the left pushbutton to access the menu.<br />

3. Use the right pushbutton to change each letter until the password VA is reached.<br />

4. Press the left pushbutton to confirm each letter.<br />

5. Use the right pushbutton to scroll to the Menu Set Span screen.<br />

6. Press the left pushbutton to select.<br />

7. In the GoCalib screen, press the right button to scroll to Yes and press the left<br />

pushbutton to start the calibration.<br />

8. Wait message appears, the transmitter will go into Span calibration.<br />

9. The calibration procedure is finished when the Menu Set Span message appears.<br />

10. Press the right pushbutton until the Quit screen is displayed and press the left pushbutton to exit.<br />

Table I - <strong>Calibration</strong> Information<br />

Gas Scale Warm-up Notes<br />

N2 0 - 2000 ppm 15 minutes<br />

Figure I – <strong>Calibration</strong> equipment setup<br />

CALIBRATION KIT<br />

Standard <strong>Calibration</strong> Kit<br />

Order Number Description<br />

SKCO290DM3 STANDARD CAL KIT FOR 90DM3/90DM4/IAQPoint CO2, 103L N2<br />

Low Cost <strong>Calibration</strong> Kit<br />

Order Number Description<br />

LCCO290DM3 LOW COST CAL KIT FOR 90DM3/90DM4/IAQPoint CO2, 17L N2<br />

Password<br />

* VA *<br />

MainProg<br />

Set Zero<br />

GoCalib?<br />

Yes<br />

510244 90DM4 <strong>Calibration</strong>Procedure.PDF R02 www.honeywellanalytics.com 2