90DM4 CALIBRATION PROCEDURE<br />
CALIBRATING THE SPAN (UNITS WITH DISPLAY)<br />
Access to the 90DM4 programming is achieved through push buttons located on the back of the device,<br />
accessible through an oblong cut-out. The left hand button opens access to programming functions and<br />
validates selections (equivalent to an Enter button). The right hand button scrolls through main<br />
programming screens and increases values when in a specific programming screen.<br />
Hold the unit (facing you) in both hands<br />
Place both index fingers through the cut-out until they touch the left and right push buttons,<br />
respectively.<br />
Press the left button to access the programming menus.<br />
1. Turn on the regulator. The calibration gas is now flowing into the unit. Wait for 10 minutes minimum to<br />
allow the reading to stabilize.<br />
2. Press the left pushbutton to access the menu.<br />
3. Use the right pushbutton to change each letter until the password VA is reached.<br />
4. Press the left pushbutton to confirm each letter.<br />
5. Use the right pushbutton to scroll to the Menu Set Span screen.<br />
6. Press the left pushbutton to select.<br />
7. In the GoCalib screen, press the right button to scroll to Yes and press the left<br />
pushbutton to start the calibration.<br />
8. Wait message appears, the transmitter will go into Span calibration.<br />
9. The calibration procedure is finished when the Menu Set Span message appears.<br />
10. Press the right pushbutton until the Quit screen is displayed and press the left pushbutton to exit.<br />
Table I - <strong>Calibration</strong> Information<br />
Gas Scale Warm-up Notes<br />
N2 0 - 2000 ppm 15 minutes<br />
Figure I – <strong>Calibration</strong> equipment setup<br />
CALIBRATION KIT<br />
Standard <strong>Calibration</strong> Kit<br />
Order Number Description<br />
SKCO290DM3 STANDARD CAL KIT FOR 90DM3/90DM4/IAQPoint CO2, 103L N2<br />
Low Cost <strong>Calibration</strong> Kit<br />
Order Number Description<br />
LCCO290DM3 LOW COST CAL KIT FOR 90DM3/90DM4/IAQPoint CO2, 17L N2<br />
Password<br />
* VA *<br />
MainProg<br />
Set Zero<br />
GoCalib?<br />
Yes<br />
510244 90DM4 <strong>Calibration</strong>Procedure.PDF R02 www.honeywellanalytics.com 2