<strong>M238</strong> System Variables<br />

SERIAL_R[0..1]: Serial Line Read Only System Variables<br />

Introduction<br />

Variable Structure<br />

SERIAL_R is an array of 2 SERIAL_R_STRUCT type. Each element of the array<br />

returns diagnostic System Variables for the corresponding Serial Line.<br />

For <strong>M238</strong>:<br />

Serial_R[0] refers to the Serial Line 1<br />

Serial_R[1] refers to the Serial Line 2 (only for T<strong>M238</strong>LFDC24DT• and<br />

T<strong>M238</strong>LFAC24DR )<br />

The following table describes the parameters of the SERIAL_R[0..1] System<br />

Variables:<br />

%MW Var Name Type Comment<br />

Serial Line<br />

n/a i_udiFramesTransmittedOK UDINT Number of frames successfully transmitted.<br />

n/a i_udiFramesReceivedOK UDINT Number of frames received without any<br />

detected errors.<br />

n/a i_udiRX_MessagesError UDINT Number of frames received with detected<br />

errors (checksum, parity).<br />

Modbus Specific<br />

n/a i_uiSlaveExceptionCount UINT Number of Modbus exception responses<br />

returned by the Controller.<br />

n/a i_udiSlaveMsgCount UINT Number of messages received from the Master<br />

and addressed to the Controller.<br />

n/a i_uiSlaveNoRespCount UINT Number of Modbus Broadcast requests<br />

received by the Controller.<br />

n/a i_uiSlaveNakCount UINT Not used<br />

n/a i_uiSlaveBusyCount UINT Not used<br />

n/a i_uiCharOverrunCount UINT Number of Character overrun.<br />

NOTE: n/a means that there is no predefined %MW mapping for this System<br />

Variable.<br />

NOTE:<br />

The SERIAL_R Counters are reset on:<br />

Download.<br />

Controller Reset.<br />

SERIAL_W[x].q_wResetCounter command.<br />

Reset command by Modbus request function code #8.<br />

20 EIO0000000364 04/2012