5.2.3 Ventilation The ventilation of the boiler room must satisfy the applicable<br />

national and local standards and regulations (see Supplement).<br />

5.3 Connections<br />

With regard to ventilation, pay particular attention to the following<br />

points:<br />

a Observe the applicable national and local standards and<br />

regulations for the dimensions of the openings and the protection<br />

for any mechanical ventilation<br />

b Ensure that the air inlet openings are transversely placed in<br />

two opposite walls<br />

c Fit inlet gratings with a large width and a small height<br />

d Ensure that the correct amount of high level ventilation exists<br />

e If the air supply is inadequate, it may be necessary to fit a<br />

mechanical means of providing adequate ventilation.<br />

5.3.1 Gas connection The gas connection must be made by a recognised installer in<br />

accordance with the applicable national and local standards<br />

and regulations (see Supplement).<br />

The gas connection is made at the rear of the boiler.<br />

Types 00 - 03 are not suitable for immediate connection to a<br />

100 mbar natural gas system. The pressure of the gas supplied<br />

to the unit must be reduced to 25 mbar for natural gas or 50<br />

mbar for propane with the use of a gas pressure regulator.<br />

From type 04, all <strong>boilers</strong> are suitable for gas supply pressures<br />

of both 25 and 100 mbar on natural gas.<br />

The loss of pressure in the connecting pipes must be such that,<br />

at maximum boiler capacity, the pressure must never fall below<br />

18 mbar for natural gas or 30 mbar for propane.<br />

5.3.2 Electrical connection The electrical connections and provisions must comply with the<br />

applicable national and local standards and regulations (see<br />

Supplement).<br />

The units are wired in accordance with the electrical diagram<br />

supplied with the appliance.<br />

The electrical connections, the terminals and the boiler pump<br />

relay are mounted in a separate connection box behind the<br />

front panel (extrusion profile, see fig. 4).<br />

2789CV02C 19