Maximum permitted flue system length in metres of smooth<br />

pipe. Standard flues only.<br />

Type Length of flue system in m<br />

Diameter Diameter Diameter Diameter Diameter Diameter<br />

120 mm 150 mm 180 mm 200 mm 250 mm 300 mm<br />

<strong>R2700</strong> 25 87* - - - -<br />

R2701 16 56* - - - -<br />

R2702 ** 39* - - - -<br />

R2703 ** ** 62* - - -<br />

R2704 ** ** ** 70* - -<br />

R2705 ** ** ** 35* - -<br />

R2706 ** ** ** ** 71* -<br />

R2707 ** ** ** ** 50* -<br />

R2708 ** ** ** ** ** 92*<br />

R2709 ** ** ** ** ** 69*<br />

<strong>R2800</strong> 28 96* - - - -<br />

R2801 17 59* - - - -<br />

R2802 ** 36 95* - - -<br />

R2803 ** ** 61 107* - -<br />

R2804 ** ** 30 54* - -<br />

R2805 ** ** ** 32 109* -<br />

R2806 ** ** ** 21 76* -<br />

R2807 ** ** ** ** 53 141*<br />

R2808 ** ** ** ** 38 105*<br />

R2809 ** ** ** ** 31 86*<br />

<strong>R2900</strong> 32 110* - - - -<br />

R2901 17 59* - - - -<br />

R2902 ** 36 95* - - -<br />

R2903 ** ** 61 107* - -<br />

R2904 ** ** 30 54* - -<br />

R2905 ** ** ** 32 109* -<br />

R2906 ** ** ** 21 76* -<br />

R2907 ** ** ** ** 53* 141<br />

R2908 ** ** ** ** 38 105*<br />

R2909 ** ** ** ** 31 86*<br />

Table 10 Length of flue system<br />

The flue system lengths have been rounded down.<br />

* Chimney diameter at the appliance<br />

** Not applicable<br />