5.4.2 Water flow<br />
5.4.2.1 Flow rate and The rate of water flow through the appliance must never fall<br />
resistance below the required minimum (otherwise the water flow switch<br />
will be activated and the appliance will be shut down). The use<br />
of valves, non-return valves, systems in which several appliances<br />
are connected to a common transport system, etc., must<br />
not interfere with the required water circulation.<br />
Type )T 20 K<br />
Pu mp data<br />
Nominal Boiler- Grundfos Pump Head Available Max.*<br />
flow resis- pump speed at head at power conrate<br />
tance type Qnom. Qnom. sumption<br />
3<br />
m/h kPa UPS kPa kPa W<br />
<strong>R2700</strong> 4,11 13 32-60 F 3 46 33 190<br />
R2701 5,12 20 32-60 F 3 46 26 190<br />
R2702 6,14 29 32-120F 3 80 51 400<br />
R2703 7,69 36 32-120F 3 72 36 400<br />
R2704 9,44 43 32-120F 3 59 16 400<br />
R2705 12,96 29 40-120F 3 58 29 460<br />
R2706 16,26 36 50-120F 3 75 39 720<br />
R2707 19,30 43 50-120F 3 64 21 720<br />
R2708 21,92 32 50-120F 3 55 23 720<br />
R2709 25,91 39 65-120F 3 82 43 1150<br />
<strong>R2800</strong> 4,02 12 32-60 F 3 46 34 190<br />
R2801 5,12 20 32-60 F 3 44 24 185<br />
R2802 6,41 25 32-120F 3 79 54 400<br />
R2803 7,87 30 32-120F 3 73 43 400<br />
R2804 10,80 20 40-120F 3 70 50 460<br />
R2805 13,55 25 40-120F 3 55 30 460<br />
R2806 16,08 30 50-120F 3 76 46 720<br />
R2807 18,27 22 50-120F 3 70 48 720<br />
R2808 21,59 27 50-120F 3 59 32 720<br />
R2809 23,78 32 65-120F 3 83 51 1150<br />
<strong>R2900</strong> 4,02 12 32-60 F 3 46 34 190<br />
R2901 5,12 20 32-60 F 3 44 24 185<br />
R2902 6,41 25 32-120F 3 79 54 400<br />
R2903 7,87 30 32-120F 3 73 43 400<br />
R2904 10,80 20 40-120F 3 70 50 460<br />
R2905 13,55 25 40-120F 3 55 30 460<br />
R2906 16,08 30 50-120F 3 76 46 720<br />
R2907 18,27 22 50-120F 3 70 48 720<br />
R2908 21,59 27 50-120F 3 59 32 720<br />
R2909 23,78 32 65-120F 3 83 51 1150<br />
Table 12 Water flow rate and pump data<br />
* The maximum power consumption of the pump is given for pump speed<br />
3. The optimum operating point in relation to efficiency and minimum<br />
power consumption can be determined from the related pump curve.<br />
2789CV02C 37