the use of a signal amplifier is recommended.<br />

41 - 42 SCOM bus connection (use the correct polarity).<br />

43 - 44 Primary boiler pump control (0 – 10 V = +2 °C – +90<br />

°C). (Not available for <strong>R2700</strong> series <strong>boilers</strong>).<br />

* the use of screened cables is recommended.<br />

5.3.3 Water connections The appliance must be installed by a recognised installer in<br />

accordance with the applicable national and local specifications<br />

and regulations (see Supplement). The flow and return connections<br />

are made at the rear of the unit.<br />

Supports for water connections<br />

It is recommended that the flow and return pipes be properly<br />

supported. This will avoid damage through overloading (weight)<br />

and simplifies maintenance.<br />

Fig. 17 Support<br />

The unit is a constant water flow appliance and is suitable for<br />

use in both open vented (non-pressurised) systems and sealed<br />

(pressurised) systems provided the minimum pressure requirements,<br />

as per table 14, are met. The unit is fitted with a boiler<br />

pump as standard and which guarantees the required water<br />

circulation through the boiler. The capacity and working head of<br />

the pump is sufficient to overcome both the resistance of the<br />

boiler and some resistance offered by the system.<br />

The boiler pump is however not a system pump<br />

If the resistance of the system exceeds the available working<br />

head, the boiler will be shut down by the flow switch. In order to<br />

prevent this happening, the length and diameter of the primary<br />

pipework between the boiler and the low velocity header must<br />

be chosen such that the remaining working head of the pump<br />

(see table 12) will not be exceeded.<br />

2789CV02C 25