Earth leakage trips can give problems when they are used in<br />

combination with frequency converters. In some countries this<br />

is actually forbidden. There are two reasons for this:<br />

a All rectifiers (not only frequency converters) can cause direct<br />

currents to flow in the mains power supply and which can<br />

reduce the sensitivity of the safety switch<br />

b The asymmetric loading caused by radio interference filters<br />

can result in the premature operation of the earth leakage<br />

trip, which in turn will result in the unit being switched off.<br />

In order to prevent malfunctions occurring as a result of<br />

inductive or high frequency signals, or static electricity,<br />

screened cables must be employed for all low voltage and<br />

control signals between the boiler and externally connected<br />

units. The screening must be earthed at both ends<br />

of the cable.<br />