Type Air supply X Y<br />

diameter D (mm) (mm) (mm)<br />

<strong>R2700</strong> 125 191 185<br />

R2701 <strong>R2800</strong> <strong>R2900</strong> 125 191 185<br />

R2702 R2801 R2901 125 191 185<br />

R2703 R2802 R2902 150 141 195<br />

R2704 R2803 R2903 180 160 210<br />

R2705 R2804 R2904 180 160 210<br />

R2706 R2805 R2905 200 160 220<br />

R2707 R2806 R2906 200 160 220<br />

R2708 R2807 R2907 250 240 240<br />

R2709 R2808 R2908 250 185 240<br />

R2809 R2909 250 185 240<br />

Table 8 Air supply connection<br />

Fig. 19 Air supply connection<br />

The connection to the air supply pipe is always mounted on the<br />

top of the unit.<br />

Multiple units may not be connected to the same air supply or<br />

flue pipe.<br />

To prevent snow entering, the air supply pipe must extend at<br />

least 30 cm above the roof and must be fitted with a rain cap.<br />

The flue pipe opening must end at least 100 cm above the roof,<br />

assuming the roof to be flat.<br />

2789CV02C 27