<strong>PROFIBUS</strong> IO data description<br />

5.4.2 Standard telegram 82<br />

40<br />

Standard telegram 82 uses 4 bytes <strong>for</strong> output data from the<br />

master to the encoder gateway and 14 bytes of input data from<br />

the encoder gateway to the master.<br />

Output data from the master:<br />

2 bytes Control word 2 (STW2_ENC)<br />

2 bytes Control word (G1_STW)<br />

IO Data (word) 1 2<br />

Set point STW2_ENC G1_STW<br />

Input data to the master:<br />

2 bytes Status word 2 (ZSW2_ENC)<br />

2 bytes Status word (G1_ZSW)<br />

4 bytes Position value 1 (G1_XIST1)<br />

4 bytes Position value 2 (G1_XIST2)<br />

2 bytes Velocity value A (NIST_A)<br />

IO Data (word) 1 2 3 4 5 6 7<br />

Actual value ZSW2_ENC G1_ZSW G1_XIST1 G1_XIST2 NIST_A<br />

Note: Telegram 82 is only supported by the encoder gateway.<br />

It is not supported by the absolute encoder.