19.10.2012 Views

4 WinCC-Runtime 4.1 Start of the program without Auto Start

4 WinCC-Runtime 4.1 Start of the program without Auto Start

4 WinCC-Runtime 4.1 Start of the program without Auto Start

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

IMPORTANT:<br />

These values are also used by <strong>the</strong> recipe and changes will effect <strong>the</strong> next automatic recipe.<br />

<strong>4.1</strong>1 Pressure tests<br />

The pressure test which can be performed within a<br />

recipe and by pressing <strong>the</strong> button<br />

can be configured in <strong>the</strong> menu which appears after<br />

pressing <strong>the</strong> button.<br />

The pressure will be reached automatically with <strong>the</strong><br />

nitrogen valve V39. After closing <strong>the</strong> valve <strong>the</strong> system<br />

waits for 20 seconds to ensure a stable start point.<br />

Then <strong>the</strong> test begins and after a period specified in “hold<br />

time” <strong>the</strong> final pressure will be compared to <strong>the</strong> start<br />

pressure. The test is successful if <strong>the</strong> pressure drop<br />

measured is lower <strong>the</strong>n <strong>the</strong> value specified in “pressure<br />

difference”.<br />

After <strong>the</strong> test <strong>the</strong> starting pressure (before <strong>the</strong> test) will<br />

be reached automatically by opening V04.<br />

resets a valid pressure test which<br />

means that a new pressure test is necessary.<br />

The settings are:<br />

Overpressure gives <strong>the</strong> pressure where <strong>the</strong> test is performed.<br />

Pressure difference is pressure drop with which test has failed.<br />

Hold time is <strong>the</strong> time interval which is used for this test<br />

Hold time done indicates <strong>the</strong> time elapsed from <strong>the</strong> beginning <strong>of</strong> <strong>the</strong> hold<br />

time.<br />

Pressure test o.K. Indicates a successful pressure test.<br />

Max. pressure: max. pressure during test.<br />

Pressure drop: final pressure drop after elapsed time from max. pressure<br />

AP-Miniplant - Operation Manual Mini Batch Plant Page 40