One <strong>of</strong> <strong>the</strong> events shown in <strong>the</strong> following list:<br />

Hydrogen alarm (immediately after signal changes from 1 to 0)<br />

Extraction failure (70 s after event, 1st warning after 10 s)<br />

Fire extinguisher on (immediately after signal changes from 1 to 0)<br />

Emergency <strong>of</strong>f push button (immediately after signal changes from 1 to 0)<br />

Safety questions after starting<br />

shut down<br />

Warning message in <strong>the</strong> alarm window, at <strong>the</strong> same time <strong>the</strong><br />

button starts flashing while <strong>the</strong> shut down<br />

procedure is active.<br />

The shut down procedure brings <strong>the</strong> reactor to a safe temperature. During this procedure <strong>the</strong> stirrer<br />

will go to a predefined safe stirrer speed if it was switched on before <strong>the</strong> shut down procedure started.<br />

After reaching <strong>the</strong> safe temperature, <strong>the</strong> reactor will be vented. All feeds are blocked.<br />

4.4.2 Stop shut down procedure<br />

The shut down procedure has to be stopped manually by pushing <strong>the</strong> shut down button again and<br />

answering <strong>the</strong> safety question with .<br />

Shut down procedure can also be stopped pressing <strong>the</strong> Button at <strong>the</strong> rig or <strong>the</strong> PC<br />

cabinet for more <strong>the</strong>n 3 seconds.<br />

4.5 Locking mechanism<br />

4.5.1 Valves<br />

Hydrogen input V17 is blocked as long as no pressure test has been successfully performed.<br />

Vacuum/Normal pressure valve H04 will switch automatically to normal pressure as soon as <strong>the</strong> limit<br />

<strong>of</strong> 1.2 bar is exceeded.<br />

Catalyst Feed H01<br />

Acknowledge button catalyst feed<br />

To prevent <strong>the</strong> catalyst feed from being used by mistake, <strong>the</strong>re<br />

is a locking mechanism. It is necessary to acknowledge with a<br />

button that <strong>the</strong> catalyst unit is properly prepared for use. This<br />

button has to be pressed after every opening <strong>of</strong> <strong>the</strong> ball valve<br />

H01.<br />

AP-Miniplant - Operation Manual Mini Batch Plant Page 26