Compliance and Accreditation<br />

WARNING! This is a Class A Product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate<br />

measures<br />

This product complies with the following Standards/Accreditations:<br />

FCC Part 15 Class A<br />

This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions<br />

This Device Must Not Cause Harmful Interference, and<br />

This device must accept any interference received, including interference that may cause undesired operation.<br />

EN55022 Class A<br />

EN50130-4<br />

AS/NZS 3548 Class A: Subject to the following condition:<br />

To comply with EMC requirements when the 1057 is housed in the Small or Large Universal Enclosure, all RS485 cable shielding must be terminated to<br />

the chassis earth of the 1057 PCB. A small screw is provided in the vicinity of the RS485 connections for this purpose.<br />

NOTE:Transorbs for inputs and outputs are . For inputs or outputs with no transorbs , wiring cannot exceed 20 feet.<br />

UL Compliance Considerations for USA & Canada<br />

For inputs and outputs without transorbs, wiring cannot exceed 20 feet.<br />

Emission Approvals<br />

To comply with class A requirements when the 1064 is connected to a 1057/1058 RTU, the 1057 and the 1058 will require the following modifications:<br />

A small section of paint must be removed from the underside of the metal lid where the four mounting posts touch the lid.<br />

A Ferrite with 1 turn positioned close to the AC terminal on the AC input Cable. (Ferrite Details: Fair-Rite #0431167281, or similar. 240W impedance @<br />

100MHz.)<br />

An earth ground connection must be attached to the chassis along with a ground connection between the AC power connector and the chassis.<br />