HR BOILER.pdf - Hurlcon Heating
HR BOILER.pdf - Hurlcon Heating
HR BOILER.pdf - Hurlcon Heating
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>BOILER</strong> DIMENSIONS<br />
*Indoor model shown, outdoor model supplied without flue spigot.<br />
INDOOR INSTALLATION<br />
If the <strong>HR</strong> Boiler is to be installed indoors the correct size flue must be connected. The <strong>HR</strong> series boilers have an<br />
inbuilt draught diverter so the flue can be connected directly to the outlet spigot. The top of the boiler is not<br />
designed to support the flue. Suitable support must be used.<br />
Boiler model<br />
<strong>HR</strong> 600<br />
<strong>HR</strong> 800<br />
<strong>HR</strong> 1000<br />
<strong>HR</strong> 1200<br />
<strong>HR</strong> 1400<br />
<strong>HR</strong> 1600<br />
<strong>HR</strong> 1800<br />
Flue size<br />
255 mm<br />
305 mm<br />
405 mm<br />
405 mm<br />
455 mm<br />
455 mm<br />
455 mm<br />
The flue must also be terminated with an approved gas flue cowl (not a Chinaman’s hat) 600mm above any<br />
roofline that is within 1.5 metres horizontally from the flue.<br />
<strong>HR</strong> Series II Hot Water Boiler & Pool Heater 6