CATALOG<br />
Page 19<br />
Capacities and Selection<br />
Capacity in Tons of Refrigeration<br />
These ratings are based on vapor free (subcooled) liquid refrigerant entering<br />
the expansion valve (86°F for Refrigerant 717) and standard factory setting.<br />
Because of the artificial superheat provided by the electric heater the Level-<br />
Master will have a greater capacity than a conventional thermostatic expansion<br />
valve. For selections for other refrigerants, contact Sporlan Valve<br />
Company, Washington, Missouri 63090.<br />
REFRIGERANT 717 Ammonia CAPACITIES<br />
EVAPORATOR<br />
TEMPERATURE°<br />
F<br />
LMC<br />
NOMINAL 40°<br />
to 0°<br />
- 10°<br />
- 20°<br />
-40°<br />
VALVE<br />
CAPACITY<br />
TYPE<br />
PRESSURE DROP ACROSS VALVE – psi<br />
80<br />
100<br />
120<br />
140<br />
160<br />
100<br />
120<br />
140<br />
160<br />
180<br />
100<br />
120<br />
140<br />
160<br />
180<br />
100<br />
120<br />
140<br />
160<br />
180<br />
1 0.94<br />
1.06<br />
1.16<br />
1.25<br />
1.34<br />
0.98<br />
1.07<br />
1.15<br />
1.23<br />
1.31<br />
0.86<br />
0.94<br />
1.01<br />
1.08<br />
1.15<br />
0.59<br />
0.65<br />
0.70<br />
0.75<br />
0.80<br />
2 2.69<br />
3.01<br />
3.30<br />
3.56<br />
3.80<br />
2.77<br />
3.04<br />
3.28<br />
3.50<br />
3.71<br />
2.44<br />
2.67<br />
2.88<br />
3.08<br />
3.26<br />
1.68<br />
1.85<br />
1.99<br />
2.13<br />
2.26<br />
D 5 6.08<br />
6.80<br />
7.45<br />
8.05<br />
8.60<br />
6.26<br />
6.85<br />
7.41<br />
7.91<br />
8.39<br />
5.51<br />
6.03<br />
6.52<br />
6.97<br />
7.39<br />
3.81<br />
4.17<br />
4.51<br />
4.82<br />
5.11<br />
10<br />
11.<br />
0 12.<br />
3 13.<br />
5 14.<br />
6 15.<br />
6 11.<br />
3 12.<br />
4 13.<br />
4 14.<br />
4 15.<br />
2 9.96<br />
10.<br />
9 11.<br />
8 12.<br />
6 13.<br />
4 6.89<br />
7.56<br />
8.18<br />
8.74<br />
9.26<br />
15<br />
15.<br />
0 16.<br />
8 18.<br />
4 19.<br />
9 21.<br />
3 15.<br />
4 16.<br />
9 18.<br />
3 19.<br />
6 20.<br />
8 13.<br />
6 14.<br />
9 16.<br />
1 17.<br />
2 18.<br />
3 9.41<br />
10.<br />
3 11.<br />
1 11.<br />
9 12. 6<br />
20<br />
17.<br />
8 19.<br />
8 21.<br />
8 23.<br />
5 25.<br />
1 18.<br />
2 20.<br />
0 21.<br />
6 23.<br />
1 24.<br />
5 16.<br />
0 17.<br />
6 19.<br />
0 20.<br />
3 21.<br />
6 11.<br />
1 12.<br />
2 13.<br />
2 14.<br />
0 14. 9<br />
30<br />
30.<br />
0 33.<br />
6 36.<br />
8 39.<br />
7 42.<br />
4 30.<br />
9 33.<br />
8 36.<br />
5 39.<br />
0 41.<br />
4 27.<br />
2 29.<br />
8 32.<br />
2 34.<br />
3 36.<br />
4 18.<br />
8 20.<br />
6 22.<br />
2 23.<br />
7 25. 2<br />
A 50<br />
42.<br />
7 47.<br />
7 52.<br />
3 56.<br />
5 60.<br />
4 43.<br />
9 48.<br />
1 52.<br />
0 55.<br />
6 58.<br />
9 38.<br />
6 42.<br />
4 45.<br />
8 48.<br />
9 51.<br />
9 26.<br />
7 29.<br />
3 31.<br />
6 33.<br />
8 35. 9<br />
75<br />
75.<br />
1 84.<br />
0 92.<br />
0 99.<br />
4 106<br />
77.<br />
3 84.<br />
6 91.<br />
4 97.<br />
5 103<br />
68.<br />
0 74.<br />
5 80.<br />
5 85.<br />
9 91.<br />
1 47.<br />
0 51.<br />
5 55.<br />
7 59.<br />
4 63. 0<br />
100<br />
106<br />
118<br />
130<br />
140<br />
150<br />
108<br />
120<br />
129<br />
138<br />
146<br />
95.<br />
6 105<br />
113<br />
122<br />
129<br />
66.<br />
1 72.<br />
8 78.<br />
4 84.<br />
0 89. 1<br />
These factors include corrections for liquid refrigerant density<br />
and net refrigerating effect, and are based on an average evaporating<br />
temperature of 0°F. However, they may be used for any<br />
evaporator temperature from -40°F to 40°F since the variation<br />
in the actual factors across this range is insignificant.<br />
EXAMPLE: At -20°F evaporator, 160 psi pressure drop and 50°F liquid<br />
temperature, the capacity of an LMC-DA-10 (for ammonia) is<br />
12.6 x 1.11 = 14.0 tons.<br />
Ordering Instructions<br />
Complete Control Valve and Element:<br />
1. Valve type, per specification table. If an external equalizer is<br />
required, add "E" as the sixth letter. EXAMPLE: LMC-AAE-20<br />
2. Connection sizes and tubing lengths, if other than standard.<br />
3. Electrical characteristics.<br />
COMPLETE CONTROL<br />
VALVE & ELEMENT<br />
SPECIFICATIONS<br />
ELEMENT<br />
ONLY<br />
DISCHARGE<br />
TUBE<br />
INTERNAL ➀EXTERNAL<br />
Inches<br />
EQUALIZER EQUALIZER<br />
LMC-DA-1<br />
LMC-DAE-1<br />
1/32<br />
LMC-DA-2<br />
LMC-DAE-2<br />
1/16<br />
LMC-DA-5<br />
LMC-DAE-5<br />
LMC 23AL 5/64<br />
LMC-DA-10<br />
LMC-DAE-10<br />
7/64<br />
LMC-DA-15<br />
LMC-DAE-15<br />
5/32<br />
LMC-AA-20<br />
LMC-AAE-20<br />
1/8<br />
LMC-AA-30<br />
LMC-AAE-30<br />
5/32<br />
LMC-AA-50<br />
LMC-AAE-50<br />
LMC 12AL 3/16<br />
LMC-AA-75<br />
L MC-AAE-75<br />
–<br />
LMC-AA-100<br />
L MC-AAE-100<br />
–<br />
STANDARD<br />
CONNECTIONS<br />
Inches<br />
Sizes<br />
shown in BOLD<br />
figures<br />
will be furnished unless<br />
otherwise specified.<br />
INLET<br />
OUTLET<br />
1/4,<br />
3/8, or 1/<br />
2 FPT<br />
1/2<br />
or 3/4 FPT<br />
3/4<br />
FPT<br />
➀ Standard External Equalizer Connection (1/8” FPT) available when specified.<br />
LIQUID TEMPERATURE ENTERING TEV ° F<br />
REFRIGERANT 0 ° 10°<br />
20°<br />
30°<br />
40°<br />
50°<br />
60°<br />
70°<br />
80°<br />
86°<br />
90°<br />
100°<br />
CORRECTION FACTOR, CF LIQUID TEMPERATURE<br />
717<br />
1.27<br />
1.24<br />
1.20<br />
1.17<br />
1.14<br />
1.11<br />
1.08<br />
1.05<br />
1.02<br />
1.00<br />
0.99<br />
0.96<br />
LMC Element Only:<br />
Specify voltage, wattage, and type number as shown in<br />
"Element Only" column. (A 15-watt heater is supplied as standard.<br />
For applications below -60°F evaporating temperature<br />
specify a special 25-watt heater.)<br />
Electrical Specifications<br />
15-watt, 120v or 240v any frequency AC or DC.<br />
120v-25w, 240v-25w, 24v-25w and 24v-15w or 25w<br />
are available on special order at additional charge.<br />
Standard Tubing Length<br />
10 feet – Other lengths in integrals of 5 feet available<br />
on special order.<br />
Replacement Parts<br />
Internal parts kits – Same as standard thermostatic<br />
expansion valves. Specify valve type and port size.<br />
Heater Element Assembly<br />
Consists of heater element, lead wire, protective thermostatic<br />
switch, and moisture proof seal.