Page 6<br />

CATALOG<br />

Thermostatic Expansion Valve Capacities – Tons of Refrigeration<br />

These ratings are based on vapor free 86°F liquid refrigerant entering the TEV, a maximum opening superheat of 7°F, and a<br />

standard factory air test setting.<br />

AC and AL THERMOSTATIC CHARGES<br />

EVAPORATOR<br />

TEMPERATURE ° F<br />

VALVE NOMINAL PORT DISCHARGE<br />

40°<br />

20°<br />

5°<br />

TYPE CAPACITY SIZE TUBE SIZE<br />

PRESSURE DROP ACROSS VALVE – psi<br />

80<br />

100<br />

120<br />

140<br />

100<br />

120<br />

140<br />

160<br />

100<br />

120<br />

140<br />

160<br />

D 1 1/16<br />

1/32<br />

1.08<br />

1.21<br />

1.32<br />

1.43<br />

1.02<br />

1.12<br />

1.21<br />

1.29<br />

0.85<br />

0.93<br />

1.00<br />

1.07<br />

D 2 1/16<br />

1/16<br />

2.16<br />

2.41<br />

2.64<br />

2.86<br />

2.05<br />

2.24<br />

2.42<br />

2.59<br />

1.69<br />

1.85<br />

2.00<br />

2.14<br />

D 5 7/64<br />

5/64<br />

5.40<br />

6.03<br />

6.61<br />

7.14<br />

5.12<br />

5.61<br />

6.05<br />

6.47<br />

4.23<br />

4.63<br />

5.00<br />

5.35<br />

D 10<br />

3/16<br />

7/64<br />

10.<br />

8 12.<br />

1 13.<br />

2 14.<br />

3 10.<br />

2 11.<br />

2 12.<br />

1 12.<br />

9 8.45<br />

9.26<br />

10.<br />

0 10. 7<br />

D 15<br />

3/16<br />

5/32<br />

16.<br />

2 18.<br />

1 19.<br />

8 21.<br />

4 15.<br />

4 16.<br />

8 18.<br />

2 19.<br />

4 12.<br />

7 13.<br />

9 15.<br />

0 16. 0<br />

A 20<br />

5/16<br />

1/<br />

8 19.<br />

3 21.<br />

6 23.<br />

6 25.<br />

5 18.<br />

8 20.<br />

6 22.<br />

2 23.<br />

7 16.<br />

9 18.<br />

5 20.<br />

0 21. 4<br />

A 30<br />

5/16<br />

5/32<br />

28.<br />

9 32.<br />

3 35.<br />

4 38.<br />

2 28.<br />

1 30.<br />

8 33.<br />

3 35.<br />

6 25.<br />

4 27.<br />

8 30.<br />

0 32. 1<br />

A 50<br />

3/<br />

8<br />

3/16<br />

48.<br />

2 53.<br />

9 59.<br />

0 63.<br />

7 46.<br />

9 51.<br />

4 55.<br />

5 59.<br />

3 42.<br />

3 46.<br />

3 50.<br />

0 53. 5<br />

A 75<br />

3 / 8<br />

– 72.<br />

3 80.<br />

8 88.<br />

5 95.<br />

6 70.<br />

4 77.<br />

1 83.<br />

3 89.<br />

0 63.<br />

4 69.<br />

4 75.<br />

0 80. 2<br />

A 100<br />

7 /16<br />

– 96.<br />

4 108<br />

118<br />

127<br />

93.<br />

8 103<br />

111<br />

119<br />

84.<br />

5 92.<br />

6 100<br />

107<br />

AZ and AL THERMOSTATIC CHARGES<br />

EVAPORATOR<br />

TEMPERATURE ° F<br />

VALVE NOMINAL PORT DISCHARGE<br />

- 10°<br />

-20°<br />

TYPE CAPACITY SIZE TUBE SIZE PRESSURE DROP ACROSS VALVE – psi<br />

120<br />

140<br />

160<br />

180<br />

120<br />

140<br />

160<br />

180<br />

D 1 1/16<br />

1/32<br />

0.61<br />

0.66<br />

0.71<br />

0.75<br />

0.52<br />

0.56<br />

0.60<br />

0.63<br />

D 2 1/16<br />

1/16<br />

1.06<br />

1.14<br />

1.22<br />

1.29<br />

0.89<br />

0.96<br />

1.03<br />

1.09<br />

D 5 7/64<br />

5/64<br />

2.48<br />

2.68<br />

2.87<br />

3.04<br />

2.09<br />

2.26<br />

2.42<br />

2.56<br />

D 10<br />

3/16<br />

7/64<br />

5.24<br />

5.66<br />

6.05<br />

6.42<br />

4.42<br />

4.78<br />

5.11<br />

5.42<br />

D 15<br />

3/16<br />

5/32<br />

7.27<br />

7.85<br />

8.39<br />

8.90<br />

6.13<br />

6.62<br />

7.08<br />

7.51<br />

A 20<br />

5/16<br />

1/<br />

8 15.<br />

9 17.<br />

2 18.<br />

4 19.<br />

5 13.<br />

6 14.<br />

7 15.<br />

8 16. 7<br />

A 30<br />

5/16<br />

5/32<br />

23.<br />

9 25.<br />

8 27.<br />

6 29.<br />

3 20.<br />

5 22.<br />

1 23.<br />

6 25. 1<br />

A 50<br />

3/<br />

8<br />

3/16<br />

39.<br />

9 43.<br />

1 46.<br />

0 48.<br />

8 34.<br />

1 36.<br />

9 39.<br />

4 41. 8<br />

A 75<br />

3 / 8<br />

– 59.<br />

8 64.<br />

6 69.<br />

1 73.<br />

2 51.<br />

2 55.<br />

3 59.<br />

1 62. 7<br />

A 100<br />

7 /16<br />

– 79.<br />

7 86.<br />

1 92.<br />

1 97.<br />

7 68.<br />

2 73.<br />

7 78.<br />

8 83. 6<br />

LIQUID TEMPERATURE ENTERING TEV ° F<br />

REFRIGERANT 0 ° 10°<br />

20°<br />

30°<br />

40°<br />

50°<br />

60°<br />

70°<br />

80°<br />

86°<br />

90°<br />

100°<br />

CORRECTION FACTOR, CF LIQUID TEMPERATURE<br />

717<br />

1.27<br />

1.24<br />

1.20<br />

1.17<br />

1.14<br />

1.11<br />

1.08<br />

1.05<br />

1.02<br />

1.00<br />

0.99<br />

0.96<br />

EXAMPLE: Actual capacity of nominal 10 ton valve at -10°F evaporator,<br />

160 psi pressure drop and 60°F liquid temperature = 6.05<br />

tons x 1.08 = 6.53 tons.<br />

These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an average evaporator temperature<br />

of 0°F. However, they may be used for any evaporator temperature from -20°F to 40°F since the variation in the actual factors<br />

across this range is insignificant.