C•<strong>CURE</strong> 800 Typical Controller Network<br />
C><strong>CURE</strong> 800 Typical System Schematic<br />
Controller Networks<br />
C•<strong>CURE</strong> 800<br />
C.<strong>CURE</strong> 800<br />
Model X<br />
apC/L<br />
LAN/WAN Belden 9842<br />
RS232 to 485<br />
Convertor<br />
apC/L apC/8x apC/L<br />
apC/8x<br />
NOTES:<br />
UDS10<br />
apC/8x apC/8x<br />
When a controller is wired directly into a PC serial<br />
port, only 1 apC/8x or apC/L can be connected.<br />
Maximum cable distance PC to controller is 15<br />
metres (serial)when set to RS232<br />
Up to 10 apC controllers on one comms line<br />
Belden 9842 (RS485)<br />
Maximum distance from convertor to last controller<br />
in the line is 1,200 metres<br />
Up to 6 apC controllers on a UDS10 comms line<br />
(still 1200m) when the UDS10 is set to RS485.<br />
Only one apC can be connected to a UDS10<br />
when set to RS232