Inverter shutdown<br />
WARNING!<br />
Hazardous live voltages can be present in the inverter even if the electrical connections are switched off or disco<br />
nnected. Please wait for 1 minute before accessing the inverter<br />
The inverter must be switched off for adjusting, maintenance and repair work. Please proceed as follows:<br />
1. Turn the inverter off by pushing the off button in the GUI.<br />
2. Turn the AC and DC switches to the OFF position<br />
a. (The off position is green and the on position is color coded red).<br />
3. Disconnect the inverter from the PV array.<br />
4. Disconnect the inverter from the grid.<br />
5. Check that the inverter is disconnected from all voltage sources.<br />
6. If possible Install lockout devices on the utility connection circuit breaker, AC and DC disconnect<br />
switches.<br />
7. Wait 1 minute for all capacitors inside inverter to discharge.<br />
8. When reactivating the XP inverter expect a five minute commission window.<br />
Page 12