IMPORTANT!<br />
Please check that the cables are connected and torqued properly.<br />
Use 90℃ copper conductors only.<br />
XP100U-H2 XP100U-H4 XP83U-H6 XP90U-H6 XP100U-H6<br />
AC connection cable<br />
A, B, C, N and PE<br />
Nominal AC voltage 208V 480V 600V 600V 600V<br />
Maximum AC current 278A 120A 80A 87A 96A<br />
XP100U-H4/ XP83U-H6/ XP90U-H6/ XP100U-H6<br />
Number of GRID cables Cable Size Torque<br />
A, B, C, N 4 1AWG<br />
All 194 (90℃) copper wire, 40 lb-ft<br />
tightening torque<br />
PE 1 4AWG<br />
194 (90℃) copper wire, 40 lb-ft<br />
tightening torque<br />
XP100U-H2<br />
Number of GRID cables Cable Size Torque<br />
A, B, C, N 4 300kcmil<br />
All 194 (90℃) copper wire, 40 lb-ft<br />
tightening torque<br />
PE 1 4AWG<br />
194 (90℃) copper wire, 40 lb-℉t<br />
tightening torque<br />