USER AND INSTALLATION MANUAL - KACO new energy, Inc.
USER AND INSTALLATION MANUAL - KACO new energy, Inc.
USER AND INSTALLATION MANUAL - KACO new energy, Inc.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
UAI terminal blocks (User Analog Inputs)<br />
The Inverter provide 4 user analog input interface connections that can be connected to an Irradiation sensor, a<br />
PV cell temperature sensor, and a PT1000 temperature sensor through the user analog input interface. The user<br />
analog input interface voltage range is 0 ~ 10V.<br />
Irradiance and Cell temperature Sensor (Si-12TC)<br />
Si-12TC figure<br />
Wire description<br />
VCC (12-24Vdc)<br />
GND<br />
Irradiation value(0-10V)<br />
Cell Temperature (0-10V)<br />
Frame GND<br />
Target port figure<br />
Connect the wires<br />
Port num. Port name Specification Wire size<br />
5 CTN<br />
6 CTP<br />
7 IVN<br />
8 IVP<br />
0V ~ 10Vdc<br />
0V ~ 10Vdc<br />
20AWG (0.518mm2)<br />