Process or field communication<br />

Typical practice-related data<br />

The table below contains empirical<br />

values which are intended to<br />

serve as recommendation <strong>for</strong> the<br />

selection of the optimum<br />

network.<br />

AS-Interface PROFIBUS DP PROFIBUS PA<br />

1<br />

2<br />

Connectable • Binary inputs/outputs •Binary inputs/outputs •Field devices in Zone 1<br />

field devices • Analog inputs/outputs •Analog inputs/outputs hazardous area<br />

•Intelligent field devices, (type of protection: [EEx ia],<br />

e.g. drives, measuring explosive group: IIC)<br />

sensors, slaves with data •Non hazardous area<br />

preprocessing (such as (measuring transducer,<br />

ET 200X® or S7-300®, actuators or valves)<br />

SIMOTION®)<br />

Programming/ -Via PROFIBUS DP Via PROFIBUS DP<br />

commissioning with STEP 7 <strong>and</strong> PDM <strong>and</strong> PROFIBUS PA with the<br />

SIMATIC PDM (Process<br />

Device Manager) tool<br />

3<br />

Number of slaves<br />

• Max. 62 • Max. 125 • 125 DP/PA links<br />

• 15 typ. • 20 to 30 typ • 31 field devices per DP/PA link<br />

4<br />

5<br />

6<br />

7<br />

AS-i cycle time Max. 5 ms <strong>for</strong> 31 slaves --<br />

Max. 10 ms <strong>for</strong> 62 slaves<br />

Bus cycle time -2 ms at 12 Mbit/s typ. 200 ms at 31.25 kbit/s typ.<br />

10 ms at 1.5 Mbit/s typ.<br />

Network capacity Electrical: Electrical: up to 9.6 km Hazardous area: max. 1.0 km<br />

With/without repeater 100 m Optical: up to 90 km Non-haz. area: 1.9 km<br />

Topology Line, tree, star Line, tree, ring, star Line, tree, star<br />

8<br />

9<br />

10<br />

11<br />

12<br />

Transmission media Unshielded two-wire cable Shielded two-wire cable Shielded two-wire cable<br />

Available degrees IP 20 IP 20 IP 20<br />

of protection IP 65 to IP 67 IP 65 to IP 67 IP 65 to IP 67<br />

[EEx ia]<br />

St<strong>and</strong>ard EN 50295 IEC 61158/EN 50170 IEC 61158-2<br />

Power supply via bus Yes No Yes<br />

Bus interface CP, integrated interface CP/IM, integrated inter-Link or segment coupler<br />

or link<br />

face or link<br />

14