Process or field communication<br />
Typical practice-related data<br />
The table below contains empirical<br />
values which are intended to<br />
serve as recommendation <strong>for</strong> the<br />
selection of the optimum<br />
network.<br />
AS-Interface PROFIBUS DP PROFIBUS PA<br />
1<br />
2<br />
Connectable • Binary inputs/outputs •Binary inputs/outputs •Field devices in Zone 1<br />
field devices • Analog inputs/outputs •Analog inputs/outputs hazardous area<br />
•Intelligent field devices, (type of protection: [EEx ia],<br />
e.g. drives, measuring explosive group: IIC)<br />
sensors, slaves with data •Non hazardous area<br />
preprocessing (such as (measuring transducer,<br />
ET 200X® or S7-300®, actuators or valves)<br />
SIMOTION®)<br />
Programming/ -Via PROFIBUS DP Via PROFIBUS DP<br />
commissioning with STEP 7 <strong>and</strong> PDM <strong>and</strong> PROFIBUS PA with the<br />
SIMATIC PDM (Process<br />
Device Manager) tool<br />
3<br />
Number of slaves<br />
• Max. 62 • Max. 125 • 125 DP/PA links<br />
• 15 typ. • 20 to 30 typ • 31 field devices per DP/PA link<br />
4<br />
5<br />
6<br />
7<br />
AS-i cycle time Max. 5 ms <strong>for</strong> 31 slaves --<br />
Max. 10 ms <strong>for</strong> 62 slaves<br />
Bus cycle time -2 ms at 12 Mbit/s typ. 200 ms at 31.25 kbit/s typ.<br />
10 ms at 1.5 Mbit/s typ.<br />
Network capacity Electrical: Electrical: up to 9.6 km Hazardous area: max. 1.0 km<br />
With/without repeater 100 m Optical: up to 90 km Non-haz. area: 1.9 km<br />
Topology Line, tree, star Line, tree, ring, star Line, tree, star<br />
8<br />
9<br />
10<br />
11<br />
12<br />
Transmission media Unshielded two-wire cable Shielded two-wire cable Shielded two-wire cable<br />
Available degrees IP 20 IP 20 IP 20<br />
of protection IP 65 to IP 67 IP 65 to IP 67 IP 65 to IP 67<br />
[EEx ia]<br />
St<strong>and</strong>ard EN 50295 IEC 61158/EN 50170 IEC 61158-2<br />
Power supply via bus Yes No Yes<br />
Bus interface CP, integrated interface CP/IM, integrated inter-Link or segment coupler<br />
or link<br />
face or link<br />
14