Industrial Communication for Automation and Drives - Induteq
Industrial Communication for Automation and Drives - Induteq
Industrial Communication for Automation and Drives - Induteq
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Fail-safe communication<br />
S7-300F with st<strong>and</strong>ard<br />
I/O <strong>and</strong> F I/O<br />
ET 200M with<br />
st<strong>and</strong>ard I/O<br />
Operator Panel<br />
The "PROFIsafe" protocol profile, developed<br />
<strong>for</strong> PROFIBUS DP, is used <strong>for</strong> communication<br />
between a fail-safe S7 CPU <strong>and</strong> the failsafe<br />
signal module.<br />
PROFIsafe features<br />
ET 200M with<br />
F I/O<br />
ET 200S with st<strong>and</strong>ard I/O, F I/O<br />
<strong>and</strong> F motor starter<br />
Laser scanner<br />
Light curtain<br />
PROFIsafe was the first communication<br />
st<strong>and</strong>ard based on IEC 61508 to allow<br />
st<strong>and</strong>ard communication <strong>and</strong> fail-safe<br />
communication on the same bus. With SIL<br />
3 (Safety Integrity Level 3), Category 4<br />
(EN 954-1), it fulfills the highest dem<strong>and</strong>s<br />
<strong>for</strong> the production <strong>and</strong> process industries,<br />
<strong>and</strong> with the PA version (IEC 61158-2),<br />
PROFIBUS DP exp<strong>and</strong>s the integrated<br />
distributed automation into the process<br />
world. PROFIsafe thus supports the different<br />
communication requirements of both the<br />
production <strong>and</strong> process industries.<br />
PROFIsafe functionality<br />
Fail-safe<br />
data<br />
St<strong>and</strong>ard<br />
data<br />
Fail-safe<br />
data<br />
St<strong>and</strong>ard<br />
data<br />
PROFIsafe counters the possibility of<br />
transmission errors due to problems such<br />
as address falsification, loss, delay, etc. with<br />
four different measures:<br />
PROFIsafelayer<br />
• Sequential numbering of the PROFIsafe<br />
data<br />
• Time monitoring<br />
St<strong>and</strong>ard<br />
PROFIBUS DP protocol<br />
St<strong>and</strong>ard<br />
PROFIBUS DP protocol<br />
Black channel=<br />
st<strong>and</strong>ard PROFIBUS<br />
• "Password"-based authenticity<br />
monitoring <strong>and</strong><br />
• An optimized version of CRC.<br />
Using slave nodes, fail-safe encoder signals<br />
from a PROFIBUS station are transmitted<br />
to the fail-safe CPU. When these encoder<br />
signals have been logically gated, an<br />
appropriate output signal is transmitted to<br />
a fail-safe PROFIBUS slave. Single-channel<br />
transmission is used, <strong>and</strong> there is no<br />
redundant transmission path.<br />
The fail-safe SIMATIC<br />
components are part of Safety<br />
Integrated, the Siemens<br />
safety program based on<br />
SIGUARD®, SIMATIC® <strong>and</strong><br />
SINUMERIK® / SIMODRIVE®<br />
products. The PROFIsafe<br />
protocol profile is used <strong>for</strong> failsafe<br />
communication on the<br />
PROFIBUS.<br />
27