Fail-safe communication<br />

S7-300F with st<strong>and</strong>ard<br />

I/O <strong>and</strong> F I/O<br />

ET 200M with<br />

st<strong>and</strong>ard I/O<br />

Operator Panel<br />

The "PROFIsafe" protocol profile, developed<br />

<strong>for</strong> PROFIBUS DP, is used <strong>for</strong> communication<br />

between a fail-safe S7 CPU <strong>and</strong> the failsafe<br />

signal module.<br />

PROFIsafe features<br />

ET 200M with<br />

F I/O<br />

ET 200S with st<strong>and</strong>ard I/O, F I/O<br />

<strong>and</strong> F motor starter<br />

Laser scanner<br />

Light curtain<br />

PROFIsafe was the first communication<br />

st<strong>and</strong>ard based on IEC 61508 to allow<br />

st<strong>and</strong>ard communication <strong>and</strong> fail-safe<br />

communication on the same bus. With SIL<br />

3 (Safety Integrity Level 3), Category 4<br />

(EN 954-1), it fulfills the highest dem<strong>and</strong>s<br />

<strong>for</strong> the production <strong>and</strong> process industries,<br />

<strong>and</strong> with the PA version (IEC 61158-2),<br />

PROFIBUS DP exp<strong>and</strong>s the integrated<br />

distributed automation into the process<br />

world. PROFIsafe thus supports the different<br />

communication requirements of both the<br />

production <strong>and</strong> process industries.<br />

PROFIsafe functionality<br />

Fail-safe<br />

data<br />

St<strong>and</strong>ard<br />

data<br />

Fail-safe<br />

data<br />

St<strong>and</strong>ard<br />

data<br />

PROFIsafe counters the possibility of<br />

transmission errors due to problems such<br />

as address falsification, loss, delay, etc. with<br />

four different measures:<br />

PROFIsafelayer<br />

• Sequential numbering of the PROFIsafe<br />

data<br />

• Time monitoring<br />

St<strong>and</strong>ard<br />

PROFIBUS DP protocol<br />

St<strong>and</strong>ard<br />

PROFIBUS DP protocol<br />

Black channel=<br />

st<strong>and</strong>ard PROFIBUS<br />

• "Password"-based authenticity<br />

monitoring <strong>and</strong><br />

• An optimized version of CRC.<br />

Using slave nodes, fail-safe encoder signals<br />

from a PROFIBUS station are transmitted<br />

to the fail-safe CPU. When these encoder<br />

signals have been logically gated, an<br />

appropriate output signal is transmitted to<br />

a fail-safe PROFIBUS slave. Single-channel<br />

transmission is used, <strong>and</strong> there is no<br />

redundant transmission path.<br />

The fail-safe SIMATIC<br />

components are part of Safety<br />

Integrated, the Siemens<br />

safety program based on<br />

SIGUARD®, SIMATIC® <strong>and</strong><br />

SINUMERIK® / SIMODRIVE®<br />

products. The PROFIsafe<br />

protocol profile is used <strong>for</strong> failsafe<br />

communication on the<br />

PROFIBUS.<br />

27