TGMS – Basis of <strong>Design</strong><br />

Basis of <strong>Design</strong>: Code Requirements + Best Practices<br />

• Sometimes… codes conflict with each other.<br />

▫<br />

For example:<br />

• NFPA 70 - 500.5 Classifications of Locations<br />

▫<br />

A. Classifications of Locations… “Where pyrophoric materials are the only materials<br />

used or handled, these locations shall not be classified.”<br />

• CGA G-13 Storage and Handling of Silane and Silane Mixtures<br />

▫<br />

▫<br />

▫<br />

16.1…Regardless of the provisions in the NEC that allow the use of unclassified<br />

electrical equipment where pyrophoric materials are used, electrical equipment shall<br />

be classified in accordance with the requirements of Tables 7 and 8 (e.g., pressurizing<br />

& Z-purge, Class 1, Division 2 wiring requirements…)<br />

11.1 <strong>Gas</strong> <strong>Monitoring</strong> – required for enclosure exhaust ventilation<br />

11.2 Flame detection – required for gas cabinets, VMBs and open manifold assemblies<br />

with un-welded fittings…<br />