TGMS – Basis of <strong>Design</strong><br />
Basis of <strong>Design</strong>: Code Requirements + Best Practices<br />
• Sometimes… codes conflict with each other.<br />
▫<br />
For example:<br />
• NFPA 70 - 500.5 Classifications of Locations<br />
▫<br />
A. Classifications of Locations… “Where pyrophoric materials are the only materials<br />
used or handled, these locations shall not be classified.”<br />
• CGA G-13 Storage and Handling of Silane and Silane Mixtures<br />
▫<br />
▫<br />
▫<br />
16.1…Regardless of the provisions in the NEC that allow the use of unclassified<br />
electrical equipment where pyrophoric materials are used, electrical equipment shall<br />
be classified in accordance with the requirements of Tables 7 and 8 (e.g., pressurizing<br />
& Z-purge, Class 1, Division 2 wiring requirements…)<br />
11.1 <strong>Gas</strong> <strong>Monitoring</strong> – required for enclosure exhaust ventilation<br />
11.2 Flame detection – required for gas cabinets, VMBs and open manifold assemblies<br />
with un-welded fittings…<br />