D4.2 – D4.6<br />
D<br />
g. laboratories;<br />
h. lift motor rooms;<br />
i. linen stores;<br />
j. bedrooms in a building other than a hospital;<br />
k. bedrooms in a hospital where they are used by -<br />
i. elderly people, or<br />
ii.<br />
iii.<br />
those suffering with mental illness, or<br />
people with learning difficulties;<br />
l. kitchens (other than separate hospital departments);<br />
m. laundry rooms;<br />
n. staff changing and locker rooms;<br />
o. store rooms;<br />
p. X-ray film and record stores; and<br />
q. all rooms within a main laundry in which delivery, sorting, processing packing and storing are<br />
carried out.<br />
D4.3 In a building of purpose sub-group 2A no room containing sleeping accommodation shall be intended<br />
for use by more than 4 people,<br />
except -<br />
HOSPITALS<br />
in a hospital.<br />
D4.4 In a hospital every intensive therapy unit must be divided into at least 2 sub-compartments by subcompartment<br />
walls with a level of fire safety performance (see D1.3) with a short duration.<br />
D4.5 In a hospital every entrance to an intensive therapy unit must be either -<br />
a. from a hospital street (see E8.9); or<br />
b. through a lobby, enclosed with the same level of fire safety performance as that required for a subcompartment.<br />
BUILDINGS OF PURPOSE SUB-GROUP 2B<br />
D4.6 In order to aid evacuation and to limit fire spread, in a building of purpose sub-group 2B, each room<br />
containing sleeping accommodation (including any en-suite sanitary accommodation where provided)<br />
must be enclosed with the same level of fire safety performance as that required for a sub-compartment,<br />
except -<br />
a. for a wall between such rooms. and<br />
b. in the case of a place of lawful detention.<br />