D<br />

D2.3<br />

NON-COMBUSTIBLE MATERIALS<br />

D2.3 Where an element of structure provides support to a separating floor (see D5.6), a separating wall (see<br />

D5.7), an external wall (see D8.2), or an escape stair (including the floor of a protected lobby) (see<br />

D11.12) which is required to be of materials which are non-combustible, the element of structure must<br />

also be of materials which are non-combustible (see D1.3).<br />

Table 1 to D2.1: Minimum duration and maximum compartment area in a single storey building<br />

Purpose groups and purpose sub-groups Maximum area of a Minimum duration of Minimum<br />

compartment (m 2 ) compartmentation, duration of<br />

[1] where required external walls<br />

(see D3.1)<br />

(see D8.1)<br />

1 Dwellings Unlimited Not required Medium [2, 3]<br />

2A Institutional 1,500 Medium Medium [3]<br />

2B Other residential 2,000 Medium Medium [3]<br />

3 Offices 4,000 Medium Medium [3]<br />

4 Shops and commercial 2,000 [4] Long Medium [5]<br />

5A Assembly and recreational (high risk) 2,000 Medium Medium [5]<br />

5B Assembly and recreational (low risk) 6,000 Long Medium [3]<br />

6A Industrial (high risk) 33,000 Long Medium [5]<br />

6B Industrial (low risk) 93,000 Long Medium [3]<br />

7A Storage (high risk) 1,000 Long [6] Medium [5]<br />

7B Storage (low risk) 14,000 Long Medium [5]<br />

7C Open-sided car park Unlimited Not required Not required<br />

Notes:<br />

1. In a building of purpose groups 3 and 5-7 areas can be doubled where there is an appropriate fire<br />

control system.<br />

2. Short duration for -<br />

a. a dwelling with an appropriate fire control system;<br />

b. a detached building ancillary to a dwelling comprising a garden hut or store, or a building for<br />

keeping animals, birds or other livestock for domestic purposes;<br />

c. a conservatory or porch attached to a dwelling;<br />

d. a garage wall.<br />

3. Short duration for a building more than 1 m from the boundary.<br />

4. Unlimited provided there is an appropriate fire control system.<br />

5. Short duration for a building more than 1 m from the boundary which has an appropriate fire<br />

control system.<br />

6. A building comprising a single compartment of not more than 1000 m 2 is permitted. Where a<br />

building has a floor area more than this, it must be divided into a series of compartments so that no<br />

compartment is more than 200 m 2 if the compartment walls have a medium duration, or 500m 2 if<br />

the compartment walls have a long duration.<br />