D<br />
D6.7 – 7.1<br />
c. for a service opening -<br />
i. which is of suitable construction, or where the services are suitably protected, so that in the<br />
event of fire, the level of fire safety performance required is maintained, and<br />
ii.<br />
where it is suitably fire-stopped.<br />
JUNCTIONS<br />
D6.8 Where a wall, floor or other part of a building which is required to have a level of fire safety performance,<br />
abuts a structure containing a cavity, a cavity barrier with a level of fire safety performance (see<br />
D1.3) with a short duration must be installed so as to extend the line of the structure with the level of<br />
fire safety performance,<br />
except -<br />
a. a cavity formed by two leaves of masonry or concrete at least 75 mm thick; or<br />
b. a cavity formed by overcladding, both surfaces of which are non-combustible or low risk materials,<br />
attached to a masonry or concrete external wall or a concrete roof and the cavity contains only noncombustible<br />
materials; or<br />
c. in the case of a wall which is required to have a level of fire safety performance only because it is<br />
loadbearing.<br />
D6.9* A cavity barrier must be tightly fitted to rigid construction, or where this is not possible (for example, in<br />
the case of a junction with slates, tiles, corrugated sheeting or similar materials) the junction must be<br />
suitably fire-stopped.<br />
D6.10 A cavity barrier must be fixed so that its performance is not affected by -<br />
a. movement of the building due to subsidence, shrinkage or thermal change;<br />
b. collapse in a fire of any services penetrating it;<br />
c. failure in a fire of its fixings;<br />
d. failure in a fire of any material or element of structure which it abuts,<br />
except -<br />
where a cavity barrier is installed between a roof and a ceiling, there is no requirement to protect<br />
roof members supporting the cavity barrier.<br />
D7 Fire spread on internal linings<br />
PRINCIPLES<br />
D7.1* In order to resist the spread of fire and smoke, every room, fire-fighting shaft, protected zone or unprotected<br />
zone, must have wall and ceiling surfaces with a level of fire safety performance (see D1.3) which<br />
meet the requirements of the table to this standard,<br />
excepta.<br />
in a room any part of the wall may be of one risk category higher than that required (but not very<br />
high risk) where the total area of those parts in any 1 room is not more than either half the floor<br />
Amdt: September 2001<br />