NRDA F-1- Schedule-D- Section III- Technical Specification of Works<br />

Construction of Forest and Water Resources department buildings, North Block at <strong>Naya</strong> <strong>Raipur</strong><br />

NRDA<br />

B. HIGH TENSION CABLES<br />

1. General<br />

The high tension cables used in this assignment shall be three core aluminum conductors. The<br />

conductor of the cable will be made from multistranding of round wires of high purity, high<br />

conductivity, electrical grade aluminium. The cables shall confirm to IS: 7098 (latest edition) and<br />

the following details.<br />

2. Rating<br />

The cables shall be rated for use an earthed 33 KV system and should stand 17 KV for 5 minutes with<br />

insulation break.<br />

3. Core identification<br />

Cores shall be identified by numbers 1, 2 & 3 printed on the insulating.<br />

4.a)<br />

Insulation<br />

The cable will have high quality cross linked Poly Urethane, unfilled compound insulation extruded<br />

over the conductor by a continuous vulcanizing process having arrangement for chemical cross linking<br />

of the compound.<br />

b) Shielding<br />

To avoid electrical point stresses the conductor and the outer surface of the insulation layer should<br />

be shielded by a semi-conducting compound.<br />

c) Inner Sheathing<br />

The insulated conductor and the non hydroscopic gap fillers will be enveloped in either an extruded<br />

layer of compound .<br />

d) Aumouring<br />

Over the sheath a layer of hot dipped galvanised steel strips will be laid to provide the armouring to<br />

the cable. To avoid the armour heating due to induced currents the armouring should be of non<br />

magnetic metal like aluminium or copper alloys in case of single core cables.<br />

e) Outer Shielding<br />

To protect and fix the armouring and to make the handling easy a tough black coloured stabilized<br />

weather resisting grade of PVC is to be extruded over the cable.<br />

5. Current Rating:<br />

The current rating shall be based on the following conditions.<br />

Page 14 of 174