Transition Plan


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

2-Stairway Handrails:<br />

West Entrance to <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

4-Doors: West Entrance<br />

to <strong>Pierce</strong> <strong>Annex</strong>. [One<br />

set of double doors.]<br />

Rails are 34" - 38" above stair nosing. 12"<br />

minimum level extension beyond top nosing<br />

(parallel with the ground or floor surface) before<br />

being returned. 12" plus one tread width level<br />

extension beyond bottom nosing (parallel with<br />

the ground or floor surface) before being<br />

returned.<br />

5 lb. maximum pressure to operate exterior<br />

doors.<br />

Raise existing handrail height.<br />

Install top and bottom<br />

extensions to existing handrail.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $6,392.39<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

6-Signage: <strong>Pierce</strong> <strong>Annex</strong><br />

1st Floor.<br />

7-Tactile Exit Signage:<br />

<strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />

8-Floors and Levels:<br />

<strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />

[Four carpets / mats.]<br />

9-Doors: Unisex<br />

Restroom to the Left on<br />

the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each exit door that leads directly to a gradelevel<br />

exterior exit by means of a stairway or<br />

ramp is identified by a tactile exit sign that states<br />

"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />

"EXIT STAIR UP", or "EXIT RAMP UP", as<br />

appropriate.<br />

Carpets or carpet tiles are securely attached<br />

and do not exceed 1/2" in height. Carpet's<br />

exposed edges are fastened to floor surfaces<br />

and have trim along entire length.<br />

5 lb. maximum pressure to operate interior<br />

doors. 3 seconds minimum for door closer to<br />

close from 70 degree position to within 3" of the<br />

latch [ADAAG 404.2.8.1 Door & gate closers<br />

require a 5 second minimum closing time from<br />

open position of 90 degree to 12 degree<br />

position].<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

Secure loose doormat. 1 $980.02<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

6/1/2012 Page 1 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

11-Identification<br />

Symbols, Restrooms:<br />

Unisex Restroom to the<br />

Left on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Unisex - 12" diameter circle 1/4" thick with 1/4"<br />

thick triangle superimposed in the circle. The<br />

circle and triangle symbols contrasts with the<br />

door, light on dark background or dark on light<br />

background [CBC 1115B.6 The triangle shall<br />

contrast w the circle and the circle shall contrast<br />

with the door]. Wall mounted signage: Symbol of<br />

accessibility is mounted on wall sign adjacent to<br />

latch side of door [ADAAG 703.6.1 & CBC<br />

1117B.5.5 Item 4 Pictograms shall have a field<br />

height of 6" ADAAG 703.6.1 Characters and<br />

Braille shall not be located in the pictogram<br />

field]. Verbal description as to restroom usage is<br />

placed directly below the pictogram, if utilized in<br />

conjunction with verbal identification and the<br />

border dimensions of this pictogram is a<br />

minimum of 6" in height.<br />

Install door-mounted sign on<br />

single door. Install wallmounted<br />

sign at single<br />

entrance.<br />

3 $367.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

12-Single<br />

Accommodation Toilet:<br />

Unisex Restroom to the<br />

Left on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

60" minimum diameter turning circle, or a T-<br />

shaped clear space, is provided in room with 12"<br />

maximum door encroachment into the required<br />

clear space. A minimum 60" wide and 48" deep<br />

clear floor space is provided in front of water<br />

closet. Front of toilet paper dispenser is within<br />

36" of the back wall. The toilet paper dispenser<br />

is located on the side wall below the grab bar<br />

and within 7" - 9" of the front of the toilet seat as<br />

measured to the centerline of the dispenser.<br />

Requires<br />

engineering/architectural<br />

evaluation. Relocate the toilet<br />

paper dispenser away from the<br />

top of the grab bar.<br />

3 $7,238.13<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

13-Toilet Grab Bars:<br />

Unisex Restroom to the<br />

Left on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>. [See<br />

Sequence #12 for<br />

additional actions.]<br />

14-Lavatories: Unisex<br />

Restroom to the Left on<br />

the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

The front of the side grab bar extends 54" from<br />

back wall in single accommodation stall. Area<br />

directly above grab bars or proposed grab bars<br />

is free of protruding obstructions to a height of<br />

18" (recessed items are allowed).<br />

18" minimum from center of fixture to side wall<br />

or partition.<br />

Relocate side grab bar.<br />

Relocate the seat cover<br />

dispenser away from the top of<br />

the grab bar.<br />

Replace with accessible<br />

lavatory.<br />

3 $367.51<br />

3 $3,185.07<br />

6/1/2012 Page 2 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

15-Accessories: Unisex<br />

Restroom to the Left on<br />

the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>. [See Sequence<br />

#12 and #13 for<br />

additional actions. Soap<br />

dispenser - 44" high /<br />

seat cover dispenser -<br />

48" high / paper towel<br />

dispenser - 45" high /<br />

toilet paper dispenser -<br />

42-1/2" high.]<br />

40" max. height to all other fixtures (i.e., soap<br />

dispensers, towels, toilet seat covers, auto<br />

dryers, sanitary napkins, waste recepatacles,<br />

etc.). Coat hooks and shelving are located within<br />

appropriate reach ranges (48" max. height<br />

above floor surface is recommended). A<br />

minimum 30" x 48" minimum clear floor or<br />

ground space is provided to allow forward or<br />

parallel approach to accessories.<br />

Install accessible coat hook.<br />

Lower the soap dispenser.<br />

Lower the paper towel<br />

dispenser.<br />

3 $367.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

16-Visual/Audible<br />

Alarms: Unisex<br />

Restroom to the Left on<br />

the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

18-Doors: Unisex<br />

Restroom to the Right<br />

on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong> .<br />

20-Identification<br />

Symbols, Restrooms:<br />

Unisex Restroom to the<br />

Right on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

The appliance is placed 80" above the highest<br />

floor level within the space or 6" below the<br />

ceiling, whichever is lower.<br />

5 lb. maximum pressure to operate interior<br />

doors. 3 seconds minimum for door closer to<br />

close from 70 degree position to within 3" of the<br />

latch [ADAAG 404.2.8.1 Door & gate closers<br />

require a 5 second minimum closing time from<br />

open position of 90 degree to 12 degree<br />

position].<br />

Unisex - 12" diameter circle 1/4" thick with 1/4"<br />

thick triangle superimposed in the circle. The<br />

circle and triangle symbols contrasts with the<br />

door, light on dark background or dark on light<br />

background [CBC 1115B.6 The triangle shall<br />

contrast w the circle and the circle shall contrast<br />

with the door]. Wall mounted signage: Symbol of<br />

accessibility is mounted on wall sign adjacent to<br />

latch side of door [ADAAG 703.6.1 & CBC<br />

1117B.5.5 Item 4 Pictograms shall have a field<br />

height of 6" ADAAG 703.6.1 Characters and<br />

Braille shall not be located in the pictogram<br />

field]. Verbal description as to restroom usage is<br />

placed directly below the pictogram, if utilized in<br />

conjunction with verbal identification and the<br />

border dimensions of this pictogram is a<br />

minimum of 6" in height.<br />

Review entire alarm system. 1 $7,115.62<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

Install door-mounted sign on<br />

single door. Install wallmounted<br />

sign at single<br />

entrance.<br />

2 $306.26<br />

3 $367.51<br />

6/1/2012 Page 3 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

21-Single<br />

Accommodation Toilet:<br />

Unisex Restroom to the<br />

Right on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

A minimum 60" wide and 48" deep clear floor<br />

space is provided in front of water closet. Front<br />

of toilet paper dispenser is within 36" of the back<br />

wall. The toilet paper dispenser is located on the<br />

side wall below the grab bar and within 7" - 9" of<br />

the front of the toilet seat as measured to the<br />

centerline of the dispenser.<br />

Requires<br />

engineering/architectural<br />

evaluation. Relocate the toilet<br />

paper dispenser away from the<br />

top of the grab bar.<br />

3 $7,238.13<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

22-Toilet Grab Bars:<br />

Unisex Restroom to the<br />

Right on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>. [See<br />

Sequence #21 for<br />

additional actions.]<br />

23-Lavatories: Unisex<br />

Restroom to the Right<br />

on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

24-Accessories: Unisex<br />

Restroom to the Right<br />

on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>. [See<br />

Sequence #21 and #22<br />

for additional actions.<br />

Soap dispenser - 43" /<br />

seat cover dispenser -<br />

48" / paper towel<br />

dispenser - 45" / toilet<br />

paper dispenser - 42-<br />

1/4".]<br />

28-Water Fountains<br />

(Drinking): 1st Floor<br />

Corridor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

33-Clear Space at<br />

Doors: 1st Floor Rooms<br />

#124, #123, #103 and<br />

#102 at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Four office doors.]<br />

The front of the side grab bar extends 54" from<br />

back wall in single accommodation stall. Area<br />

directly above grab bars or proposed grab bars<br />

is free of protruding obstructions to a height of<br />

18" (recessed items are allowed).<br />

18" minimum from center of fixture to side wall<br />

or partition.<br />

40" max. height to all other fixtures (i.e., soap<br />

dispensers, towels, toilet seat covers, auto<br />

dryers, sanitary napkins, waste recepatacles,<br />

etc.). Coat hooks and shelving are located within<br />

appropriate reach ranges (48" max. height<br />

above floor surface is recommended). A<br />

minimum 30" x 48" minimum clear floor or<br />

ground space is provided to allow forward or<br />

parallel approach to accessories.<br />

Stream of bubbler is parallel to front edge. The<br />

force required to activate controls does not<br />

exceed 5lbf.<br />

60" min. clear space in direction of door swing.<br />

Minimum strike side clearance on PULL side of<br />

door: 18" wide x 60" depth at interior doors, front<br />

approach.<br />

Relocate side grab bar.<br />

Relocate the seat cover<br />

dispenser away from the top of<br />

the grab bar.<br />

Replace with accessible<br />

lavatory.<br />

Install accessible coat hook.<br />

Lower the soap dispenser.<br />

Adjust angle of stream.<br />

Reduce force needed to<br />

operate fountain controls ( 5 lb.<br />

maximum).<br />

Relocate furniture to provide<br />

clear space. University staff<br />

shall be instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

Relocate restricting objects.<br />

3 $367.51<br />

3 $3,185.07<br />

3 $245.01<br />

2 $551.26<br />

1M $428.77<br />

6/1/2012 Page 4 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

34-Signage: 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate existing signage. 3 $980.02<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

35-Doors: Room #107<br />

on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

36-Clear Space at<br />

Doors: Room #107 on<br />

the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

37-Signage: Room #107<br />

on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Interior<br />

door inside of Room<br />

#107.]<br />

39-Clear Space at<br />

Doors: Behind Room<br />

#107 Toward Lab on the<br />

1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

40-Sales and Service<br />

Counters: Room #106<br />

on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Minimum strike side clearance on PUSH side of<br />

door: 12" front approach with latch and closer.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate furniture to provide<br />

clear space. University staff shall<br />

be instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

1M $61.25<br />

Relocate existing signage. 3 $490.00<br />

Minimum strike side clearance on PULL side of Relocate furniture to provide 1M $61.25<br />

door: 18" wide x 60" depth at interior doors, front clear space. University staff shall<br />

approach.<br />

be instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

Knee space at table(s) is at least 27" high, 30" Install accessible counter. 2 $1,592.53<br />

wide and extends 19" under the table(s) and;<br />

6/1/2012 Page 5 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

41-Sinks: Room #106 on<br />

the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Minimum 30" x 48" clear space is provided in<br />

front of sink that allows forward approach. 34"<br />

maximum height of rim or counter above floor<br />

surfaces. Sink is a maximum of 6-1/2" deep.<br />

Knee clearance under sink is a minimum of 27"<br />

high and 30" wide, and provides an absolute<br />

depth of 19" underneath the sink [ADAAG 606.2<br />

Exception 6 The dip of the overflow shall not be<br />

considered in determining knee and toe<br />

clearance]. Drain and hot water piping is<br />

insulated or configured to prevent contact.<br />

Replace with accessible sink.<br />

Insulate pipes under lavatory<br />

sink. Cut the paneling under<br />

the sink counter to comply with<br />

knee clearance.<br />

3 $3,920.09<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

44-Controls, Operating<br />

Mechanisms & Vending<br />

Machines.: Room #106<br />

on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />

hood.]<br />

Forward Reach to Objects: Highest operable<br />

part of object is a maximum of 48" above the<br />

floor surface.<br />

Replace the fume hood with an<br />

accessible fume hood<br />

workstation.<br />

3 $18,216.00 Until such time<br />

as accessible<br />

furniture /<br />

stations are<br />

available in this<br />

room staff shall<br />

be informed of<br />

the immediate<br />

availability of<br />

accessible<br />

furniture /<br />

stations that<br />

may be placed<br />

in the room to<br />

meet the needs<br />

of people with<br />

disabilities.<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

46-Protruding Objects:<br />

Room #106 on the 1st<br />

Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Fume hood.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $245.01<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

47-Protruding Objects:<br />

Room #106 on the 1st<br />

Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Power control boxes.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $980.02<br />

6/1/2012 Page 6 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

48-Protruding Objects:<br />

Room #106 on the 1st<br />

Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Emergency eyewash.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $122.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

50-Doors: Room #111<br />

on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>. [One set<br />

of double doors.]<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

52-Signage: Room #111<br />

on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate existing signage. 3 $245.01<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

54-Doors: Door to<br />

Courtyard from Room<br />

#111 on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

32" minimum clear width of doorway. 5 lb.<br />

maximum pressure to operate exterior doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted<br />

by DSA Fire / Life Safety.<br />

Consider issues connected<br />

with building pressure / climate<br />

control. Replace door and<br />

frame (concrete or block wall).<br />

2 $5,573.87<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

56-Signage: Door to<br />

Courtyard from Room<br />

#111 on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

57-Elevators: Southeast<br />

Side at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

68" min. width of the car platform with off-center<br />

door panels. Elevator doors have an automatic<br />

reopening device. The device opens the doors<br />

when objects pass through the opening at<br />

heights of 5" and 29" from the floor without<br />

requiring contact. Doors remain open for 20<br />

seconds minimum. At the grade level, a raised<br />

five-pointed star with an outside diameter of 2" is<br />

placed to the left of the raised character.<br />

Install permanent ID sign to<br />

latch side of door.<br />

Requires<br />

engineering/architectural<br />

evaluation. Repair door<br />

operation. Provide a raised five<br />

pointed star at the ground<br />

level.<br />

1 $183.75<br />

1 $9,606.09<br />

6/1/2012 Page 7 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

60-Doors: Southeast<br />

Entrance on the 1st<br />

Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

[One set of double<br />

doors.]<br />

32" minimum clear width of doorway. 5 lb.<br />

maximum pressure to operate exterior doors.<br />

The international symbol of accessibility is<br />

posted at all primary entrances.<br />

Replace door(s) and frame<br />

(stud wall). Adjust door<br />

opening pressure / closing time<br />

unless accepted by DSA Fire /<br />

Life Safety. Consider issues<br />

connected with building<br />

pressure / climate control. Post<br />

a sign/decal displaying the<br />

"International Symbol of<br />

Accessibility" at the primary<br />

entrance.<br />

2 $3,466.84<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

62-Stairways: Southeast<br />

Entrance on the 1st<br />

Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Two staircases.]<br />

All steps have uniform riser height and tread<br />

width.<br />

Replace existing steps. 2 $30,135.81<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

63-Stairway Handrails:<br />

Southeast Entrance on<br />

the 1st Floor to <strong>Pierce</strong><br />

<strong>Annex</strong>. [Two stair<br />

cases.]<br />

64-Doors: Room #109<br />

on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Rails are 34" - 38" above stair nosing. 12"<br />

minimum level extension beyond top nosing<br />

(parallel with the ground or floor surface) before<br />

being returned. 12" plus one tread width level<br />

extension beyond bottom nosing (parallel with<br />

the ground or floor surface) before being<br />

returned.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Raise existing handrail height. 2 $16,280.55<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

66-Signage: Room #109<br />

on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate existing signage. 3 $245.01<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

68-Sinks: Room #109 on<br />

the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Knee clearance under sink is a minimum of 27"<br />

high and 30" wide, and provides an absolute<br />

depth of 19" underneath the sink [ADAAG 606.2<br />

Exception 6 The dip of the overflow shall not be<br />

considered in determining knee and toe<br />

clearance].<br />

Insulate pipes under sink. Cut<br />

the paneling under the sink<br />

counter to comply with knee<br />

clearance.<br />

3 $735.02<br />

6/1/2012 Page 8 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

69-Controls, Operating<br />

Mechanisms & Vending<br />

Machines.: Room #109<br />

on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Paper<br />

towel dispenser.]<br />

Forward Reach to Objects: Highest operable<br />

part of object is a maximum of 48" above the<br />

floor surface.<br />

Relocate existing paper towel<br />

dispenser.<br />

3 $122.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

73-Doors: Room #104<br />

on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

74-Clear Space at<br />

Doors: Room #104 on<br />

the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Minimum strike side clearance on PULL side of<br />

door: 18" wide x 60" depth at interior doors, front<br />

approach. Minimum strike side clearance on<br />

PUSH side of door: 12" front approach with latch<br />

and closer.<br />

Relocate furniture to provide<br />

clear space. University staff<br />

shall be instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces. Modify<br />

door to swing opposite hand.<br />

2 $551.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

75-Signage: Room #104<br />

on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate existing signage. 3 $245.01<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

77-Sinks: Room #105 on<br />

the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Minimum 30" x 48" clear space is provided in<br />

front of sink that allows forward approach. Sink<br />

is a maximum of 6-1/2" deep. Knee clearance<br />

under sink is a minimum of 27" high and 30"<br />

wide, and provides an absolute depth of 19"<br />

underneath the sink [ADAAG 606.2 Exception 6<br />

The dip of the overflow shall not be considered<br />

in determining knee and toe clearance]. Drain<br />

and hot water piping is insulated or configured to<br />

prevent contact.<br />

Replace with accessible sink.<br />

Insulate pipes under sink. Cut<br />

the paneling under the sink<br />

counter to comply with knee<br />

clearance.<br />

3 $3,920.09<br />

6/1/2012 Page 9 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

79-Controls, Operating<br />

Mechanisms & Vending<br />

Machines.: Room #105<br />

on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

[Thermogravimetric<br />

analyzer.]<br />

81-Seating, Tables and<br />

Work Surfaces: Room<br />

#105 on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />

hood.]<br />

Forward Reach to Objects: Highest operable<br />

part of object is a maximum of 48" above the<br />

floor surface.<br />

27" high, 30" wide and 19" deep knee clearance<br />

provided. 28" - 34" height of table or work<br />

surface that is 36" wide.<br />

Lower the machine. 1M $61.25<br />

Replace the fume hood with an<br />

accessible fume hood<br />

workstation.<br />

3 $18,216.00 Until such time<br />

as accessible<br />

furniture /<br />

stations are<br />

available in this<br />

room staff shall<br />

be informed of<br />

the immediate<br />

availability of<br />

accessible<br />

furniture /<br />

stations that<br />

may be placed<br />

in the room to<br />

meet the needs<br />

of people with<br />

disabilities.<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

82-Protruding Objects:<br />

Room #105 on the 1st<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Fume hood.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $245.01<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

83-Aisles: Room #105<br />

on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

36" minimum width of aisles. Requires<br />

engineering/architectural<br />

evaluation.<br />

2 $7,115.62<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

84-Protruding Objects:<br />

Room #105 on the 1st<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Emergency eye wash.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $122.51<br />

6/1/2012 Page 10 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

85-Doors: Room #105<br />

and Room #106 on the<br />

1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. [Three doors.]<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $612.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

87-Signage: Room #105<br />

and Room #106 on the<br />

1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

88-Doors: North<br />

Stairwell on the 1st Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

32" minimum clear width of doorway. 5 lb.<br />

maximum pressure to operate interior doors.<br />

Relocate existing signage. 3 $490.00<br />

Adjust door opening pressure /<br />

closing time unless accepted<br />

by DSA Fire / Life Safety.<br />

Consider issues connected<br />

with building pressure / climate<br />

control. Replace door and<br />

frame (concrete or block wall).<br />

2 $5,573.87<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

90-Signage: North<br />

Stairwell on the 1st Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>.<br />

91-Tactile Exit Signage:<br />

North Stairwell on the<br />

1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

92-Doors: Stairwell to<br />

Outside on the 1st Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>. [Exit<br />

only door.]<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each exit door that leads directly to a gradelevel<br />

exterior exit by means of a stairway or<br />

ramp is identified by a tactile exit sign that states<br />

"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />

"EXIT STAIR UP", or "EXIT RAMP UP", as<br />

appropriate.<br />

5 lb. maximum pressure to operate exterior<br />

doors.<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

95-Stairway Handrails:<br />

North Stairwell on the<br />

1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Rails are 34" - 38" above stair nosing. 12"<br />

minimum level extension beyond top nosing<br />

(parallel with the ground or floor surface) before<br />

being returned. 12" plus one tread width level<br />

extension beyond bottom nosing (parallel with<br />

the ground or floor surface) before being<br />

returned.<br />

Raise existing handrail height. 2 $5,879.79<br />

6/1/2012 Page 11 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

97-Hazards: North<br />

Stairwell on the 1st Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>.<br />

98-Doors: North<br />

Entrance on the 1st<br />

Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

[One set of double<br />

doors.]<br />

Any obstrution that overhangs a pedestrian way<br />

is a minimum 80" above the walking surface<br />

(measured from the bottom of the obstruction).<br />

Sidewalks are clear of hazards. If vertical<br />

clearance of an area adjoining an accessible<br />

route is reduced to less than 80", a barrier to<br />

warn blind or visually impaired persons is<br />

provided.<br />

5 lb. maximum pressure to operate exterior<br />

doors.<br />

Install cane detectable barrier<br />

below stairwell.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

1 $980.02<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

100-Signage: North<br />

Entrance on the 1st<br />

Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

101-Tactile Exit<br />

Signage: North Entrance<br />

on the 1st Floor to<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

102-Doors: West<br />

Entrance on the 2nd<br />

Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

[One set of double<br />

doors.]<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each grade-level exterior exit door shall be<br />

identified by a tactile sign with the word "EXIT".<br />

5 lb. maximum pressure to operate exterior<br />

doors.<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

104-Signage: West<br />

Entrance on the 2nd<br />

Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

105-Tactile Exit<br />

Signage: West Entrance<br />

on the 2nd Floor to<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each exit door that leads directly to a gradelevel<br />

exterior exit by means of a stairway or<br />

ramp is identified by a tactile exit sign that states<br />

"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />

"EXIT STAIR UP", or "EXIT RAMP UP", as<br />

appropriate.<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

6/1/2012 Page 12 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

106-Doors: Unisex<br />

Restroom to the Left on<br />

the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

108-Identification<br />

Symbols, Restrooms:<br />

Unisex Restroom to the<br />

Left on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Unisex - 12" diameter circle 1/4" thick with 1/4"<br />

thick triangle superimposed in the circle. The<br />

circle and triangle symbols contrasts with the<br />

door, light on dark background or dark on light<br />

background [CBC 1115B.6 The triangle shall<br />

contrast w the circle and the circle shall contrast<br />

with the door]. Wall mounted signage: Symbol of<br />

accessibility is mounted on wall sign adjacent to<br />

latch side of door [ADAAG 703.6.1 & CBC<br />

1117B.5.5 Item 4 Pictograms shall have a field<br />

height of 6" ADAAG 703.6.1 Characters and<br />

Braille shall not be located in the pictogram<br />

field]. Verbal description as to restroom usage is<br />

placed directly below the pictogram, if utilized in<br />

conjunction with verbal identification and the<br />

border dimensions of this pictogram is a<br />

minimum of 6" in height.<br />

Install door-mounted sign on<br />

single door. Install wallmounted<br />

sign at single<br />

entrance.<br />

3 $367.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

109-Single<br />

Accommodation Toilet:<br />

Unisex Restroom to the<br />

Left on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

110-Toilet Grab Bars:<br />

Unisex Restroom to the<br />

Left on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [See<br />

Sequence #109 for<br />

additional actions.]<br />

111-Lavatories: Unisex<br />

Restroom to the Left on<br />

the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

60" minimum diameter turning circle, or a T-<br />

shaped clear space, is provided in room with 12"<br />

maximum door encroachment into the required<br />

clear space. A minimum 60" wide and 48" deep<br />

clear floor space is provided in front of water<br />

closet. Front of toilet paper dispenser is within<br />

36" of the back wall.<br />

The front of the side grab bar extends 54" from<br />

back wall in single accommodation stall. Area<br />

directly above grab bars or proposed grab bars<br />

is free of protruding obstructions to a height of<br />

18" (recessed items are allowed).<br />

18" minimum from center of fixture to side wall<br />

or partition. 34" max. height to rim or counter<br />

above floor surface.<br />

Requires<br />

engineering/architectural<br />

evaluation. Relocate the toilet<br />

paper dispenser away from the<br />

top of the grab bar.<br />

Relocate side grab bar.<br />

Relocate the seat cover<br />

dispenser away from the top of<br />

the grab bar.<br />

Replace with accessible<br />

lavatory.<br />

3 $7,238.13<br />

3 $367.51<br />

3 $3,185.07<br />

6/1/2012 Page 13 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

112-Accessories: Unisex<br />

Restroom to the Left on<br />

the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. [See Sequence<br />

#109 and #110 for<br />

additional actions.]<br />

40" max. height to all other fixtures (i.e., soap<br />

dispensers, towels, toilet seat covers, auto<br />

dryers, sanitary napkins, waste recepatacles,<br />

etc.). Coat hooks and shelving are located within<br />

appropriate reach ranges (48" max. height<br />

above floor surface is recommended).<br />

Install accessible coat hook.<br />

Lower the soap dispenser.<br />

Lower the paper towel<br />

dispenser.<br />

3 $367.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

113-Doors: Unisex<br />

Restroom to the Right<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

115-Identification<br />

Symbols, Restrooms:<br />

Unisex Restroom to the<br />

Right on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Unisex - 12" diameter circle 1/4" thick with 1/4"<br />

thick triangle superimposed in the circle. The<br />

circle and triangle symbols contrasts with the<br />

door, light on dark background or dark on light<br />

background [CBC 1115B.6 The triangle shall<br />

contrast w the circle and the circle shall contrast<br />

with the door]. Wall mounted signage: Symbol of<br />

accessibility is mounted on wall sign adjacent to<br />

latch side of door [ADAAG 703.6.1 & CBC<br />

1117B.5.5 Item 4 Pictograms shall have a field<br />

height of 6" ADAAG 703.6.1 Characters and<br />

Braille shall not be located in the pictogram<br />

field]. Verbal description as to restroom usage is<br />

placed directly below the pictogram, if utilized in<br />

conjunction with verbal identification and the<br />

border dimensions of this pictogram is a<br />

minimum of 6" in height.<br />

Install door-mounted sign on<br />

single door. Install wallmounted<br />

sign at single<br />

entrance.<br />

3 $367.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

116-Single<br />

Accommodation Toilet:<br />

Unisex Restroom to the<br />

Right on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

60" minimum diameter turning circle, or a T-<br />

shaped clear space, is provided in room with 12"<br />

maximum door encroachment into the required<br />

clear space. A minimum 60" wide and 48" deep<br />

clear floor space is provided in front of water<br />

closet. Front of toilet paper dispenser is within<br />

36" of the back wall. The toilet paper dispenser<br />

is located on the side wall below the grab bar<br />

and within 7" - 9" of the front of the toilet seat as<br />

measured to the centerline of the dispenser.<br />

Requires<br />

engineering/architectural<br />

evaluation. Relocate the toilet<br />

paper dispenser away from the<br />

top of the grab bar.<br />

3 $7,238.13<br />

6/1/2012 Page 14 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

117-Toilet Grab Bars:<br />

Unisex Restroom to the<br />

Right on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [See<br />

Sequence #116 for<br />

additional actions.]<br />

118-Lavatories: Unisex<br />

Restroom to the Right<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

119-Accessories: Unisex<br />

Restroom to the Right<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [See<br />

Sequence #116 and<br />

#117 for additional<br />

actions. Soap dispenser -<br />

44-12" / paper towel<br />

dispenser - 45" / seat<br />

cover dispenser - 48" /<br />

toilet paper dispenser -<br />

43".]<br />

120-Water Fountains<br />

(Drinking): 2nd Floor<br />

Corridor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

128-Signage: Fire Door<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

129-Doors: Room #204<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

The front of the side grab bar extends 54" from<br />

back wall in single accommodation stall. Area<br />

directly above grab bars or proposed grab bars<br />

is free of protruding obstructions to a height of<br />

18" (recessed items are allowed).<br />

18" minimum from center of fixture to side wall<br />

or partition.<br />

40" max. height to all other fixtures (i.e., soap<br />

dispensers, towels, toilet seat covers, auto<br />

dryers, sanitary napkins, waste recepatacles,<br />

etc.). Coat hooks and shelving are located within<br />

appropriate reach ranges (48" max. height<br />

above floor surface is recommended).<br />

Stream of bubbler is parallel to front edge. The<br />

force required to activate controls does not<br />

exceed 5lbf.<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Relocate side grab bar. 3 $245.01<br />

Replace with accessible<br />

lavatory.<br />

Install accessible coat hook.<br />

Lower the soap dispenser.<br />

Lower the paper towel<br />

dispenser.<br />

Adjust water pressure of<br />

existing fountain. Adjust angle<br />

of stream.<br />

Install permanent ID sign to<br />

latch side of door.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

3 $3,185.07<br />

3 $367.51<br />

2 $673.76<br />

1 $183.75<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

131-Signage: Room<br />

#204 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate existing signage. 3 $245.01<br />

6/1/2012 Page 15 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

134-Clear Space at<br />

Doors: Behind Room<br />

#204 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

135-Signage: Behind<br />

Room #204 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

136-Sales and Service<br />

Counters: Room #205<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

137-Sinks: Room #205<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Minimum strike side clearance on PULL side of Relocate furniture to provide<br />

door: 18" wide x 60" depth at interior doors, front clear space. University staff shall<br />

approach. Minimum strike side clearance on be instructed to place and<br />

PUSH side of door: 12" front approach with latch maintain the placement of<br />

and closer.<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Knee space at table(s) is at least 27" high, 30"<br />

wide and extends 19" under the table(s) and;<br />

Minimum 30" x 48" clear space is provided in<br />

front of sink that allows forward approach. 34"<br />

maximum height of rim or counter above floor<br />

surfaces. Knee clearance under sink is a<br />

minimum of 27" high and 30" wide, and provides<br />

an absolute depth of 19" underneath the sink<br />

[ADAAG 606.2 Exception 6 The dip of the<br />

overflow shall not be considered in determining<br />

knee and toe clearance]. Drain and hot water<br />

piping is insulated or configured to prevent<br />

contact.<br />

Install permanent ID sign to<br />

latch side of door.<br />

Cut skirt on the counter to<br />

comply with knee clearance.<br />

Replace with accessible sink.<br />

Insulate pipes under sink. Cut<br />

the paneling under the sink<br />

counter to comply with knee<br />

clearance.<br />

1M $122.51<br />

1 $183.75<br />

2 $490.00<br />

3 $3,920.09<br />

6/1/2012 Page 16 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

140-Seating, Tables and<br />

Work Surfaces: Room<br />

#205 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />

hood. Relocate the<br />

flammable box.]<br />

27" high, 30" wide and 19" deep knee clearance<br />

provided.<br />

Replace the fume hood with an<br />

accessible fume hood<br />

workstation.Relocate furniture<br />

to provide clear space.<br />

University staff shall be<br />

instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

3 $18,277.25 Until such time<br />

as accessible<br />

furniture /<br />

stations are<br />

available in this<br />

room staff shall<br />

be informed of<br />

the immediate<br />

availability of<br />

accessible<br />

furniture /<br />

stations that<br />

may be placed<br />

in the room to<br />

meet the needs<br />

of people with<br />

disabilities.<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

141-Protruding Objects:<br />

Room #205 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Fume hood.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $245.01<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

142-Protruding Objects:<br />

Room #205 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Emergency eyewash.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $122.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

143-Aisles: Room #205<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

36" minimum width of aisles. Requires<br />

engineering/architectural<br />

evaluation.<br />

2 $7,115.62<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

144-Doors: Rooms #205<br />

and #206 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Three doors.]<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $612.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

146-Signage: Rooms<br />

#205 and #206 on the<br />

2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate existing signage. 3 $490.00<br />

6/1/2012 Page 17 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

147-Doors: Room #207<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

148-Clear Space at<br />

Doors: Room #207 on<br />

the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

149-Signage: Room<br />

#207 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Minimum strike side clearance on PUSH side of<br />

door: 12" front approach with latch and closer.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate furniture to provide<br />

clear space. University staff shall<br />

be instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

1M $61.25<br />

Relocate existing signage. 3 $245.01<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

151-Sinks: Room #206<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Minimum 30" x 48" clear space is provided in<br />

front of sink that allows forward approach. Sink<br />

is a maximum of 6-1/2" deep. Knee clearance<br />

under sink is a minimum of 27" high and 30"<br />

wide, and provides an absolute depth of 19"<br />

underneath the sink [ADAAG 606.2 Exception 6<br />

The dip of the overflow shall not be considered<br />

in determining knee and toe clearance]. Drain<br />

and hot water piping is insulated or configured to<br />

prevent contact.<br />

Replace with accessible sink.<br />

Insulate pipes under sink. Cut<br />

the paneling under the sink<br />

counter to comply with knee<br />

clearance.<br />

3 $3,920.09<br />

6/1/2012 Page 18 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

155-Seating, Tables and<br />

Work Surfaces: Room<br />

#206 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />

hood.]<br />

28" - 34" height of table or work surface that is<br />

36" wide.<br />

Replace the fume hood with an<br />

accessible fume hood<br />

workstation.<br />

3 $18,216.00 Until such time<br />

as accessible<br />

furniture /<br />

stations are<br />

available in this<br />

room staff shall<br />

be informed of<br />

the immediate<br />

availability of<br />

accessible<br />

furniture /<br />

stations that<br />

may be placed<br />

in the room to<br />

meet the needs<br />

of people with<br />

disabilities.<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

156-Protruding Objects:<br />

Room #206 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Fume hood.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $245.01<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

157-Aisles: Room #206<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

36" minimum width of aisles. Requires<br />

engineering/architectural<br />

evaluation.<br />

2 $7,115.62<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

158-Protruding Objects:<br />

Room #206 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Emergency eye wash.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $122.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

160-Doors: Rooms #222<br />

and #219 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Two doors.]<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $612.51<br />

6/1/2012 Page 19 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

161-Clear Space at<br />

Doors: Rooms #222 and<br />

#219 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

162-Signage: Rooms<br />

#222 and #219 on the<br />

2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

164-Sinks: Rooms #222<br />

and #219 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Minimum strike side clearance on PUSH side of<br />

door: 12" front approach with latch and closer.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Minimum 30" x 48" clear space is provided in<br />

front of sink that allows forward approach. Sink<br />

is a maximum of 6-1/2" deep. Knee clearance<br />

under sink is a minimum of 27" high and 30"<br />

wide, and provides an absolute depth of 19"<br />

underneath the sink [ADAAG 606.2 Exception 6<br />

The dip of the overflow shall not be considered<br />

in determining knee and toe clearance]. Drain<br />

and hot water piping is insulated or configured to<br />

prevent contact.<br />

Relocate furniture to provide<br />

clear space. University staff shall<br />

be instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

1M $122.51<br />

Relocate existing signage. 3 $490.00<br />

Replace with accessible sink.<br />

Insulate pipes under sink. Cut<br />

the paneling under the sink<br />

counter to comply with knee<br />

clearance.<br />

3 $7,840.16<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

166-Controls, Operating<br />

Mechanisms & Vending<br />

Machines.: Rooms #222<br />

and #219 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Various machines.]<br />

Forward Reach to Objects: Highest operable<br />

part of object is a maximum of 48" above the<br />

floor surface.<br />

Relocate existing paper towel<br />

dispenser. Lower the machine.<br />

3 $183.75<br />

6/1/2012 Page 20 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

168-Seating, Tables and<br />

Work Surfaces: Rooms<br />

#222 and #219 on the<br />

2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. [Fume hood.]<br />

28" - 34" height of table or work surface that is<br />

36" wide.<br />

Replace the fume hood with an<br />

accessible fume hood<br />

workstation.<br />

3 $18,216.00 Until such time<br />

as accessible<br />

furniture /<br />

stations are<br />

available in this<br />

room staff shall<br />

be informed of<br />

the immediate<br />

availability of<br />

accessible<br />

furniture /<br />

stations that<br />

may be placed<br />

in the room to<br />

meet the needs<br />

of people with<br />

disabilities.<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

170-Aisles: Rooms #222<br />

and #219 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

36" minimum width of aisles. Requires<br />

engineering/architectural<br />

evaluation.<br />

2 $7,115.62<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

171-Protruding Objects:<br />

Rooms #222 and #219<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

[Emergency eyewash.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

1 $122.51<br />

6/1/2012 Page 21 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

172-Seating, Tables and<br />

Work Surfaces: Rooms<br />

#222 and #219 on the<br />

2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

30" x 48" min. clear floor space is provided. 27"<br />

high, 30" wide and 19" deep knee clearance<br />

provided.<br />

Provide accessible table. 1M $245.01 Until such time<br />

as accessible<br />

furniture /<br />

stations are<br />

available in this<br />

room staff shall<br />

be informed of<br />

the immediate<br />

availability of<br />

accessible<br />

furniture /<br />

stations that<br />

may be placed<br />

in the room to<br />

meet the needs<br />

of people with<br />

disabilities.<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

173-Doors: Rooms #218<br />

and #221 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Three doors.]<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $612.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

175-Signage: Rooms<br />

#218 and #221 on the<br />

2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

177-Clear Space at<br />

Doors: Rooms #202,<br />

#203, #225 and #224 on<br />

the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. [Four office<br />

doors.]<br />

178-Signage: Rooms<br />

#202, #203, #225 and<br />

#224 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Four<br />

office doors.]<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

60" min. clear space in direction of door swing.<br />

Minimum strike side clearance on PULL side of<br />

door: 18" wide x 60" depth at interior doors, front<br />

approach.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate existing signage. 3 $490.00<br />

Relocate furniture to provide<br />

clear space. University staff shall<br />

be instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

1M $245.01<br />

Relocate existing signage. 3 $980.02<br />

6/1/2012 Page 22 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

179-Doors: North<br />

Stairwell on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

32" minimum clear width of doorway. 5 lb.<br />

maximum pressure to operate interior doors.<br />

Adjust door opening pressure<br />

/ closing time unless accepted<br />

by DSA Fire / Life Safety.<br />

Consider issues connected<br />

with building pressure / climate<br />

control. Replace door and<br />

frame (concrete or block wall).<br />

2 $5,573.87<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

181-Signage: North<br />

Stairwell on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

182-Tactile Exit<br />

Signage: North Stairwell<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

183-Doors: North<br />

Entrance to <strong>Pierce</strong><br />

<strong>Annex</strong> on the 2nd Floor.<br />

[One set of double<br />

doors.]<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each exit door that leads directly to a gradelevel<br />

exterior exit by means of a stairway or<br />

ramp is identified by a tactile exit sign that states<br />

"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />

"EXIT STAIR UP", or "EXIT RAMP UP", as<br />

appropriate.<br />

5 lb. maximum pressure to operate exterior<br />

doors.<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

185-Signage: North<br />

Entrance to <strong>Pierce</strong><br />

<strong>Annex</strong> on the 2nd Floor.<br />

186-Tactile Exit<br />

Signage: North Entrance<br />

to <strong>Pierce</strong> <strong>Annex</strong> on the<br />

2nd Floor.<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each grade-level exterior exit door shall be<br />

identified by a tactile sign with the word "EXIT".<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

6/1/2012 Page 23 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

187-Doors: West<br />

Entrance to <strong>Pierce</strong><br />

<strong>Annex</strong> on the 3rd Floor.<br />

[One set of double<br />

doors.]<br />

189-Signage: West<br />

Entrance to <strong>Pierce</strong><br />

<strong>Annex</strong> on the 3rd Floor.<br />

190-Tactile Exit<br />

Signage: West Entrance<br />

to <strong>Pierce</strong> <strong>Annex</strong> on the<br />

3rd Floor.<br />

191-Doors: Unisex<br />

Restroom on the Left on<br />

the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

193-Identification<br />

Symbols, Restrooms:<br />

Unisex Restroom on the<br />

Left on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

5 lb. maximum pressure to operate exterior<br />

doors. 3 seconds minimum for door closer to<br />

close from 70 degree position to within 3" of the<br />

latch [ADAAG 404.2.8.1 Door & gate closers<br />

require a 5 second minimum closing time from<br />

open position of 90 degree to 12 degree<br />

position].<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each exit door that leads directly to a gradelevel<br />

exterior exit by means of a stairway or<br />

ramp is identified by a tactile exit sign that states<br />

"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />

"EXIT STAIR UP", or "EXIT RAMP UP", as<br />

appropriate.<br />

5 lb. maximum pressure to operate interior<br />

doors. 3 seconds minimum for door closer to<br />

close from 70 degree position to within 3" of the<br />

latch [ADAAG 404.2.8.1 Door & gate closers<br />

require a 5 second minimum closing time from<br />

open position of 90 degree to 12 degree<br />

position].<br />

Unisex - 12" diameter circle 1/4" thick with 1/4"<br />

thick triangle superimposed in the circle. The<br />

circle and triangle symbols contrasts with the<br />

door, light on dark background or dark on light<br />

background [CBC 1115B.6 The triangle shall<br />

contrast w the circle and the circle shall contrast<br />

with the door]. Wall mounted signage: Symbol of<br />

accessibility is mounted on wall sign adjacent to<br />

latch side of door [ADAAG 703.6.1 & CBC<br />

1117B.5.5 Item 4 Pictograms shall have a field<br />

height of 6" ADAAG 703.6.1 Characters and<br />

Braille shall not be located in the pictogram<br />

field]. Verbal description as to restroom usage is<br />

placed directly below the pictogram, if utilized in<br />

conjunction with verbal identification and the<br />

border dimensions of this pictogram is a<br />

minimum of 6" in height.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

Install permanent ID sign to<br />

latch side of door.<br />

2 $306.26<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

Install door-mounted sign on<br />

single door. Install wallmounted<br />

sign at single<br />

entrance.<br />

2 $306.26<br />

3 $367.51<br />

6/1/2012 Page 24 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

194-Single<br />

Accommodation Toilet:<br />

Unisex Restroom on the<br />

Left on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

195-Toilet Grab Bars:<br />

Unisex Restroom on the<br />

Left on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [See<br />

Sequence #194 for<br />

additional actions.]<br />

196-Lavatories: Unisex<br />

Restroom on the Left on<br />

the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

197-Accessories: Unisex<br />

Restroom on the Left on<br />

the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. [See Sequence<br />

#194 and #195 for<br />

additional actions. Soap<br />

dispenser - 43" / paper<br />

towel dispenser - 45" /<br />

seat cover dispenser -<br />

48" / toilet paper<br />

dispenser - 42-1/4". ]<br />

60" minimum diameter turning circle, or a T-<br />

shaped clear space, is provided in room with 12"<br />

maximum door encroachment into the required<br />

clear space. Front of toilet paper dispenser is<br />

within 36" of the back wall. The toilet paper<br />

dispenser is located on the side wall below the<br />

grab bar and within 7" - 9" of the front of the<br />

toilet seat as measured to the centerline of the<br />

dispenser.<br />

The front of the side grab bar extends 54" from<br />

back wall in single accommodation stall. Area<br />

directly above grab bars or proposed grab bars<br />

is free of protruding obstructions to a height of<br />

18" (recessed items are allowed).<br />

18" minimum from center of fixture to side wall<br />

or partition. 34" max. height to rim or counter<br />

above floor surface.<br />

40" max. height to all other fixtures (i.e., soap<br />

dispensers, towels, toilet seat covers, auto<br />

dryers, sanitary napkins, waste recepatacles,<br />

etc.). Coat hooks and shelving are located within<br />

appropriate reach ranges (48" max. height<br />

above floor surface is recommended).<br />

Requires<br />

engineering/architectural<br />

evaluation. Relocate the toilet<br />

paper dispenser away from the<br />

top of the grab bar.<br />

Relocate side grab bar.<br />

Relocate the seat cover<br />

dispenser away from the top of<br />

the grab bar.<br />

Replace with accessible<br />

lavatory.<br />

Install accessible coat hook.<br />

Lower the soap dispenser.<br />

Lower the paper towel<br />

dispenser.<br />

3 $7,238.13<br />

3 $367.51<br />

3 $3,185.07<br />

3 $367.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

198-Doors: Unisex<br />

Restroom on the Right<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

6/1/2012 Page 25 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

200-Identification<br />

Symbols, Restrooms:<br />

Unisex Restroom on the<br />

Right on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Unisex - 12" diameter circle 1/4" thick with 1/4"<br />

thick triangle superimposed in the circle. The<br />

circle and triangle symbols contrasts with the<br />

door, light on dark background or dark on light<br />

background [CBC 1115B.6 The triangle shall<br />

contrast w the circle and the circle shall contrast<br />

with the door]. Wall mounted signage: Symbol of<br />

accessibility is mounted on wall sign adjacent to<br />

latch side of door [ADAAG 703.6.1 & CBC<br />

1117B.5.5 Item 4 Pictograms shall have a field<br />

height of 6" ADAAG 703.6.1 Characters and<br />

Braille shall not be located in the pictogram<br />

field]. Verbal description as to restroom usage is<br />

placed directly below the pictogram, if utilized in<br />

conjunction with verbal identification and the<br />

border dimensions of this pictogram is a<br />

minimum of 6" in height.<br />

Install door-mounted sign on<br />

single door. Install wallmounted<br />

sign at single<br />

entrance.<br />

3 $367.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

201-Single<br />

Accommodation Toilet:<br />

Unisex Restroom on the<br />

Right on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

60" minimum diameter turning circle, or a T-<br />

shaped clear space, is provided in room with 12"<br />

maximum door encroachment into the required<br />

clear space. A minimum 60" wide and 48" deep<br />

clear floor space is provided in front of water<br />

closet. Front of toilet paper dispenser is within<br />

36" of the back wall. The toilet paper dispenser<br />

is located on the side wall below the grab bar<br />

and within 7" - 9" of the front of the toilet seat as<br />

measured to the centerline of the dispenser.<br />

Requires<br />

engineering/architectural<br />

evaluation. Relocate the toilet<br />

paper dispenser away from the<br />

top of the grab bar.<br />

3 $7,238.13<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

202-Toilet Grab Bars:<br />

Unisex Restroom on the<br />

Right on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [See<br />

Sequence #201 for<br />

additional actions.]<br />

203-Lavatories: Unisex<br />

Restroom on the Right<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

The front of the side grab bar extends 54" from<br />

back wall in single accommodation stall. Area<br />

directly above grab bars or proposed grab bars<br />

is free of protruding obstructions to a height of<br />

18" (recessed items are allowed).<br />

18" minimum from center of fixture to side wall<br />

or partition.<br />

Relocate side grab bar.<br />

Relocate the seat cover<br />

dispenser away from the top of<br />

the grab bar.<br />

Replace with accessible<br />

lavatory.<br />

3 $367.51<br />

3 $3,185.07<br />

6/1/2012 Page 26 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

204-Accessories: Unisex<br />

Restroom on the Right<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [See<br />

Sequence #201 and<br />

#202 for additional<br />

actions.]<br />

207-Water Fountains<br />

(Drinking): Corridor on<br />

the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

211-Signage: Fire Doors<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

212-Doors: Rooms #321<br />

and #318 on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

40" max. height to all other fixtures (i.e., soap<br />

dispensers, towels, toilet seat covers, auto<br />

dryers, sanitary napkins, waste recepatacles,<br />

etc.). Coat hooks and shelving are located within<br />

appropriate reach ranges (48" max. height<br />

above floor surface is recommended).<br />

Stream of bubbler is parallel to front edge. The<br />

force required to activate controls does not<br />

exceed 5lbf.<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Install accessible coat hook.<br />

Lower the paper towel<br />

dispenser. Lower the soap<br />

dispenser.<br />

Adjust angle of stream.<br />

Reduce force needed to<br />

operate fountain controls ( 5 lb.<br />

maximum).<br />

Install permanent ID sign to<br />

latch side of door.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

3 $367.51<br />

2 $551.26<br />

1 $183.75<br />

2 $612.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

214-Signage: Rooms<br />

#321 and #318 on the<br />

3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Relocate existing signage. 3 $490.00<br />

6/1/2012 Page 27 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

220-Seating, Tables and<br />

Work Surfaces: Rooms<br />

#321 and #318 on the<br />

3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. [Fume hood.]<br />

28" - 34" height of table or work surface that is<br />

36" wide.<br />

Replace the fume hood with an<br />

accessible fume hood<br />

workstation.<br />

3 $18,216.00 Until such time<br />

as accessible<br />

furniture /<br />

stations are<br />

available in this<br />

room staff shall<br />

be informed of<br />

the immediate<br />

availability of<br />

accessible<br />

furniture /<br />

stations that<br />

may be placed<br />

in the room to<br />

meet the needs<br />

of people with<br />

disabilities.<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

221-Protruding Objects:<br />

Rooms #321 and #318<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Eight<br />

fume hoods.]<br />

222-Protruding Objects:<br />

Rooms #321 and #318<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Two<br />

emergency eyewash<br />

controls.]<br />

223-Aisles: Rooms #321<br />

and #318 on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

Install cane detectable barrier<br />

below object.<br />

36" minimum width of aisles. Requires<br />

engineering/architectural<br />

evaluation.<br />

1 $980.02<br />

1 $245.01<br />

2 $7,115.62<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

224-Floors and Levels:<br />

Rooms #321 and #318<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Four<br />

carpets / mats.]<br />

225-Protruding Objects:<br />

Rooms #321 and #318<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Shelf on<br />

machine.]<br />

Carpets or carpet tiles are securely attached<br />

and do not exceed 1/2" in height. Carpet's<br />

exposed edges are fastened to floor surfaces<br />

and have trim along entire length.<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Secure loose doormat. 1 $980.02<br />

Install cane detectable barrier<br />

below object.<br />

1 $245.01<br />

6/1/2012 Page 28 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

226-Doors: Rooms #319<br />

and #317 on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Three doors.]<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $612.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

228-Signage: Rooms<br />

#319 and #317 on the<br />

3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

229-Doors: Rooms #307<br />

and #304 on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Relocate existing signage. 3 $490.00<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $612.51<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

231-Signage: Rooms<br />

#307 and #304 on the<br />

3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

233-Sinks: Rooms #307<br />

and #304 on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

Sink is a maximum of 6-1/2" deep. Knee<br />

clearance under sink is a minimum of 27" high<br />

and 30" wide, and provides an absolute depth of<br />

19" underneath the sink [ADAAG 606.2<br />

Exception 6 The dip of the overflow shall not be<br />

considered in determining knee and toe<br />

clearance]. Drain and hot water piping is<br />

insulated or configured to prevent contact.<br />

Relocate existing signage. 3 $490.00<br />

Replace with accessible sink.<br />

Insulate pipes under sink.<br />

3 $3,430.07<br />

6/1/2012 Page 29 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

237-Seating, Tables and<br />

Work Surfaces: Rooms<br />

#307 and #304 on the<br />

3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. [Fume hood.]<br />

27" high, 30" wide and 19" deep knee clearance<br />

provided. 28" - 34" height of table or work<br />

surface that is 36" wide.<br />

Replace the fume hood with an<br />

accessible fume hood<br />

workstation.<br />

3 $18,216.00 Until such time<br />

as accessible<br />

furniture /<br />

stations are<br />

available in this<br />

room staff shall<br />

be informed of<br />

the immediate<br />

availability of<br />

accessible<br />

furniture /<br />

stations that<br />

may be placed<br />

in the room to<br />

meet the needs<br />

of people with<br />

disabilities.<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

238-Protruding Objects:<br />

Rooms #307 and #304<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Fume<br />

hood.]<br />

239-Protruding Objects:<br />

Rooms #307 and #304<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Two<br />

eyewash controls.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

Install cane detectable barrier<br />

below object.<br />

Install cane detectable barrier<br />

below object.<br />

1 $980.02<br />

1 $490.00<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

240-Aisles: Rooms #307<br />

and #304 on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

36" minimum width of aisles. Requires<br />

engineering/architectural<br />

evaluation.<br />

2 $7,115.62<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

241-Protruding Objects:<br />

Rooms #307 and #304<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. [Shelf on<br />

machine.]<br />

242-Doors: Rooms #306<br />

and #305 on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[Three doors.]<br />

Objects projecting from walls (i.e. telephones,<br />

etc.) have 4" maximum projection into walks,<br />

halls, corridors, passageways or aisles if lower<br />

edge of object is above 27" and below 80".<br />

5 lb. maximum pressure to operate interior<br />

doors.<br />

Install cane detectable barrier<br />

below object.<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

1 $245.01<br />

2 $612.51<br />

6/1/2012 Page 30 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

244-Signage: Rooms<br />

#306 and #305 on the<br />

3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

246-Clear Space at<br />

Doors: Rooms #323,<br />

#324, #303 and #302 on<br />

the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

247-Signage: Rooms<br />

#323, #324, #303 and<br />

#302 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

248-Doors: North<br />

Stairwell on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

250-Signage: North<br />

Stairwell on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

251-Tactile Exit<br />

Signage: North Stairwell<br />

on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

252-Doors: North<br />

Entrance on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

60" min. clear space in direction of door swing.<br />

Minimum strike side clearance on PULL side of<br />

door: 18" wide x 60" depth at interior doors, front<br />

approach.<br />

Mounting height is 60" from the finish floor to the<br />

centerline of the sign.<br />

32" minimum clear width of doorway. 5 lb.<br />

maximum pressure to operate interior doors.<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each exit door that leads directly to a gradelevel<br />

exterior exit by means of a stairway or<br />

ramp is identified by a tactile exit sign that states<br />

"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />

"EXIT STAIR UP", or "EXIT RAMP UP", as<br />

appropriate.<br />

5 lb. maximum pressure to operate exterior<br />

doors.<br />

Relocate existing signage. 3 $490.00<br />

Relocate furniture to provide<br />

clear space. University staff shall<br />

be instructed to place and<br />

maintain the placement of<br />

furniture to provide a clear path<br />

of travel and avoid the<br />

obstruction of accessible<br />

required clear spaces.<br />

1M $245.01<br />

Relocate existing signage. 3 $980.02<br />

Adjust door opening pressure /<br />

closing time unless accepted<br />

by DSA Fire / Life Safety.<br />

Consider issues connected<br />

with building pressure / climate<br />

control. Replace door and<br />

frame (concrete or block wall).<br />

Install permanent ID sign to<br />

latch side of door.<br />

2 $5,573.87<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

6/1/2012 Page 31 of 32


Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

254-Signage: North<br />

Entrance on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

[No signage.]<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $183.75<br />

Grand Total $406,255.30<br />

6/1/2012 Page 32 of 32


Cost Report


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

2. Stairway Handrails - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Raise/Lower existing handrail height. 44 l.f. $88.00 $3,872.00 $4,259.20 $4,791.60 $5,510.34 $5,510.34<br />

Install top or bottom extensions to existing handrail. 6 ea. $103.30 $619.80 $681.78 $767.00 $882.05 $882.05<br />

TOTAL EST: $6,392.39<br />

4. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

6. Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

7. Tactile Exit Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

8. Floors and Levels - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Secure loose doormat. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />

TOTAL EST: $980.02<br />

Page 1 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

9. Doors - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $306.26<br />

11. Identification Symbols, Restrooms - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $367.50<br />

12. Single Accommodation Toilet - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $7,238.13<br />

13. Toilet Grab Bars - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $367.52<br />

14. Lavatories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

TOTAL EST: $3,185.07<br />

Page 2 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

15. Accessories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $367.53<br />

16. Visual/Audible Alarms - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 0<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

TOTAL EST: $7,115.62<br />

18. Doors - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong> .<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $306.26<br />

20. Identification Symbols, Restrooms - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $367.50<br />

21. Single Accommodation Toilet - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $7,238.13<br />

Page 3 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

22. Toilet Grab Bars - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $367.52<br />

23. Lavatories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

TOTAL EST: $3,185.07<br />

24. Accessories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $245.02<br />

28. Water Fountains (Drinking) - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust angle of stream. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Reduce force needed to operate fountain controls ( 5 lb. maximum).<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $551.27<br />

30. Visual/Audible Alarms - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 0<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

TOTAL EST: $7,115.62<br />

Page 4 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

33. Clear Space at Doors - 1st Floor Rooms #124, #123, #103 and #102 at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 3 ea. $43.04 $129.12 $142.03 $159.78 $183.75 $183.75<br />

Modify, relocate, replace or remove restricting objects. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $428.76<br />

34. Signage - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate permanent ID sign to latch side of door. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />

TOTAL EST: $980.02<br />

35. Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

36. Clear Space at Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />

TOTAL EST: $61.25<br />

37. Signage - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

Page 5 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

39. Clear Space at Doors - Behind Room #107 Toward Lab on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />

TOTAL EST: $61.25<br />

40. Sales and Service Counters - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install accessible counter. 1 ea. $1,119.04 $1,119.04 $1,230.94 $1,384.81 $1,592.53 $1,592.53<br />

TOTAL EST: $1,592.53<br />

41. Sinks - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />

knee clearance.<br />

TOTAL EST: $3,920.08<br />

44. Controls, Operating Mechanisms & Vending Machines. - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />

TOTAL EST: $18,216.00<br />

46. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

Page 6 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

47. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 8 l.f. $86.08 $688.64 $757.50 $852.19 $980.02 $980.02<br />

TOTAL EST: $980.02<br />

48. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $122.51<br />

50. Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

52. Signage - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

54. Doors - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61<br />

TOTAL EST: $5,573.87<br />

Page 7 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

56. Signage - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

57. Elevators - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

Repair door operation. 1 ea. $1,500.00 $1,500.00 $1,650.00 $1,856.25 $2,134.69 $2,134.69<br />

Provide a raised five pointed star at the ground level. 1 ea. $250.00 $250.00 $275.00 $309.38 $355.79 $355.79<br />

TOTAL EST: $9,606.10<br />

60. Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace door(s) and frame (stud wall). 1 ea. $2,203.65 $2,203.65 $2,424.02 $2,727.02 $3,136.07 $3,136.07<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

Post a sign/decal displaying the ”International Symbol of Accessibility”<br />

1 ea. $17.22 $17.22 $18.94 $21.31 $24.51 $24.51<br />

at the primary entrance.<br />

TOTAL EST: $3,466.84<br />

62. Stairways - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Remove/Replace existing stairways or steps. 30 riser $705.86 $21,175.80 $23,293.38 $26,205.05 $30,135.81 $30,135.81<br />

TOTAL EST: $30,135.81<br />

63. Stairway Handrails - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Raise/Lower existing handrail height. 130 l.f. $88.00 $11,440.00 $12,584.00 $14,157.00 $16,280.55 $16,280.55<br />

TOTAL EST: $16,280.55<br />

Page 8 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

64. Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

66. Signage - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

68. Sinks - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />

knee clearance.<br />

TOTAL EST: $735.01<br />

69. Controls, Operating Mechanisms & Vending Machines. - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing paper towel dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $122.51<br />

73. Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

Page 9 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

74. Clear Space at Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />

Modify door to swing opposite hand. 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $551.25<br />

75. Signage - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

77. Sinks - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />

knee clearance.<br />

TOTAL EST: $3,920.08<br />

79. Controls, Operating Mechanisms & Vending Machines. - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Lower the machine. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />

TOTAL EST: $61.25<br />

81. Seating, Tables and Work Surfaces - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />

TOTAL EST: $18,216.00<br />

Page 10 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

82. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

83. Aisles - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

TOTAL EST: $7,115.62<br />

84. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $122.51<br />

85. Doors - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $612.51<br />

87. Signage - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

Page 11 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

88. Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61<br />

TOTAL EST: $5,573.87<br />

90. Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

91. Tactile Exit Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

92. Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $306.26<br />

95. Stairway Handrails - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Raise/Lower existing handrail height. 120 l.f. $34.43 $4,131.60 $4,544.76 $5,112.86 $5,879.79 $5,879.79<br />

TOTAL EST: $5,879.79<br />

Page 12 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

97. Hazards - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 8 l.f. $86.08 $688.64 $757.50 $852.19 $980.02 $980.02<br />

TOTAL EST: $980.02<br />

98. Doors - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

100. Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

101. Tactile Exit Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

102. Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

Page 13 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

104. Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

105. Tactile Exit Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

106. Doors - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $306.26<br />

108. Identification Symbols, Restrooms - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $367.50<br />

109. Single Accommodation Toilet - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $7,238.13<br />

Page 14 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

110. Toilet Grab Bars - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $367.52<br />

111. Lavatories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

TOTAL EST: $3,185.07<br />

112. Accessories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $367.53<br />

113. Doors - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $306.26<br />

115. Identification Symbols, Restrooms - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $367.50<br />

Page 15 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

116. Single Accommodation Toilet - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $7,238.13<br />

117. Toilet Grab Bars - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

118. Lavatories - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

TOTAL EST: $3,185.07<br />

119. Accessories - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $367.53<br />

120. Water Fountains (Drinking) - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust water pressure of existing fountain. 1 ea. $301.28 $301.28 $331.41 $372.84 $428.77 $428.77<br />

Adjust angle of stream. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $673.78<br />

Page 16 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

128. Signage - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

129. Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

131. Signage - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

134. Clear Space at Doors - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 2 ea. $43.04 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $122.51<br />

135. Signage - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

136. Sales and Service Counters - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Cut skirt on the counter to comply with knee clearance. 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

Page 17 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

137. Sinks - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />

knee clearance.<br />

TOTAL EST: $3,920.08<br />

140. Seating, Tables and Work Surfaces - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />

Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />

TOTAL EST: $18,277.25<br />

141. Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

142. Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $122.51<br />

143. Aisles - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

TOTAL EST: $7,115.62<br />

Page 18 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

144. Doors - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $612.51<br />

146. Signage - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

147. Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

148. Clear Space at Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />

TOTAL EST: $61.25<br />

149. Signage - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

Page 19 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

151. Sinks - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00<br />

knee clearance.<br />

TOTAL EST: $3,920.08<br />

155. Seating, Tables and Work Surfaces - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />

TOTAL EST: $18,216.00<br />

156. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

157. Aisles - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

TOTAL EST: $7,115.62<br />

158. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $122.51<br />

Page 20 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

160. Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $612.51<br />

161. Clear Space at Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 2 ea. $43.04 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $122.51<br />

162. Signage - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

164. Sinks - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible sink. 2 ea. $2,238.08 $4,476.16 $4,923.78 $5,539.25 $6,370.14 $6,370.14<br />

Insulate pipes under lavatory (or sink when applicable). 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

Cut the paneling under the lavatory/sink counter to comply with 2 ea. $344.32 $688.64 $757.50 $852.19 $980.02 $980.02<br />

knee clearance.<br />

TOTAL EST: $7,840.16<br />

166. Controls, Operating Mechanisms & Vending Machines. - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing paper towel dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Lower the machine. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25<br />

TOTAL EST: $183.76<br />

Page 21 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

168. Seating, Tables and Work Surfaces - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />

TOTAL EST: $18,216.00<br />

169. Protruding Objects - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

170. Aisles - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

TOTAL EST: $7,115.62<br />

171. Protruding Objects - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Modify, relocate, replace or remove restricting objects. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

172. Seating, Tables and Work Surfaces - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Provide accessible table. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

173. Doors - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $612.51<br />

Page 22 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

175. Signage - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

177. Clear Space at Doors - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 4 ea. $43.04 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

178. Signage - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />

TOTAL EST: $980.02<br />

179. Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61<br />

TOTAL EST: $5,573.87<br />

181. Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

Page 23 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

182. Tactile Exit Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

183. Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

185. Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

186. Tactile Exit Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

187. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

Page 24 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

189. Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

190. Tactile Exit Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

191. Doors - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $306.26<br />

193. Identification Symbols, Restrooms - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $367.50<br />

194. Single Accommodation Toilet - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $7,238.13<br />

Page 25 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

195. Toilet Grab Bars - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $367.52<br />

196. Lavatories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

TOTAL EST: $3,185.07<br />

197. Accessories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $367.53<br />

198. Doors - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $306.26<br />

200. Identification Symbols, Restrooms - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $367.50<br />

Page 26 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

201. Single Accommodation Toilet - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $7,238.13<br />

202. Toilet Grab Bars - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Relocate the seat cover dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

bars or proposed grab bars.<br />

TOTAL EST: $367.52<br />

203. Lavatories - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

TOTAL EST: $3,185.07<br />

204. Accessories - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install accessible coat hook. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51<br />

TOTAL EST: $367.53<br />

207. Water Fountains (Drinking) - Corridor on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust angle of stream. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

Reduce force needed to operate fountain controls ( 5 lb. maximum).<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $551.27<br />

Page 27 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

211. Signage - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

212. Doors - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $612.51<br />

214. Signage - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

220. Seating, Tables and Work Surfaces - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />

TOTAL EST: $18,216.00<br />

221. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 8 l.f. $86.08 $688.64 $757.50 $852.19 $980.02 $980.02<br />

TOTAL EST: $980.02<br />

222. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

Page 28 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

223. Aisles - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

TOTAL EST: $7,115.62<br />

224. Floors and Levels - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Secure loose doormat. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />

TOTAL EST: $980.02<br />

225. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

226. Doors - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $612.51<br />

228. Signage - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

Page 29 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

229. Doors - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $612.51<br />

231. Signage - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

233. Sinks - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07<br />

Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $3,430.08<br />

237. Seating, Tables and Work Surfaces - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00<br />

TOTAL EST: $18,216.00<br />

238. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 8 l.f. $86.08 $688.64 $757.50 $852.19 $980.02 $980.02<br />

TOTAL EST: $980.02<br />

Page 30 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

239. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 4 l.f. $86.08 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

240. Aisles - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62<br />

TOTAL EST: $7,115.62<br />

241. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 1<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

242. Doors - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51<br />

by DSA / Fire Life Safety.<br />

TOTAL EST: $612.51<br />

244. Signage - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00<br />

TOTAL EST: $490.00<br />

246. Clear Space at Doors - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate furniture to provide clear space. 4 ea. $43.04 $172.16 $189.38 $213.05 $245.01 $245.01<br />

TOTAL EST: $245.01<br />

Page 31 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

247. Signage - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Relocate existing signage. 4 ea. $172.16 $688.64 $757.50 $852.19 $980.02 $980.02<br />

TOTAL EST: $980.02<br />

248. Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

by DSA / Fire Life Safety.<br />

Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61<br />

TOTAL EST: $5,573.87<br />

250. Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

251. Tactile Exit Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 3<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

252. Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Adjust door for opening pressure/closing times unless accepted<br />

by DSA / Fire Life Safety.<br />

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26<br />

TOTAL EST: $306.26<br />

Page 32 of 33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue Qty Unit<br />

Sub<br />

Contractor<br />

Sub<br />

Total<br />

(10%)<br />

Concealed<br />

Conditions<br />

(12.5%)<br />

Security<br />

Conditions<br />

(15%)<br />

General<br />

Conditions<br />

Total<br />

254. Signage - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Priority: 2<br />

RECOMMENDATIONS AND RETROFIT COSTS:<br />

Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75<br />

TOTAL EST: $183.75<br />

REPORT TOTALS: $290,897.43 $319,987.17 $359,985.57 $413,983.41 $413,983.41<br />

Page 33 of 33


Survey


Americans with Disabilities Act of 1990<br />

Site Assessment Report<br />

Report: UCR P5508 <strong>Pierce</strong><br />

<strong>Annex</strong><br />

900 University Avenue<br />

Riverside, CA 93012<br />

Inspection Date: 08/25/2009<br />

Prepared for:<br />

University of California at Riverside<br />

Prepared by:<br />

National Access Consultants, LLC<br />

2321 Abbot Kinney Blvd. Suite 200<br />

Venice, California 90291<br />

(805)497-6116


Contents<br />

1. Stairways - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1<br />

2. Stairway Handrails - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 2<br />

3. Stairway Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4<br />

4. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5<br />

5. Clear Space at Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 7<br />

6. Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9<br />

7. Tactile Exit Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10<br />

8. Floors and Levels - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11<br />

9. Doors - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 12<br />

10. Clear Space at Doors - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 14<br />

11. Identification Symbols, Restrooms - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. 16<br />

12. Single Accommodation Toilet - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . 17<br />

13. Toilet Grab Bars - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 19<br />

14. Lavatories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 21<br />

15. Accessories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 23<br />

16. Visual/Audible Alarms - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 25<br />

17. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex Restroom to the Left on the 1st Floor<br />

of <strong>Pierce</strong> <strong>Annex</strong> . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26<br />

18. Doors - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong> . . . . . . . . . . . . . . . . 27<br />

19. Clear Space at Doors - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 29<br />

20. Identification Symbols, Restrooms - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. 31<br />

21. Single Accommodation Toilet - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . 32<br />

22. Toilet Grab Bars - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 34<br />

23. Lavatories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 36<br />

24. Accessories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 38<br />

25. Visual/Audible Alarms - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 40<br />

26. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex Restroom to the Right on the 1st Floor<br />

of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41<br />

27. Corridors - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42


28. Water Fountains (Drinking) - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 44<br />

29. Controls, Operating Mechanisms & Vending Machines. - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . 46<br />

30. Visual/Audible Alarms - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 47<br />

31. Electrical Controls & Receptacles/Fire Alarm Boxes - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 48<br />

32. Doors - 1st Floor Rooms #124, #123, #103 and #102 at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 50<br />

33. Clear Space at Doors - 1st Floor Rooms #124, #123, #103 and #102 at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 52<br />

34. Signage - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54<br />

35. Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 56<br />

36. Clear Space at Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 58<br />

37. Signage - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 60<br />

38. Doors - Behind Room #107 Toward Lab on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 62<br />

39. Clear Space at Doors - Behind Room #107 Toward Lab on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . 64<br />

40. Sales and Service Counters - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 66<br />

41. Sinks - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 67<br />

42. Controls, Operating Mechanisms & Vending Machines. - Room #106 on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69<br />

43. Controls, Operating Mechanisms & Vending Machines. - Room #106 on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70<br />

44. Controls, Operating Mechanisms & Vending Machines. - Room #106 on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71<br />

45. Seating, Tables and Work Surfaces - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 72<br />

46. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 73<br />

47. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 74<br />

48. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 75<br />

49. Electrical Controls & Receptacles/Fire Alarm Boxes - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. 76<br />

50. Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 78<br />

51. Clear Space at Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 80<br />

52. Signage - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 82<br />

53. Seating, Tables and Work Surfaces - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 84<br />

54. Doors - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 85<br />

55. Clear Space at Doors - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . 87


56. Signage - Door to Courtyard from Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 89<br />

57. Elevators - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90<br />

58. Elevator Control (Panel & Hall Call) - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 93<br />

59. Visual and Audible Signals For Elevators - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 95<br />

60. Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . 96<br />

61. Clear Space at Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 98<br />

62. Stairways - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 100<br />

63. Stairway Handrails - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 101<br />

64. Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 103<br />

65. Clear Space at Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 105<br />

66. Signage - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 107<br />

67. Sales and Service Counters - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 109<br />

68. Sinks - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 110<br />

69. Controls, Operating Mechanisms & Vending Machines. - Room #109 on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112<br />

70. Doors - Between Room #109 and Room #111 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 113<br />

71. Clear Space at Doors - Between Room #109 and Room #111 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . 115<br />

72. Signage - Between Room #109 and Room #111 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 117<br />

73. Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 119<br />

74. Clear Space at Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 121<br />

75. Signage - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 123<br />

76. Sales and Service Counters - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 125<br />

77. Sinks - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 126<br />

78. Controls, Operating Mechanisms & Vending Machines. - Room #105 on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128<br />

79. Controls, Operating Mechanisms & Vending Machines. - Room #105 on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130<br />

80. Controls, Operating Mechanisms & Vending Machines. - Room #105 on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131<br />

81. Seating, Tables and Work Surfaces - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 132<br />

82. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 133<br />

83. Aisles - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 134


84. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 135<br />

85. Doors - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 136<br />

86. Clear Space at Doors - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 138<br />

87. Signage - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . 140<br />

88. Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 142<br />

89. Clear Space at Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 144<br />

90. Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 146<br />

91. Tactile Exit Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 147<br />

92. Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . 148<br />

93. Clear Space at Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 150<br />

94. Stairways - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 151<br />

95. Stairway Handrails - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 152<br />

96. Stairway Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 154<br />

97. Hazards - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 155<br />

98. Doors - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 156<br />

99. Clear Space at Doors - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 158<br />

100.Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 160<br />

101.Tactile Exit Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 161<br />

102.Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 162<br />

103.Clear Space at Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 164<br />

104.Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 166<br />

105.Tactile Exit Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 167<br />

106.Doors - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 168<br />

107.Clear Space at Doors - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 170<br />

108.Identification Symbols, Restrooms - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 172<br />

109.Single Accommodation Toilet - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 173<br />

110.Toilet Grab Bars - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 175<br />

111.Lavatories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 177<br />

112.Accessories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 179<br />

113.Doors - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 181


114.Clear Space at Doors - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 183<br />

115.Identification Symbols, Restrooms - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 185<br />

116.Single Accommodation Toilet - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . 186<br />

117.Toilet Grab Bars - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 188<br />

118.Lavatories - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 190<br />

119.Accessories - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 192<br />

120.Water Fountains (Drinking) - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 194<br />

121.Controls, Operating Mechanisms & Vending Machines. - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . 196<br />

122.Seating, Tables and Work Surfaces - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 197<br />

123.Controls, Operating Mechanisms & Vending Machines. - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . 198<br />

124.Visual/Audible Alarms - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 199<br />

125.Electrical Controls & Receptacles/Fire Alarm Boxes - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . 200<br />

126.Doors - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 202<br />

127.Clear Space at Doors - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 204<br />

128.Signage - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 206<br />

129.Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 207<br />

130.Clear Space at Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 209<br />

131.Signage - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 211<br />

132.Seating, Tables and Work Surfaces - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . 213<br />

133.Doors - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . 214<br />

134.Clear Space at Doors - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 216<br />

135.Signage - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 218<br />

136.Sales and Service Counters - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 219<br />

137.Sinks - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 220<br />

138.Controls, Operating Mechanisms & Vending Machines. - Room #205 on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222<br />

139.Controls, Operating Mechanisms & Vending Machines. - Room #205 on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224<br />

140.Seating, Tables and Work Surfaces - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . 225<br />

141.Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 226<br />

142.Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 227


143.Aisles - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 228<br />

144.Doors - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 230<br />

145.Clear Space at Doors - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 232<br />

146.Signage - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 234<br />

147.Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 236<br />

148.Clear Space at Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 238<br />

149.Signage - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 240<br />

150.Sales and Service Counters - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 242<br />

151.Sinks - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 243<br />

152.Controls, Operating Mechanisms & Vending Machines. - Room #206 on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245<br />

153.Controls, Operating Mechanisms & Vending Machines. - Room #206 on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246<br />

154.Controls, Operating Mechanisms & Vending Machines. - Room #206 on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248<br />

155.Seating, Tables and Work Surfaces - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . 249<br />

156.Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 250<br />

157.Aisles - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 251<br />

158.Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 253<br />

159.Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 254<br />

160.Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 255<br />

161.Clear Space at Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 257<br />

162.Signage - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 259<br />

163.Sales and Service Counters - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 261<br />

164.Sinks - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 262<br />

165.Controls, Operating Mechanisms & Vending Machines. - Rooms #222 and #219 on the 2nd Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264<br />

166.Controls, Operating Mechanisms & Vending Machines. - Rooms #222 and #219 on the 2nd Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266<br />

167.Controls, Operating Mechanisms & Vending Machines. - Rooms #222 and #219 on the 2nd Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268<br />

168.Seating, Tables and Work Surfaces - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 269<br />

169.Protruding Objects - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 270


170.Aisles - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 271<br />

171.Protruding Objects - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 272<br />

172.Seating, Tables and Work Surfaces - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 273<br />

173.Doors - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 274<br />

174.Clear Space at Doors - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 276<br />

175.Signage - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 278<br />

176.Doors - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 280<br />

177.Clear Space at Doors - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . 281<br />

178.Signage - Rooms #202, #203, #225 and #224 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 282<br />

179.Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 284<br />

180.Clear Space at Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 286<br />

181.Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 288<br />

182.Tactile Exit Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 289<br />

183.Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . 290<br />

184.Clear Space at Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor. . . . . . . . . . . . . . . 292<br />

185.Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . 294<br />

186.Tactile Exit Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor. . . . . . . . . . . . . . . . 295<br />

187.Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor. . . . . . . . . . . . . . . . . . . . . . . . . 296<br />

188.Clear Space at Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor. . . . . . . . . . . . . . . . 298<br />

189.Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor. . . . . . . . . . . . . . . . . . . . . . . . 300<br />

190.Tactile Exit Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor. . . . . . . . . . . . . . . . . 301<br />

191.Doors - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . 302<br />

192.Clear Space at Doors - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . 304<br />

193.Identification Symbols, Restrooms - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 306<br />

194.Single Accommodation Toilet - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 307<br />

195.Toilet Grab Bars - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 309<br />

196.Lavatories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 311<br />

197.Accessories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . 313<br />

198.Doors - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 315<br />

199.Clear Space at Doors - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 317


200.Identification Symbols, Restrooms - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 319<br />

201.Single Accommodation Toilet - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . 320<br />

202.Toilet Grab Bars - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 322<br />

203.Lavatories - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 324<br />

204.Accessories - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 326<br />

205.Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex Restroom on the Right on the 3rd Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328<br />

206.Corridors - 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330<br />

207.Water Fountains (Drinking) - Corridor on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 332<br />

208.Controls, Operating Mechanisms & Vending Machines. - Corridor on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. 334<br />

209.Doors - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . 335<br />

210.Clear Space at Doors - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 337<br />

211.Signage - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . 339<br />

212.Doors - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 340<br />

213.Clear Space at Doors - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 342<br />

214.Signage - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 344<br />

215.Sales and Service Counters - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 346<br />

216.Sinks - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 347<br />

217.Controls, Operating Mechanisms & Vending Machines. - Rooms #321 and #318 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349<br />

218.Controls, Operating Mechanisms & Vending Machines. - Rooms #321 and #318 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 351<br />

219.Controls, Operating Mechanisms & Vending Machines. - Rooms #321 and #318 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353<br />

220.Seating, Tables and Work Surfaces - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 354<br />

221.Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 355<br />

222.Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 356<br />

223.Aisles - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 357<br />

224.Floors and Levels - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . 358<br />

225.Protruding Objects - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 359<br />

226.Doors - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 360<br />

227.Clear Space at Doors - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 362


228.Signage - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 364<br />

229.Doors - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 366<br />

230.Clear Space at Doors - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 368<br />

231.Signage - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 370<br />

232.Sales and Service Counters - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . 372<br />

233.Sinks - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 373<br />

234.Controls, Operating Mechanisms & Vending Machines. - Rooms #307 and #304 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375<br />

235.Controls, Operating Mechanisms & Vending Machines. - Rooms #307 and #304 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377<br />

236.Controls, Operating Mechanisms & Vending Machines. - Rooms #307 and #304 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379<br />

237.Seating, Tables and Work Surfaces - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 380<br />

238.Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 381<br />

239.Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 382<br />

240.Aisles - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . 383<br />

241.Protruding Objects - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . 384<br />

242.Doors - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . 385<br />

243.Clear Space at Doors - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 387<br />

244.Signage - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . 389<br />

245.Doors - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . 391<br />

246.Clear Space at Doors - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . 393<br />

247.Signage - Rooms #323, #324, #303 and #302 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . 395<br />

248.Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . . 397<br />

249.Clear Space at Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 399<br />

250.Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 401<br />

251.Tactile Exit Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 402<br />

252.Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . . 403<br />

253.Clear Space at Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . 405<br />

254.Signage - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>. . . . . . . . . . . . . . . . . . . . . . . 407


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

1. Stairways - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

44” min. width if occupant load is more than 50.<br />

All treads are slip resistant.<br />

Nosing projection is less than 1-1/2”.<br />

All risers are closed.<br />

All steps have uniform riser height and tread width.<br />

11” min. tread width.<br />

Stairs do not accumulate water.<br />

Ext. - Top landing and all steps have color striping minimum 2” wide and a maximum 4” wide parallel to, and not<br />

more than 1” maximum from tread nose or landing.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-1-1 (originally 0001-400)<br />

1


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

2. Stairway Handrails - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Handrails are provided on both sides and are continuous for the full length of the stairway.<br />

1-1/4” to 1-1/2” handgrip portion or cross section equivalent or the shape provides an equivalent gripping surface.<br />

1-1/2” clearance provided between rail and wall.<br />

Handrails do not rotate in their fittings.<br />

Wall or adjacent surface is free of sharp or abrasive elements.<br />

Ends of rails are rounded or returned smoothly to wall or floor.<br />

Handrail is smooth with no sharp edges.<br />

Handrails do not protrude into pathways.<br />

Inner rails that double back or turn are continuous.<br />

Areas not meeting new construction standards:<br />

Rails are 34” - 38” above stair nosing. (32-1/2” high.)<br />

12” minimum level extension beyond top nosing (parallel with the ground or floor surface) before being returned. (10”.)<br />

12” plus one tread width level extension beyond bottom nosing (parallel with the ground or floor surface) before being<br />

returned. (9-1/2”+ tread.)<br />

Recommendation:<br />

Raise/Lower existing handrail height.<br />

Install top or bottom extensions to existing handrail.<br />

2


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-2-1 (originally 0002-400)<br />

3


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

3. Stairway Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Identification signage is located at each floor level in all enclosed stairways in buildings two or more stories in height.<br />

Signs are a min. of 12” x 12” in size.<br />

Sign identifies the stairway location, floor level number, and upper and lower terminus of stairway.<br />

Information is presented with raised Arabic numerals and corresponding Grade II Braille.<br />

Sign is centered 60” above the floor landing immediately adjacent to the door on the strike side.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-3-1 (originally 0003-400)<br />

4


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

4. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate exterior doors. (7 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-4-1 (originally 0004-400)<br />

5


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-4-2 (originally 0005-400)<br />

6


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

5. Clear Space at Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-5-1 (originally 0006-400)<br />

7


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-5-2 (originally 0007-400)<br />

8


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

6. Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (No sign for door.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-6-1 (originally 0008-400)<br />

9


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

7. Tactile Exit Signage - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />

exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />

appropriate. (Not proper wording.)<br />

Recommendation:<br />

Provide compliant sign.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-7-1 (originally 0009-400)<br />

10


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

8. Floors and Levels - <strong>Pierce</strong> <strong>Annex</strong> 1st Floor.<br />

Memo:<br />

Four carpets / mats.<br />

Areas noted in compliance:<br />

Floor surface is slip resistant.<br />

Changes in level do not exceed 1/4” vertical or 1/2” with 1:2 bevel.<br />

Areas not meeting new construction standards:<br />

Carpets or carpet tiles are securely attached and do not exceed 1/2” in height. (Not secured.)<br />

Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length. (Not fastened.)<br />

Recommendation:<br />

Secure loose doormat.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-8-1 (originally 0010-400)<br />

11


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

9. Doors - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (11 lbs.)<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2.5 seconds.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-9-1 (originally 0011-400)<br />

12


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-9-2 (originally 0012-400)<br />

13


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

10. Clear Space at Doors - Unisex Restroom to the Left on the 1st Floor<br />

of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />

to water closet.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-10-1 (originally 0013-400)<br />

14


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-10-2 (originally 0014-400)<br />

15


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

11. Identification Symbols, Restrooms - Unisex Restroom to the Left on<br />

the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />

contrasts with the door, light on dark background or dark on light background. (No sign.)<br />

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />

identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />

Recommendation:<br />

Install door-mounted sign on single door.<br />

Install wall-mounted sign at single entrance.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-11-1 (originally 0015-400)<br />

16


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

12. Single Accommodation Toilet - Unisex Restroom to the Left on the<br />

1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Space for 30” x 48” wheelchair to enter and permit door to close.<br />

Privacy lock, push button, lever release.<br />

28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />

the water closet to opposite wall or partition.<br />

18” between centerline of water closet and side wall or partition. (18-1/2” (within dimensional tolerance).)<br />

42” min. clearance between centerline of water closet and opposite wall.<br />

The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />

(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />

44” max. height to flush valve.<br />

Flush valve is on wide side of the water closet<br />

5 lb. max. force is required to operate the flush valve.<br />

19” min. height to toilet paper dispenser.<br />

Toilet paper dispenser provides continuous flow.<br />

Areas not meeting new construction standards:<br />

60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />

into the required clear space. (50”.)<br />

A minimum 60” wide and 48” deep clear floor space is provided in front of water closet. (60” x 44-1/4” deep.)<br />

Front of toilet paper dispenser is within 36” of the back wall. (37-1/2”.)<br />

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />

seat. (13” and above grab bar.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />

17


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-12-1 (originally 0016-400)<br />

18


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

13. Toilet Grab Bars - Unisex Restroom to the Left on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

See Sequence #12 for additional recommendations.<br />

Areas noted in compliance:<br />

1-1/4” to 1-1/2” diameter of bars.<br />

1-1/2” clearance between bars and each wall or partition.<br />

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />

(33-1/2” high.)<br />

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />

tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2” high.)<br />

Side bar has 42” min. length.<br />

Side bar begins a max. of 12” from back wall.<br />

Back bar has 36” min. length.<br />

Back bar begins a max. of 6” from side wall.<br />

Bars are smooth with a min. edge radius of 1/8”.<br />

Grab bars do not rotate within their fittings.<br />

Min. structural strength to support 250 lb. point load.<br />

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />

Areas not meeting new construction standards:<br />

The front of the side grab bar extends 54” from back wall in single accommodation stall. (50-1/4”.)<br />

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />

items are allowed). (Toilet paper dispenser - 8-1/2” / seat cover dispenser - 5-3/4”.)<br />

Recommendation:<br />

Relocate grab bar.<br />

Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />

19


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-13-1 (originally 0017-400)<br />

20


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

14. Lavatories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />

space).<br />

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />

34” max. height to rim or counter above floor surface.<br />

29” min. clearance from bottom of apron to floor surface.<br />

27” high x 8” deep knee clearance under front lip.<br />

30” wide x 9” high x 17” deep clearance from front of lavatory.<br />

Drain and piping is insulated or configured to prevent contact.<br />

There are no sharp or abrasive elements under lavatory.<br />

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />

5 lb. max. force required to operate controls.<br />

Areas not meeting new construction standards:<br />

18” minimum from center of fixture to side wall or partition. (17-1/2”.)<br />

Recommendation:<br />

Replace/Install accessible lavatory.<br />

21


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-14-1 (originally 0018-400)<br />

22


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

15. Accessories - Unisex Restroom to the Left on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

See Sequence #12 and #13 for additional recommendations. Soap dispenser - 44” high / seat cover dispenser - 48” high<br />

/ paper towel dispenser - 45” high / toilet paper dispenser - 42-1/2” high.<br />

Areas noted in compliance:<br />

40” maximum height to bottom of reflective surface of mirror.<br />

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />

A maximum of 5 lbs. force is required to operate mechanisms.<br />

Areas not meeting new construction standards:<br />

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />

recepatacles, etc.). (See memo.)<br />

height above floor surface is recom-<br />

Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />

mended). (66-1/2” high.)<br />

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />

(Seat cover dispenser.)<br />

Recommendation:<br />

Install accessible coat hook.<br />

Relocate the soap dispenser.<br />

Relocate the paper towel dispenser / hand dryer.<br />

23


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-15-1 (originally 0019-400)<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-15-2 (originally 0020-400)<br />

24


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

16. Visual/Audible Alarms - Unisex Restroom to the Left on the 1st Floor<br />

of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.<br />

(79-1/2” high.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-16-1 (originally 0021-400)<br />

25


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

17. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex<br />

Restroom to the Left on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong> .<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform.<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-17-1 (originally 0022-400)<br />

26


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

18. Doors - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong> .<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (10 lbs.)<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2.5 seconds.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-18-1 (originally 0023-400)<br />

27


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-18-2 (originally 0024-400)<br />

28


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

19. Clear Space at Doors - Unisex Restroom to the Right on the 1st Floor<br />

of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-19-1 (originally 0025-400)<br />

29


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-19-2 (originally 0026-400)<br />

30


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

20. Identification Symbols, Restrooms - Unisex Restroom to the Right on<br />

the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />

contrasts with the door, light on dark background or dark on light background. (No sign.)<br />

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />

identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />

Recommendation:<br />

Install door-mounted sign on single door.<br />

Install wall-mounted sign at single entrance.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-20-1 (originally 0027-400)<br />

31


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

21. Single Accommodation Toilet - Unisex Restroom to the Right on the<br />

1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Space for 30” x 48” wheelchair to enter and permit door to close.<br />

Privacy lock, push button, lever release.<br />

60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />

into the required clear space.<br />

28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />

the water closet to opposite wall or partition.<br />

18” between centerline of water closet and side wall or partition. (17-1/4” (within dimensional tolerance).)<br />

42” min. clearance between centerline of water closet and opposite wall.<br />

The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />

(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />

44” max. height to flush valve.<br />

Flush valve is on wide side of the water closet<br />

5 lb. max. force is required to operate the flush valve.<br />

19” min. height to toilet paper dispenser.<br />

Toilet paper dispenser provides continuous flow.<br />

Areas not meeting new construction standards:<br />

A minimum 60” wide and 48” deep clear floor space is provided in front of water closet.<br />

Front of toilet paper dispenser is within 36” of the back wall. (39”.)<br />

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />

seat. (14” and above grab bar.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />

32


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-21-1 (originally 0028-400)<br />

33


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

22. Toilet Grab Bars - Unisex Restroom to the Right on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

See Sequence #21 for additional recommendations.<br />

Areas noted in compliance:<br />

1-1/4” to 1-1/2” diameter of bars.<br />

1-1/2” clearance between bars and each wall or partition.<br />

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />

(33-1/2” high.)<br />

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />

tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2” high.)<br />

Side bar has 42” min. length.<br />

Side bar begins a max. of 12” from back wall.<br />

Back bar has 36” min. length.<br />

Back bar begins a max. of 6” from side wall.<br />

Bars are smooth with a min. edge radius of 1/8”.<br />

Grab bars do not rotate within their fittings.<br />

Min. structural strength to support 250 lb. point load.<br />

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />

Areas not meeting new construction standards:<br />

The front of the side grab bar extends 54” from back wall in single accommodation stall. (50-3/4”.)<br />

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />

items are allowed). (Toilet paper dispenser - 8-1/2” / seat cover dispenser - 5-3/4”.)<br />

Recommendation:<br />

Relocate grab bar.<br />

Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />

34


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-22-1 (originally 0029-400)<br />

35


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

23. Lavatories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />

space).<br />

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />

34” max. height to rim or counter above floor surface.<br />

29” min. clearance from bottom of apron to floor surface.<br />

27” high x 8” deep knee clearance under front lip.<br />

30” wide x 9” high x 17” deep clearance from front of lavatory.<br />

Drain and piping is insulated or configured to prevent contact.<br />

There are no sharp or abrasive elements under lavatory.<br />

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />

5 lb. max. force required to operate controls.<br />

Areas not meeting new construction standards:<br />

18” minimum from center of fixture to side wall or partition. (17-1/2”.)<br />

Recommendation:<br />

Replace/Install accessible lavatory.<br />

36


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-23-1 (originally 0030-400)<br />

37


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

24. Accessories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

See Sequence #21 and #22 for additional recommendations. Soap dispenser - 43” / seat cover dispenser - 48” / paper<br />

towel dispenser - 45” / toilet paper dispenser - 42-1/4”.<br />

Areas noted in compliance:<br />

40” maximum height to bottom of reflective surface of mirror.<br />

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />

A maximum of 5 lbs. force is required to operate mechanisms.<br />

Areas not meeting new construction standards:<br />

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />

recepatacles, etc.). (See memo.)<br />

height above floor surface is recom-<br />

Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />

mended). (66-1/2” high.)<br />

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />

(Seat cover dispenser.)<br />

Recommendation:<br />

Install accessible coat hook.<br />

Relocate the soap dispenser.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-24-1 (originally 0031-400)<br />

38


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-24-2 (originally 0032-400)<br />

39


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

25. Visual/Audible Alarms - Unisex Restroom to the Right on the 1st<br />

Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

The alarm is integrated into the building or facility alarm system.<br />

Lamp is a xenon strobe type or equivalent.<br />

The color is clear and nominal white (unfiltered) or clear filtered white light.<br />

The maximum pulse duration is two-tenths of one second (0.2 sec) with a maximum duty cycle of 40 percent.<br />

The intensity is a maximum of 75 candela.<br />

The flash rate is a minimum of 1Hz and a maximum of 3Hz.<br />

The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.<br />

When provided/required, audible emergency alarms meet applicable requirements.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-25-1 (originally 0033-400)<br />

40


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

26. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex<br />

Restroom to the Right on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform.<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

41


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

27. Corridors - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

44” minimum width for occupant loads of 10 or more.<br />

and 60” x 60” turning space at central location, or,<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-27-1 (originally 0035-400)<br />

42


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-27-2 (originally 0036-400)<br />

43


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

28. Water Fountains (Drinking) - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

32” minimum wide and 18” minimum deep alcove provided.<br />

18” minimum depth of fountain.<br />

27” high x 8” deep clear knee space under fountain.<br />

9” high x 17” deep toe clearance.<br />

Lever or push bar control is located 6” max. from front edge.<br />

Bubbler outlet is 6” maximum from front.<br />

Bubbler outlet is 36” maximum from floor.<br />

4” minimum height of stream.<br />

Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficulty<br />

bending or stooping.<br />

Areas not meeting new construction standards:<br />

Stream of bubbler is parallel to front edge. (On angle.)<br />

The force required to activate controls does not exceed 5lbf. (7 lbs.)<br />

Recommendation:<br />

Adjust angle of stream.<br />

Reduce force needed to operate fountain controls ( 5 lb. maximum).<br />

44


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-28-1 (originally 0037-400)<br />

45


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

29. Controls, Operating Mechanisms & Vending Machines. - 1st Floor<br />

Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fire extinguisher cabinets.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-29-1 (originally 0038-400)<br />

46


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

30. Visual/Audible Alarms - 1st Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

There are no places in common corridors or hallways that are more than 50’ from required signaling appliances.<br />

Areas not meeting new construction standards:<br />

The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.<br />

(79-1/2” high.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-30-1 (originally 0039-400)<br />

47


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

31. Electrical Controls & Receptacles/Fire Alarm Boxes - 1st Floor<br />

Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform.<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform.<br />

The height of the manual fire alarm box is a minimum of 42” and a maximum of 48”, measured vertically, from the<br />

floor level to the highest point of the activating handle or lever of the box.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-31-1 (originally 0040-400)<br />

48


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-31-2 (originally 0042-400)<br />

49


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

32. Doors - 1st Floor Rooms #124, #123, #103 and #102 at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Four office doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

5 lb. maximum pressure to operate interior doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-32-1 (originally 0044-400)<br />

50


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-32-2 (originally 0045-400)<br />

51


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

33. Clear Space at Doors - 1st Floor Rooms #124, #123, #103 and<br />

#102 at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Four office doors.<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PUSH side of door: 0”.<br />

Areas not meeting new construction standards:<br />

60” min. clear space in direction of door swing. (50” to boxes at Room #102.)<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (9” to the furniture at Room<br />

#102.)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Modify, relocate, replace or remove restricting objects.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-33-1 (originally 0046-400)<br />

52


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-33-2 (originally 0047-400)<br />

53


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

34. Signage - 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (54-3/4”.)<br />

Recommendation:<br />

Relocate permanent ID sign to latch side of door.<br />

54


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-34-1 (originally 0048-400)<br />

55


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

35. Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (8 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-35-1 (originally 1417-400)<br />

56


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-35-2 (originally 1418-400)<br />

57


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

36. Clear Space at Doors - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (0” to furniture.)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-36-1 (originally 1419-400)<br />

58


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-36-2 (originally 1420-400)<br />

59


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

37. Signage - Room #107 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Interior door inside of Room #107.<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

60


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-37-1 (originally 1421-400)<br />

61


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

38. Doors - Behind Room #107 Toward Lab on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

5 lb. maximum pressure to operate interior doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-38-1 (originally 1422-400)<br />

62


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-38-2 (originally 1423-400)<br />

63


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

39. Clear Space at Doors - Behind Room #107 Toward Lab on the 1st<br />

Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PUSH side of door: 0”.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (18” wide x 36” deep.)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-39-1 (originally 1424-400)<br />

64


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-39-2 (originally 1425-400)<br />

65


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

40. Sales and Service Counters - Room #106 on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />

A minimum 30” x 48” clear floor space is provided at the counter and;<br />

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />

Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and;<br />

Areas not meeting new construction standards:<br />

Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and; (25” high.)<br />

Recommendation:<br />

Install accessible counter.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-40-1 (originally 1426-400)<br />

66


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

41. Sinks - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Required clear space adjoins or overlaps an accessible route.<br />

There are no sharp or abrasive elements under sink.<br />

Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />

5 lb. maximum force required to activate controls.<br />

Areas not meeting new construction standards:<br />

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />

34” maximum height of rim or counter above floor surfaces. (35” high.)<br />

Sink is a maximum of 6-1/2” deep. (12”.)<br />

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />

sink. (0” deep.)<br />

Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />

Recommendation:<br />

Replace/Install accessible sink.<br />

Insulate pipes under lavatory (or sink when applicable).<br />

Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />

67


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-41-1 (originally 1427-400)<br />

68


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

42. Controls, Operating Mechanisms & Vending Machines. - Room #106<br />

on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-42-1 (originally 1428-400)<br />

69


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

43. Controls, Operating Mechanisms & Vending Machines. - Room #106<br />

on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-43-1 (originally 1429-400)<br />

70


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

44. Controls, Operating Mechanisms & Vending Machines. - Room #106<br />

on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (59”.)<br />

Recommendation:<br />

Replace the fume hood with an accessible fume hood workstation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-44-1 (originally 1430-400)<br />

71


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

45. Seating, Tables and Work Surfaces - Room #106 on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood. See Sequence #44 for recommendation.<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />

27” high, 30” wide and 19” deep knee clearance provided.<br />

Areas not meeting new construction standards:<br />

28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-45-1 (originally 1431-400)<br />

72


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

46. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (5” projection.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-46-1 (originally 1432-400)<br />

73


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

47. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Power control boxes.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (6” projection.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-47-1 (originally 1433-400)<br />

74


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

48. Protruding Objects - Room #106 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Emergency eyewash.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (6” projection.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-48-1 (originally 1434-400)<br />

75


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

49. Electrical Controls & Receptacles/Fire Alarm Boxes - Room #106 on<br />

the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform.<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform. (85” high / Others at ground level.)<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-49-1 (originally 1435-400)<br />

76


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-49-2 (originally 1436-400)<br />

77


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

50. Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (7 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-50-1 (originally 1438-400)<br />

78


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-50-2 (originally 1439-400)<br />

79


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

51. Clear Space at Doors - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-51-1 (originally 1440-400)<br />

80


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-51-2 (originally 1441-400)<br />

81


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

52. Signage - Room #111 on the 1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

82


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-52-1 (originally 1442-400)<br />

83


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

53. Seating, Tables and Work Surfaces - Room #111 on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />

27” high, 30” wide and 19” deep knee clearance provided.<br />

28” - 34” height of table or work surface that is 36” wide.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-53-1 (originally 1443-400)<br />

84


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

54. Doors - Door to Courtyard from Room #111 on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

32” minimum clear width of doorway. (30-1/4”.)<br />

5 lb. maximum pressure to operate exterior doors. (10 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Replace door and frame (concrete or block wall).<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-54-1 (originally 1444-400)<br />

85


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-54-2 (originally 1445-400)<br />

86


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

55. Clear Space at Doors - Door to Courtyard from Room #111 on the<br />

1st Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-55-1 (originally 1446-400)<br />

87


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-55-2 (originally 1447-400)<br />

88


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

56. Signage - Door to Courtyard from Room #111 on the 1st Floor of<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (None.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-56-1 (originally 1448-400)<br />

89


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

57. Elevators - Southeast Side at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Located near major path of travel and are accessible at all times the building is occupied.<br />

54” min. depth of the car platform (rear wall to door)<br />

51” min. clearance from the rear wall to return panel.<br />

36” min. clear width of doorway when fully open.<br />

Handrail is provided (1 minimum) on one wall of the car (rear preferred).<br />

Operation of doors (opening and closing) is automatic.<br />

Elevator is self leveling within 1/2” of floor landings.<br />

Emergency communication device does not require voice communication.<br />

The car inside allows for the turning of a wheelchair (enter the car, maneuver within reach of controls, and exit from the car).<br />

32” (+or- 1”) height of the handrail from the floor.<br />

Minimum of 1-1/2” clearance of the handrail from the wall.<br />

Handrail is smooth, no sharp edges.<br />

Doors are side-slide type (power-operated horizontally sliding).<br />

The clearance between the car platform sill and the edge of the hoistway landing is no greater than 1-1/4”.<br />

Doors remain fully open a minimum of 5 seconds when initially activated.<br />

Door jambs at all landings identify the floor by both raised Arabic numerals (minimum of 2” in height) and Braille<br />

symbols (immediately to left of numerals).<br />

Raised characters are on a contrasting background.<br />

Doorjamb markings are centered at 60” above the floor on both sides of the door.<br />

Emergency communication device is a maximum of 48” from the floor.<br />

The level of illumination at the platform, car threshold and landing sill is at least 5 foot-candles.<br />

Areas not meeting new construction standards:<br />

68” min. width of the car platform with off-center door panels. (65”.)<br />

Elevator doors have an automatic reopening device. The device opens the doors when objects pass through the opening<br />

at heights of 5” and 29” from the floor without requiring contact. Doors remain open for 20 seconds minimum. (5 seconds.)<br />

At grade level, a raised five-pointed star with an outside diameter of 2” is placed to the left of the raised character.<br />

90


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

(1” star.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Repair door operation.<br />

Provide a raised five pointed star at the ground level.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-57-1 (originally 1449-400)<br />

91


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-57-2 (originally 1450-400)<br />

92


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

58. Elevator Control (Panel & Hall Call) - Southeast Side at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Elevator car controls are located on a front wall in cars that have center opening doors, and at the side wall or at the front<br />

wall next to the door if the car has side opening doors.<br />

Elevator floor buttons comply with reach range requirements (48” front reach; 54” side reach to centerline of buttons).<br />

Control buttons are square shouldered, and are a minimum of 3/4” and raised 1/8” plus of minus 1/32” above the<br />

sorrounding surface.<br />

Control buttons are illuminated and are activated by a mechanical motion that is detectable.<br />

All buttons are designated by a 5/8” minimum Arabic Numeral, alphabet or other standard sans serif uppercase character,<br />

or standard raised symbol immediately to the left of the control button.<br />

All raised characters are white on a black background.<br />

Grade 2 Braille symbols are located immediately below the raised characters.<br />

Emergency controls (stop and alarm) are a minimum of 35” from the floor.<br />

The centerline of hall call buttons in elevator lobbies are located at 42” above the floor.<br />

Hall call buttons are a minimum of 3/4” in size and raised 1/8” plus or minus 1/32” above the sorrounding surface.<br />

Hall call button provides visual indication that shows each call registered and extinguishes when answered.<br />

Objects adjacent to and below hall call buttons do not project more than 4”.<br />

Hall call buttons are internally illuminated with a white light over the entire surface of the button.<br />

Areas not meeting new construction standards:<br />

3/8” minimum distance between the rows of the control buttons.<br />

Recommendation:<br />

None.<br />

93


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-58-1 (originally 1451-400)<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-58-2 (originally 1452-400)<br />

94


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

59. Visual and Audible Signals For Elevators - Southeast Side at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Elevator has visual and audible signals indicating the position of the car on or between floors. The indication is positioned<br />

above the car control panel or over the door.<br />

The visual signal for each direction is a minimum of 2-1/2” x 2-1/2”, and visible from the proximity of the hall call<br />

button. NOTE: An automatic verbal announcement of the floor number at which a car stops or which a car passes may<br />

be substituted for the audible signal.<br />

Audible signal sounds are once for up and twice for down. (or equivalent)<br />

Audible signal is no less than 20 decibels with a frequency no higher than 1500 Hz.<br />

Centerline of the fixture is a minimum of 6’ (72”) in height above the lobby floor. NOTE: The use of in-car lanterns,<br />

located in or on the door jambs, visible from the proximity of the call buttons and conforming to items 1, 2, & 3 above<br />

shall or will be acceptable.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-59-1 (originally 1453-400)<br />

95


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

60. Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

32” minimum clear width of doorway. (30-1/4”.)<br />

5 lb. maximum pressure to operate exterior doors. (10 lbs.)<br />

The international symbol of accessibility is posted at all primary entrances.<br />

Recommendation:<br />

Replace door(s) and frame (stud wall).<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Post a sign/decal displaying the ”International Symbol of Accessibility” at the primary entrance.<br />

96


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-60-1 (originally 1454-400)<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-60-2 (originally 1455-400)<br />

97


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

61. Clear Space at Doors - Southeast Entrance on the 1st Floor to <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-61-1 (originally 1456-400)<br />

98


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-61-2 (originally 1457-400)<br />

99


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

62. Stairways - Southeast Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Two staircases.<br />

Areas noted in compliance:<br />

44” min. width if occupant load is more than 50.<br />

All treads are slip resistant.<br />

Nosing projection is less than 1-1/2”.<br />

All risers are closed.<br />

11” min. tread width.<br />

Stairs do not accumulate water.<br />

Ext. - Top landing and all steps have color striping minimum 2” wide and a maximum 4” wide parallel to, and not<br />

more than 1” maximum from tread nose or landing.<br />

Areas not meeting new construction standards:<br />

All steps have uniform riser height and tread width. (6-1/2” - 7-1/4” risers.)<br />

Recommendation:<br />

Remove/Replace existing stairways or steps.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-62-1 (originally 1458-400)<br />

100


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

63. Stairway Handrails - Southeast Entrance on the 1st Floor to <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Two stair cases.<br />

Areas noted in compliance:<br />

Handrails are provided on both sides and are continuous for the full length of the stairway.<br />

1-1/4” to 1-1/2” handgrip portion or cross section equivalent or the shape provides an equivalent gripping surface.<br />

1-1/2” clearance provided between rail and wall.<br />

Handrails do not rotate in their fittings.<br />

Wall or adjacent surface is free of sharp or abrasive elements.<br />

Ends of rails are rounded or returned smoothly to wall or floor.<br />

Handrail is smooth with no sharp edges.<br />

Handrails do not protrude into pathways.<br />

Areas not meeting new construction standards:<br />

Rails are 34” - 38” above stair nosing. (33” high.)<br />

12” minimum level extension beyond top nosing (parallel with the ground or floor surface) before being returned. (9”.)<br />

12” plus one tread width level extension beyond bottom nosing (parallel with the ground or floor surface) before being<br />

returned. (9”+ tread.)<br />

Recommendation:<br />

Raise/Lower existing handrail height.<br />

101


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-63-1 (originally 1459-400)<br />

102


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

64. Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (8 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-64-1 (originally 1460-400)<br />

103


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-64-2 (originally 1461-400)<br />

104


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

65. Clear Space at Doors - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-65-1 (originally 1462-400)<br />

105


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-65-2 (originally 1463-400)<br />

106


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

66. Signage - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

107


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-66-1 (originally 1464-400)<br />

108


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

67. Sales and Service Counters - Room #109 on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />

A minimum 30” x 48” clear floor space is provided at the counter and;<br />

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-67-1 (originally 1465-400)<br />

109


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

68. Sinks - Room #109 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />

Required clear space adjoins or overlaps an accessible route.<br />

34” maximum height of rim or counter above floor surfaces.<br />

Sink is a maximum of 6-1/2” deep.<br />

Drain and hot water piping is insulated or configured to prevent contact.<br />

There are no sharp or abrasive elements under sink.<br />

Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />

5 lb. maximum force required to activate controls.<br />

Areas not meeting new construction standards:<br />

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />

sink. (0” deep.)<br />

Recommendation:<br />

Insulate pipes under lavatory (or sink when applicable).<br />

Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />

110


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-68-1 (originally 1468-400)<br />

111


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

69. Controls, Operating Mechanisms & Vending Machines. - Room #109<br />

on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Paper towel dispenser.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (54” high.)<br />

Recommendation:<br />

Relocate existing paper towel dispenser.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-69-1 (originally 1470-400)<br />

112


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

70. Doors - Between Room #109 and Room #111 on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

5 lb. maximum pressure to operate interior doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-70-1 (originally 1471-400)<br />

113


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-70-2 (originally 1472-400)<br />

114


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

71. Clear Space at Doors - Between Room #109 and Room #111 on the<br />

1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-71-1 (originally 1473-400)<br />

115


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-71-2 (originally 1474-400)<br />

116


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

72. Signage - Between Room #109 and Room #111 on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Not required here.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-72-1 (originally 1475-400)<br />

117


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-72-2 (originally 1476-400)<br />

118


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

73. Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (6 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-73-1 (originally 1477-400)<br />

119


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-73-2 (originally 1478-400)<br />

120


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

74. Clear Space at Doors - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (12” to wall.)<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (2” to trash can.)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Modify door to swing opposite hand.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-74-1 (originally 1479-400)<br />

121


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-74-2 (originally 1480-400)<br />

122


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

75. Signage - Room #104 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

123


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-75-1 (originally 1481-400)<br />

124


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

76. Sales and Service Counters - Room #105 on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />

A minimum 30” x 48” clear floor space is provided at the counter and;<br />

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-76-1 (originally 1482-400)<br />

125


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

77. Sinks - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Required clear space adjoins or overlaps an accessible route.<br />

34” maximum height of rim or counter above floor surfaces.<br />

There are no sharp or abrasive elements under sink.<br />

Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />

5 lb. maximum force required to activate controls.<br />

Areas not meeting new construction standards:<br />

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />

Sink is a maximum of 6-1/2” deep. (10” deep.)<br />

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />

sink.<br />

Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />

Recommendation:<br />

Replace/Install accessible sink.<br />

Insulate pipes under lavatory (or sink when applicable).<br />

Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />

126


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-77-1 (originally 1484-400)<br />

127


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

78. Controls, Operating Mechanisms & Vending Machines. - Room #105<br />

on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Knob.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-78-1 (originally 1487-400)<br />

128


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-78-2 (originally 1488-400)<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-78-3 (originally 1489-400)<br />

129


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

79. Controls, Operating Mechanisms & Vending Machines. - Room #105<br />

on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Thermogravimetric analyzer.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (56” high.)<br />

Recommendation:<br />

Lower the machine.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-79-1 (originally 1490-400)<br />

130


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

80. Controls, Operating Mechanisms & Vending Machines. - Room #105<br />

on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood. See Sequence #81 for recommendation.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (59” high.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-80-1 (originally 1491-400)<br />

131


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

81. Seating, Tables and Work Surfaces - Room #105 on the 1st Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor<br />

space.<br />

Areas not meeting new construction standards:<br />

27” high, 30” wide and 19” deep knee clearance provided. (0” deep.)<br />

28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />

Recommendation:<br />

Replace the fume hood with an accessible fume hood workstation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-81-1 (originally 1492-400)<br />

132


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

82. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (5-1/2” projection.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-82-1 (originally 1493-400)<br />

133


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

83. Aisles - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

36” minimum width of aisles. (25” - 35”.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-83-1 (originally 1494-400)<br />

134


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

84. Protruding Objects - Room #105 on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Emergency eye wash.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-84-1 (originally 1495-400)<br />

135


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

85. Doors - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Three doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (8 - 11 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-85-1 (originally 1496-400)<br />

136


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-85-2 (originally 1497-400)<br />

137


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

86. Clear Space at Doors - Room #105 and Room #106 on the 1st Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Three doors.<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-86-1 (originally 1498-400)<br />

138


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-86-2 (originally 1499-400)<br />

139


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

87. Signage - Room #105 and Room #106 on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

140


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-87-1 (originally 1500-400)<br />

141


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

88. Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

32” minimum clear width of doorway. (31”.)<br />

5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Replace door and frame (concrete or block wall).<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-88-1 (originally 1501-400)<br />

142


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-88-2 (originally 1502-400)<br />

143


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

89. Clear Space at Doors - North Stairwell on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-89-1 (originally 1503-400)<br />

144


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-89-2 (originally 1504-400)<br />

145


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

90. Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (None.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-90-1 (originally 1505-400)<br />

146


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

91. Tactile Exit Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />

exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />

appropriate. (Not proper wording.)<br />

Recommendation:<br />

Provide compliant sign.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-91-1 (originally 1505-400)<br />

147


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

92. Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Exit only door.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate exterior doors. (9 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-92-1 (originally 1506-400)<br />

148


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-92-2 (originally 1507-400)<br />

149


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

93. Clear Space at Doors - Stairwell to Outside on the 1st Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Exit door only.<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-93-1 (originally 1508-400)<br />

150


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

94. Stairways - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

44” min. width if occupant load is more than 50.<br />

All treads are slip resistant.<br />

Nosing projection is less than 1-1/2”.<br />

All risers are closed.<br />

All steps have uniform riser height and tread width.<br />

11” min. tread width.<br />

Stairs do not accumulate water.<br />

Int. - Top landing and lower tread have color striping minimum 2” wide and a maximum 4” wide parallel to, and<br />

not more than 1” maximum from tread nose or landing.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-94-1 (originally 1510-400)<br />

151


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

95. Stairway Handrails - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Handrails are provided on both sides and are continuous for the full length of the stairway.<br />

1-1/4” to 1-1/2” handgrip portion or cross section equivalent or the shape provides an equivalent gripping surface.<br />

1-1/2” clearance provided between rail and wall.<br />

Handrails do not rotate in their fittings.<br />

Wall or adjacent surface is free of sharp or abrasive elements.<br />

Ends of rails are rounded or returned smoothly to wall or floor.<br />

Handrail is smooth with no sharp edges.<br />

Handrails do not protrude into pathways.<br />

Inner rails that double back or turn are continuous.<br />

Areas not meeting new construction standards:<br />

Rails are 34” - 38” above stair nosing. (32” - 32-1/2” high.)<br />

12” minimum level extension beyond top nosing (parallel with the ground or floor surface) before being returned. (9”.)<br />

12” plus one tread width level extension beyond bottom nosing (parallel with the ground or floor surface) before being<br />

returned. (Tread - 9”+.)<br />

Recommendation:<br />

Raise/Lower existing handrail height.<br />

152


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-95-1 (originally 1511-400)<br />

153


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

96. Stairway Signage - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Every sign in stairwell.<br />

Areas noted in compliance:<br />

Identification signage is located at each floor level in all enclosed stairways in buildings two or more stories in height.<br />

Signs are a min. of 12” x 12” in size.<br />

Sign identifies the stairway location, floor level number, and upper and lower terminus of stairway.<br />

Information is presented with raised Arabic numerals and corresponding Grade II Braille.<br />

Sign is centered 60” above the floor landing immediately adjacent to the door on the strike side.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-96-1 (originally 1512-400)<br />

154


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

97. Hazards - North Stairwell on the 1st Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Underneath stairwell.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Any obstrution that overhangs a pedestrian way is a minimum 80” above the walking surface (measured from the bottom<br />

of the obstruction). (27” - 80”.)<br />

Sidewalks are clear of hazards.<br />

If vertical clearance of an area adjoining an accessible route is reduced to less than 80”, a barrier to warn blind or<br />

visually impaired persons is provided. (No barrier.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-97-1 (originally 1513-400)<br />

155


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

98. Doors - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate exterior doors. (8 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-98-1 (originally 1514-400)<br />

156


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-98-2 (originally 1515-400)<br />

157


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

99. Clear Space at Doors - North Entrance on the 1st Floor to <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-99-1 (originally 1516-400)<br />

158


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-99-2 (originally 1517-400)<br />

159


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

100. Signage - North Entrance on the 1st Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (None.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-100-1 (originally 1518-400)<br />

160


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

101. Tactile Exit Signage - North Entrance on the 1st Floor to <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Each grade-level exterior exit door shall be identified by a tactile sign with the word ”EXIT”. (None.)<br />

Recommendation:<br />

Provide compliant sign.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-101-1 (originally 1519-400)<br />

161


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

102. Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate exterior doors. (8 - 9 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-102-1 (originally 1520-400)<br />

162


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-102-2 (originally 1521-400)<br />

163


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

103. Clear Space at Doors - West Entrance on the 2nd Floor to <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-103-1 (originally 1522-400)<br />

164


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-103-2 (originally 1523-400)<br />

165


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

104. Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (No door sign.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-104-1 (originally 1524-400)<br />

166


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

105. Tactile Exit Signage - West Entrance on the 2nd Floor to <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />

exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />

appropriate. (Improper wording.)<br />

Recommendation:<br />

Provide compliant sign.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-105-1 (originally 1525-400)<br />

167


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

106. Doors - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (12 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-106-1 (originally 1526-400)<br />

168


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-106-2 (originally 1527-400)<br />

169


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

107. Clear Space at Doors - Unisex Restroom to the Left on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />

to water closet.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-107-1 (originally 1528-400)<br />

170


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-107-2 (originally 1529-400)<br />

171


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

108. Identification Symbols, Restrooms - Unisex Restroom to the Left on<br />

the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />

contrasts with the door, light on dark background or dark on light background. (No signage.)<br />

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />

identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />

Recommendation:<br />

Install door-mounted sign on single door.<br />

Install wall-mounted sign at single entrance.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-108-1 (originally 1530-400)<br />

172


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

109. Single Accommodation Toilet - Unisex Restroom to the Left on the<br />

2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Space for 30” x 48” wheelchair to enter and permit door to close.<br />

Privacy lock, push button, lever release.<br />

28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />

the water closet to opposite wall or partition.<br />

18” between centerline of water closet and side wall or partition.<br />

42” min. clearance between centerline of water closet and opposite wall.<br />

The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />

(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />

44” max. height to flush valve.<br />

Flush valve is on wide side of the water closet<br />

5 lb. max. force is required to operate the flush valve.<br />

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />

seat.<br />

19” min. height to toilet paper dispenser.<br />

Toilet paper dispenser provides continuous flow.<br />

Areas not meeting new construction standards:<br />

60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />

into the required clear space. (50”.)<br />

A minimum 60” wide and 48” deep clear floor space is provided in front of water closet. (60” x 44-1/4”.)<br />

Front of toilet paper dispenser is within 36” of the back wall. (38”.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />

173


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-109-1 (originally 1531-400)<br />

174


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

110. Toilet Grab Bars - Unisex Restroom to the Left on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

See Sequence #109 for additional recommendations.<br />

Areas noted in compliance:<br />

1-1/4” to 1-1/2” diameter of bars.<br />

1-1/2” clearance between bars and each wall or partition.<br />

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />

(33-1/2”.)<br />

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />

tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2”.)<br />

Side bar has 42” min. length.<br />

Side bar begins a max. of 12” from back wall.<br />

Back bar has 36” min. length.<br />

Back bar begins a max. of 6” from side wall.<br />

Bars are smooth with a min. edge radius of 1/8”.<br />

Grab bars do not rotate within their fittings.<br />

Min. structural strength to support 250 lb. point load.<br />

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />

Areas not meeting new construction standards:<br />

The front of the side grab bar extends 54” from back wall in single accommodation stall. (51-1/4”.)<br />

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />

items are allowed). (Toilet paper dispenser - 8” / seat cover dispenser - 5-3/4”.)<br />

Recommendation:<br />

Relocate grab bar.<br />

Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />

175


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-110-1 (originally 1531-400)<br />

176


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

111. Lavatories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />

space).<br />

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />

29” min. clearance from bottom of apron to floor surface.<br />

27” high x 8” deep knee clearance under front lip.<br />

30” wide x 9” high x 17” deep clearance from front of lavatory.<br />

Drain and piping is insulated or configured to prevent contact.<br />

There are no sharp or abrasive elements under lavatory.<br />

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />

5 lb. max. force required to operate controls.<br />

Areas not meeting new construction standards:<br />

18” minimum from center of fixture to side wall or partition. (17-1/2”.)<br />

34” max. height to rim or counter above floor surface. (34-1/4”.)<br />

Recommendation:<br />

Replace/Install accessible lavatory.<br />

177


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-111-1 (originally 1532-400)<br />

178


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

112. Accessories - Unisex Restroom to the Left on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

See Sequence #109 and #110 for additional recommendations.<br />

Areas noted in compliance:<br />

40” maximum height to bottom of reflective surface of mirror.<br />

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />

A maximum of 5 lbs. force is required to operate mechanisms.<br />

Areas not meeting new construction standards:<br />

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />

recepatacles, etc.). (Soap dispenser - 44” / seat covers - 48” / paper towels - 45-1/2” / toilet paper - 42-1/2”.)<br />

height above floor surface is recom-<br />

Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />

mended). (Coat hook - 66-1/2”.)<br />

Recommendation:<br />

Install accessible coat hook.<br />

Relocate the soap dispenser.<br />

Relocate the paper towel dispenser / hand dryer.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-112-1 (originally 1533-400)<br />

179


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-112-2 (originally 1534-400)<br />

180


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

113. Doors - Unisex Restroom to the Right on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (10 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-113-1 (originally 1538-400)<br />

181


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-113-2 (originally 1539-400)<br />

182


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

114. Clear Space at Doors - Unisex Restroom to the Right on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />

to the water closet.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-114-1 (originally 1540-400)<br />

183


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-114-2 (originally 1541-400)<br />

184


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

115. Identification Symbols, Restrooms - Unisex Restroom to the Right<br />

on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />

contrasts with the door, light on dark background or dark on light background. (No signage.)<br />

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />

identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />

Recommendation:<br />

Install door-mounted sign on single door.<br />

Install wall-mounted sign at single entrance.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-115-1 (originally 1542-400)<br />

185


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

116. Single Accommodation Toilet - Unisex Restroom to the Right on the<br />

2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Space for 30” x 48” wheelchair to enter and permit door to close.<br />

Privacy lock, push button, lever release.<br />

28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />

the water closet to opposite wall or partition.<br />

18” between centerline of water closet and side wall or partition. (18-3/4” (within dimensional tolerance).)<br />

42” min. clearance between centerline of water closet and opposite wall.<br />

The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />

(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />

44” max. height to flush valve.<br />

Flush valve is on wide side of the water closet<br />

5 lb. max. force is required to operate the flush valve.<br />

19” min. height to toilet paper dispenser.<br />

Toilet paper dispenser provides continuous flow.<br />

Areas not meeting new construction standards:<br />

60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />

into the required clear space. (50”.)<br />

A minimum 60” wide and 48” deep clear floor space is provided in front of water closet. (60” x 44”.)<br />

Front of toilet paper dispenser is within 36” of the back wall. (39-1/2”.)<br />

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />

seat. (13” and above.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />

186


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-116-1 (originally 1543-400)<br />

187


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

117. Toilet Grab Bars - Unisex Restroom to the Right on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

See Sequence #116 for additional recommendations.<br />

Areas noted in compliance:<br />

1-1/4” to 1-1/2” diameter of bars.<br />

1-1/2” clearance between bars and each wall or partition.<br />

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />

(33-1/2”.)<br />

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />

tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2”.)<br />

Side bar has 42” min. length.<br />

Side bar begins a max. of 12” from back wall.<br />

Back bar has 36” min. length.<br />

Back bar begins a max. of 6” from side wall.<br />

Bars are smooth with a min. edge radius of 1/8”.<br />

Grab bars do not rotate within their fittings.<br />

Min. structural strength to support 250 lb. point load.<br />

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />

Areas not meeting new construction standards:<br />

The front of the side grab bar extends 54” from back wall in single accommodation stall. (52”.)<br />

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />

items are allowed). (Toilet paper dispenser - 8-1/2” / seat cover dispenser - 5-3/4”.)<br />

Recommendation:<br />

Relocate grab bar.<br />

188


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-117-1 (originally 1544-400)<br />

189


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

118. Lavatories - Unisex Restroom to the Right on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />

space).<br />

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />

34” max. height to rim or counter above floor surface.<br />

29” min. clearance from bottom of apron to floor surface.<br />

27” high x 8” deep knee clearance under front lip.<br />

30” wide x 9” high x 17” deep clearance from front of lavatory.<br />

Drain and piping is insulated or configured to prevent contact.<br />

There are no sharp or abrasive elements under lavatory.<br />

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />

5 lb. max. force required to operate controls.<br />

Areas not meeting new construction standards:<br />

18” minimum from center of fixture to side wall or partition. (17”.)<br />

Recommendation:<br />

Replace/Install accessible lavatory.<br />

190


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-118-1 (originally 1545-400)<br />

191


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

119. Accessories - Unisex Restroom to the Right on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

See Sequence #116 and #117 for additional recommendations. Soap dispenser - 44-12” / paper towel dispenser - 45” /<br />

seat cover dispenser - 48” / toilet paper dispenser - 43”.<br />

Areas noted in compliance:<br />

40” maximum height to bottom of reflective surface of mirror.<br />

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />

A maximum of 5 lbs. force is required to operate mechanisms.<br />

Areas not meeting new construction standards:<br />

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />

recepatacles, etc.). (See memo.)<br />

height above floor surface is recom-<br />

Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />

mended). (Hook - 66”.)<br />

Recommendation:<br />

Install accessible coat hook.<br />

Relocate the soap dispenser.<br />

Relocate the paper towel dispenser / hand dryer.<br />

192


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-119-1 (originally 1546-400)<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-119-2 (originally 1547-400)<br />

193


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

120. Water Fountains (Drinking) - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

32” minimum wide and 18” minimum deep alcove provided.<br />

18” minimum depth of fountain.<br />

27” high x 8” deep clear knee space under fountain.<br />

9” high x 17” deep toe clearance.<br />

Lever or push bar control is located 6” max. from front edge.<br />

Bubbler outlet is 6” maximum from front.<br />

Bubbler outlet is 36” maximum from floor.<br />

4” minimum height of stream.<br />

Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficulty<br />

bending or stooping.<br />

Areas not meeting new construction standards:<br />

Stream of bubbler is parallel to front edge. (On angle.)<br />

The force required to activate controls does not exceed 5lbf. (6 lbs.)<br />

Recommendation:<br />

Adjust water pressure of existing fountain.<br />

Adjust angle of stream.<br />

194


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-120-1 (originally 1548-400)<br />

195


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

121. Controls, Operating Mechanisms & Vending Machines. - 2nd Floor<br />

Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fire extinguisher cabinet.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-121-1 (originally 1549-400)<br />

196


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

122. Seating, Tables and Work Surfaces - 2nd Floor Corridor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />

27” high, 30” wide and 19” deep knee clearance provided.<br />

28” - 34” height of table or work surface that is 36” wide.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-122-1 (originally 1550-400)<br />

197


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

123. Controls, Operating Mechanisms & Vending Machines. - 2nd Floor<br />

Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Copy machine.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-123-1 (originally 1551-400)<br />

198


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

124. Visual/Audible Alarms - 2nd Floor Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-124-1 (originally 1552-400)<br />

199


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

125. Electrical Controls & Receptacles/Fire Alarm Boxes - 2nd Floor<br />

Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform.<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform.<br />

The height of the manual fire alarm box is a minimum of 42” and a maximum of 48”, measured vertically, from the<br />

floor level to the highest point of the activating handle or lever of the box.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-125-1 (originally 1553-400)<br />

200


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-125-2 (originally 1554-400)<br />

201


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

126. Doors - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

15 lb. maximum pressure to operate fire doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-126-1 (originally 1555-400)<br />

202


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-126-2 (originally 1556-400)<br />

203


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

127. Clear Space at Doors - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-127-1 (originally 1557-400)<br />

204


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-127-2 (originally 1558-400)<br />

205


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

128. Signage - Fire Door on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (None.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-128-1 (originally 1559-400)<br />

206


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

129. Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (7 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-129-1 (originally 1565-400)<br />

207


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-129-2 (originally 1566-400)<br />

208


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

130. Clear Space at Doors - Room #204 on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-130-1 (originally 1567-400)<br />

209


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-130-2 (originally 1568-400)<br />

210


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

131. Signage - Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

211


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-131-1 (originally 1569-400)<br />

212


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

132. Seating, Tables and Work Surfaces - Room #204 on the 2nd Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />

27” high, 30” wide and 19” deep knee clearance provided.<br />

28” - 34” height of table or work surface that is 36” wide.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-132-1 (originally 1570-400)<br />

213


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

133. Doors - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

5 lb. maximum pressure to operate interior doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-133-1 (originally 1571-400)<br />

214


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-133-2 (originally 1572-400)<br />

215


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

134. Clear Space at Doors - Behind Room #204 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (3” to chair.)<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (0” to furniture.)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-134-1 (originally 1573-400)<br />

216


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-134-2 (originally 1574-400)<br />

217


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

135. Signage - Behind Room #204 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (None.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-135-1 (originally 1575-400)<br />

218


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

136. Sales and Service Counters - Room #205 on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />

A minimum 30” x 48” clear floor space is provided at the counter and;<br />

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />

Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and;<br />

Areas not meeting new construction standards:<br />

Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and; (25” high.)<br />

Recommendation:<br />

Cut skirt on the counter to comply with knee clearance.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-136-1 (originally 1576-400)<br />

219


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

137. Sinks - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Required clear space adjoins or overlaps an accessible route.<br />

Sink is a maximum of 6-1/2” deep.<br />

There are no sharp or abrasive elements under sink.<br />

Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />

5 lb. maximum force required to activate controls.<br />

Areas not meeting new construction standards:<br />

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />

34” maximum height of rim or counter above floor surfaces. (34-1/2” high.)<br />

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />

sink. (15” deep.)<br />

Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />

Recommendation:<br />

Replace/Install accessible sink.<br />

Insulate pipes under lavatory (or sink when applicable).<br />

Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />

220


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-137-1 (originally 1577-400)<br />

221


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

138. Controls, Operating Mechanisms & Vending Machines. - Room<br />

#205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-138-1 (originally 1580-400)<br />

222


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-138-2 (originally 1581-400)<br />

223


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

139. Controls, Operating Mechanisms & Vending Machines. - Room<br />

#205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood. See Sequence #140 for recommendation.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (58-1/2”.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-139-1 (originally 1582-400)<br />

224


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

140. Seating, Tables and Work Surfaces - Room #205 on the 2nd Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood. Relocate the flammable box.<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />

28” - 34” height of table or work surface that is 36” wide.<br />

Areas not meeting new construction standards:<br />

27” high, 30” wide and 19” deep knee clearance provided. (2” deep.)<br />

Recommendation:<br />

Replace the fume hood with an accessible fume hood workstation.<br />

Relocate furniture to provide clear space.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-140-1 (originally 1583-400)<br />

225


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

141. Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-141-1 (originally 1584-400)<br />

226


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

142. Protruding Objects - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Emergency eyewash.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-142-1 (originally 1585-400)<br />

227


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

143. Aisles - Room #205 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

36” minimum width of aisles. (21” - 27”.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-143-1 (originally 1586-400)<br />

228


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-143-2 (originally 1587-400)<br />

229


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

144. Doors - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Three doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (7 - 8 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-144-1 (originally 1588-400)<br />

230


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-144-2 (originally 1589-400)<br />

231


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

145. Clear Space at Doors - Rooms #205 and #206 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Three doors.<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-145-1 (originally 1590-400)<br />

232


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-145-2 (originally 1591-400)<br />

233


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

146. Signage - Rooms #205 and #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (58” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

234


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-146-1 (originally 1592-400)<br />

235


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

147. Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-147-1 (originally 1593-400)<br />

236


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-147-2 (originally 1594-400)<br />

237


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

148. Clear Space at Doors - Room #207 on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (5” to the table.)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-148-1 (originally 1595-400)<br />

238


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-148-2 (originally 1596-400)<br />

239


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

149. Signage - Room #207 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (58” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

240


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-149-1 (originally 1597-400)<br />

241


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

150. Sales and Service Counters - Room #206 on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Work counter.<br />

Areas noted in compliance:<br />

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />

A minimum 30” x 48” clear floor space is provided at the counter and;<br />

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-150-1 (originally 1600-400)<br />

242


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

151. Sinks - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Required clear space adjoins or overlaps an accessible route.<br />

34” maximum height of rim or counter above floor surfaces.<br />

There are no sharp or abrasive elements under sink.<br />

Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />

5 lb. maximum force required to activate controls.<br />

Areas not meeting new construction standards:<br />

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />

Sink is a maximum of 6-1/2” deep. (10” deep.)<br />

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />

sink. (25” high.)<br />

Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />

Recommendation:<br />

Replace/Install accessible sink.<br />

Insulate pipes under lavatory (or sink when applicable).<br />

Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />

243


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-151-1 (originally 1601-400)<br />

244


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

152. Controls, Operating Mechanisms & Vending Machines. - Room<br />

#206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-152-1 (originally 1602-400)<br />

245


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

153. Controls, Operating Mechanisms & Vending Machines. - Room<br />

#206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-153-1 (originally 1603-400)<br />

246


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-153-2 (originally 1604-400)<br />

247


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

154. Controls, Operating Mechanisms & Vending Machines. - Room<br />

#206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood. See Sequence #155 for recommendation.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (63” high.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-154-1 (originally 1605-400)<br />

248


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

155. Seating, Tables and Work Surfaces - Room #206 on the 2nd Floor<br />

at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor<br />

space.<br />

Areas not meeting new construction standards:<br />

28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />

Recommendation:<br />

Replace the fume hood with an accessible fume hood workstation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-155-1 (originally 1606-400)<br />

249


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

156. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-156-1 (originally 1607-400)<br />

250


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

157. Aisles - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

36” minimum width of aisles. (30” - 33”.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-157-1 (originally 1608-400)<br />

251


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-157-2 (originally 1609-400)<br />

252


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

158. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Emergency eye wash.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-158-1 (originally 1610-400)<br />

253


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

159. Protruding Objects - Room #206 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

MB RO B-G machine.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (15” projection.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-159-1 (originally 1611-400)<br />

254


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

160. Doors - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Two doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (11 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-160-1 (originally 1612-400)<br />

255


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-160-2 (originally 1613-400)<br />

256


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

161. Clear Space at Doors - Rooms #222 and #219 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (3” - 4” to shelves.)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-161-1 (originally 1614-400)<br />

257


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-161-2 (originally 1615-400)<br />

258


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

162. Signage - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (58” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

259


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-162-1 (originally 1616-400)<br />

260


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

163. Sales and Service Counters - Rooms #222 and #219 on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />

A minimum 30” x 48” clear floor space is provided at the counter and;<br />

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-163-1 (originally 1619-400)<br />

261


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

164. Sinks - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Required clear space adjoins or overlaps an accessible route.<br />

34” maximum height of rim or counter above floor surfaces.<br />

There are no sharp or abrasive elements under sink.<br />

Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />

5 lb. maximum force required to activate controls.<br />

Areas not meeting new construction standards:<br />

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />

Sink is a maximum of 6-1/2” deep. (10” deep.)<br />

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />

sink. (24” high.)<br />

Drain and hot water piping is insulated or configured to prevent contact. (None.)<br />

Recommendation:<br />

Replace/Install accessible sink.<br />

Insulate pipes under lavatory (or sink when applicable).<br />

Cut the paneling under the lavatory/sink counter to comply with knee clearance.<br />

262


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-164-1 (originally 1620-400)<br />

263


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

165. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />

#222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-165-1 (originally 1622-400)<br />

264


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-165-2 (originally 1623-400)<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-165-3 (originally 1624-400)<br />

265


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

166. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />

#222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (58” high x 60”<br />

high.)<br />

Recommendation:<br />

Relocate existing paper towel dispenser.<br />

Lower the machine.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-166-1 (originally 1625-400)<br />

266


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-166-2 (originally 1626-400)<br />

267


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

167. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />

#222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood. See Sequence #168 for recommendation.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (63” high.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-167-1 (originally 1627-400)<br />

268


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

168. Seating, Tables and Work Surfaces - Rooms #222 and #219 on the<br />

2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor<br />

space.<br />

Areas not meeting new construction standards:<br />

28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />

Recommendation:<br />

Replace the fume hood with an accessible fume hood workstation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-168-1 (originally 1628-400)<br />

269


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

169. Protruding Objects - Rooms #222 and #219 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-169-1 (originally 1629-400)<br />

270


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

170. Aisles - Rooms #222 and #219 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

36” minimum width of aisles. (29” - 35”.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-170-1 (originally 1630-400)<br />

271


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

171. Protruding Objects - Rooms #222 and #219 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Emergency eyewash.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />

Recommendation:<br />

Modify, relocate, replace or remove restricting objects.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-171-1 (originally 1631-400)<br />

272


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

172. Seating, Tables and Work Surfaces - Rooms #222 and #219 on the<br />

2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />

28” - 34” height of table or work surface that is 36” wide.<br />

Areas not meeting new construction standards:<br />

30” x 48” min. clear floor space is provided.<br />

27” high, 30” wide and 19” deep knee clearance provided. (28” wide.)<br />

Recommendation:<br />

Provide accessible table.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-172-1 (originally 1632-400)<br />

273


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

173. Doors - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Three doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (8 - 10 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-173-1 (originally 1633-400)<br />

274


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-173-2 (originally 1634-400)<br />

275


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

174. Clear Space at Doors - Rooms #218 and #221 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-174-1 (originally 1635-400)<br />

276


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-174-2 (originally 1636-400)<br />

277


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

175. Signage - Rooms #218 and #221 on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (55” high.)<br />

Recommendation:<br />

Relocate existing signage.<br />

278


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-175-1 (originally 1637-400)<br />

279


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

176. Doors - Rooms #202, #203, #225 and #224 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Four office doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

5 lb. maximum pressure to operate interior doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-176-1 (originally 1638-400)<br />

280


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

177. Clear Space at Doors - Rooms #202, #203, #225 and #224 on the<br />

2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Four office doors.<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PUSH side of door: 0”.<br />

Areas not meeting new construction standards:<br />

60” min. clear space in direction of door swing. (Varies.)<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (Varies.)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-177-1 (originally 1639-400)<br />

281


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

178. Signage - Rooms #202, #203, #225 and #224 on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Four office doors.<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (55”.)<br />

Recommendation:<br />

Relocate existing signage.<br />

282


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-178-1 (originally 1640-400)<br />

283


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

179. Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

32” minimum clear width of doorway. (31” wide.)<br />

5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Replace door and frame (concrete or block wall).<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-179-1 (originally 1641-400)<br />

284


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-179-2 (originally 1642-400)<br />

285


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

180. Clear Space at Doors - North Stairwell on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-180-1 (originally 1643-400)<br />

286


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-180-2 (originally 1644-400)<br />

287


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

181. Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (None.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-181-1 (originally 1645-400)<br />

288


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

182. Tactile Exit Signage - North Stairwell on the 2nd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />

exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />

appropriate. (Improper wording.)<br />

Recommendation:<br />

Provide compliant sign.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-182-1 (originally 1645-400)<br />

289


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

183. Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate exterior doors. (8 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-183-1 (originally 1646-400)<br />

290


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-183-2 (originally 1647-400)<br />

291


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

184. Clear Space at Doors - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd<br />

Floor.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-184-1 (originally 1648-400)<br />

292


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-184-2 (originally 1649-400)<br />

293


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

185. Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd Floor.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right.<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-185-1 (originally 1650-400)<br />

294


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

186. Tactile Exit Signage - North Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 2nd<br />

Floor.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Each grade-level exterior exit door shall be identified by a tactile sign with the word ”EXIT”. (No sign.)<br />

Recommendation:<br />

Provide compliant sign.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-186-1 (originally 1651-400)<br />

295


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

187. Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate exterior doors. (8 lbs.)<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-187-1 (originally 1652-400)<br />

296


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-187-2 (originally 1653-400)<br />

297


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

188. Clear Space at Doors - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd<br />

Floor.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-188-1 (originally 1654-400)<br />

298


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-188-2 (originally 1655-400)<br />

299


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

189. Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd Floor.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (No door sign.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-189-1 (originally 1656-400)<br />

300


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

190. Tactile Exit Signage - West Entrance to <strong>Pierce</strong> <strong>Annex</strong> on the 3rd<br />

Floor.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />

exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />

appropriate. (Improper wording.)<br />

Recommendation:<br />

Provide compliant sign.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-190-1 (originally 1657-400)<br />

301


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

191. Doors - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (12 lbs.)<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2.5 seconds.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-191-1 (originally 1658-400)<br />

302


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-191-2 (originally 1659-400)<br />

303


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

192. Clear Space at Doors - Unisex Restroom on the Left on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />

to the water closet.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-192-1 (originally 1660-400)<br />

304


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-192-2 (originally 1661-400)<br />

305


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

193. Identification Symbols, Restrooms - Unisex Restroom on the Left on<br />

the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />

contrasts with the door, light on dark background or dark on light background. (No signage.)<br />

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />

identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />

Recommendation:<br />

Install door-mounted sign on single door.<br />

Install wall-mounted sign at single entrance.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-193-1 (originally 1662-400)<br />

306


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

194. Single Accommodation Toilet - Unisex Restroom on the Left on the<br />

3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Space for 30” x 48” wheelchair to enter and permit door to close.<br />

Privacy lock, push button, lever release.<br />

28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />

the water closet to opposite wall or partition.<br />

18” between centerline of water closet and side wall or partition. (18-1/2” (within dimensional tolerance).)<br />

42” min. clearance between centerline of water closet and opposite wall.<br />

A minimum 60” wide and 48” deep clear floor space is provided in front of water closet.<br />

The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />

(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />

44” max. height to flush valve.<br />

Flush valve is on wide side of the water closet<br />

5 lb. max. force is required to operate the flush valve.<br />

19” min. height to toilet paper dispenser.<br />

Toilet paper dispenser provides continuous flow.<br />

Areas not meeting new construction standards:<br />

60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />

into the required clear space. (50”.)<br />

Front of toilet paper dispenser is within 36” of the back wall. (37”.)<br />

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />

seat. (Above grab bar.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />

307


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-194-1 (originally 1663-400)<br />

308


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

195. Toilet Grab Bars - Unisex Restroom on the Left on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

See Sequence #194 for additional recommendations.<br />

Areas noted in compliance:<br />

1-1/4” to 1-1/2” diameter of bars.<br />

1-1/2” clearance between bars and each wall or partition.<br />

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />

(33-3/4”.)<br />

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />

tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-3/4”.)<br />

Side bar has 42” min. length.<br />

Side bar begins a max. of 12” from back wall.<br />

Back bar has 36” min. length.<br />

Back bar begins a max. of 6” from side wall.<br />

Bars are smooth with a min. edge radius of 1/8”.<br />

Grab bars do not rotate within their fittings.<br />

Min. structural strength to support 250 lb. point load.<br />

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />

Areas not meeting new construction standards:<br />

The front of the side grab bar extends 54” from back wall in single accommodation stall. (51-1/2”.)<br />

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />

items are allowed). (Toilet paper dispenser - 8-1/2” / seat cover dispenser - 5-1/2”.)<br />

Recommendation:<br />

Relocate grab bar.<br />

Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />

309


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-195-1 (originally 1663-400)<br />

310


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

196. Lavatories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />

space).<br />

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />

29” min. clearance from bottom of apron to floor surface.<br />

27” high x 8” deep knee clearance under front lip.<br />

30” wide x 9” high x 17” deep clearance from front of lavatory.<br />

Drain and piping is insulated or configured to prevent contact.<br />

There are no sharp or abrasive elements under lavatory.<br />

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />

5 lb. max. force required to operate controls.<br />

Areas not meeting new construction standards:<br />

18” minimum from center of fixture to side wall or partition. (17-1/4”.)<br />

34” max. height to rim or counter above floor surface. (34-1/4”.)<br />

Recommendation:<br />

Replace/Install accessible lavatory.<br />

311


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-196-1 (originally 1664-400)<br />

312


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

197. Accessories - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

See Sequence #194 and #195 for additional recommendations. Soap dispenser - 43” / paper towel dispenser - 45” / seat<br />

cover dispenser - 48” / toilet paper dispenser - 42-1/4”.<br />

Areas noted in compliance:<br />

40” maximum height to bottom of reflective surface of mirror.<br />

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />

A maximum of 5 lbs. force is required to operate mechanisms.<br />

Areas not meeting new construction standards:<br />

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />

recepatacles, etc.). (See memo.)<br />

height above floor surface is recom-<br />

Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />

mended). (66-1/2”.)<br />

Recommendation:<br />

Install accessible coat hook.<br />

Relocate the soap dispenser.<br />

Relocate the paper towel dispenser / hand dryer.<br />

313


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-197-1 (originally 1666-400)<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-197-2 (originally 1667-400)<br />

314


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

198. Doors - Unisex Restroom on the Right on the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-198-1 (originally 1671-400)<br />

315


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-198-2 (originally 1672-400)<br />

316


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

199. Clear Space at Doors - Unisex Restroom on the Right on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Areas not meeting new construction standards:<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (12” wide x 44-1/2” deep<br />

to the water closet.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-199-1 (originally 1673-400)<br />

317


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-199-2 (originally 1674-400)<br />

318


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

200. Identification Symbols, Restrooms - Unisex Restroom on the Right<br />

on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Unisex - 12” diameter circle 1/4” thick with 1/4” thick triangle superimposed in the circle. The circle and triangle symbols<br />

contrasts with the door, light on dark background or dark on light background. (No signage.)<br />

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (Incorrect.)<br />

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal<br />

identification and the border dimensions of this pictogram is a minimum of 6” in height. (Incorrect.)<br />

Recommendation:<br />

Install door-mounted sign on single door.<br />

Install wall-mounted sign at single entrance.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-200-1 (originally 1675-400)<br />

319


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

201. Single Accommodation Toilet - Unisex Restroom on the Right on the<br />

3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Space for 30” x 48” wheelchair to enter and permit door to close.<br />

Privacy lock, push button, lever release.<br />

28” minimum between the side of the water closet and any fixture or a minimum of 32” clear space between the side of<br />

the water closet to opposite wall or partition.<br />

18” between centerline of water closet and side wall or partition.<br />

42” min. clearance between centerline of water closet and opposite wall.<br />

The top of the toilet seat is 17” - 19” from the floor surface measured to the top of a maximum 2” high toilet seat<br />

(a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).<br />

44” max. height to flush valve.<br />

Flush valve is on wide side of the water closet<br />

5 lb. max. force is required to operate the flush valve.<br />

19” min. height to toilet paper dispenser.<br />

Toilet paper dispenser provides continuous flow.<br />

Areas not meeting new construction standards:<br />

60” minimum diameter turning circle, or a T-shaped clear space, is provided in room with 12” maximum door encroachment<br />

into the required clear space. (50”.)<br />

A minimum 60” wide and 48” deep clear floor space is provided in front of water closet. (60” x 44”.)<br />

Front of toilet paper dispenser is within 36” of the back wall. (37-1/2”.)<br />

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet<br />

seat. (13” and above grab bar.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.<br />

320


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-201-1 (originally 1676-400)<br />

321


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

202. Toilet Grab Bars - Unisex Restroom on the Right on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

See Sequence #201 for additional recommendations.<br />

Areas noted in compliance:<br />

1-1/4” to 1-1/2” diameter of bars.<br />

1-1/2” clearance between bars and each wall or partition.<br />

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.<br />

(33-1/2”.)<br />

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for<br />

tank type toilets, 36” may be allowed if tank obstructs placement of bar). (33-1/2”.)<br />

Side bar has 42” min. length.<br />

Side bar begins a max. of 12” from back wall.<br />

Back bar has 36” min. length.<br />

Back bar begins a max. of 6” from side wall.<br />

Bars are smooth with a min. edge radius of 1/8”.<br />

Grab bars do not rotate within their fittings.<br />

Min. structural strength to support 250 lb. point load.<br />

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.<br />

Areas not meeting new construction standards:<br />

The front of the side grab bar extends 54” from back wall in single accommodation stall. (52”.)<br />

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed<br />

items are allowed). (Toilet paper dispenser - 8” / seat cover dispenser - 5-1/2”.)<br />

Recommendation:<br />

Relocate grab bar.<br />

Relocate the seat cover dispenser away from the top of the grab bars or proposed grab bars.<br />

322


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-202-1 (originally 1677-400)<br />

323


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

203. Lavatories - Unisex Restroom on the Right on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />

space).<br />

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />

34” max. height to rim or counter above floor surface.<br />

29” min. clearance from bottom of apron to floor surface.<br />

27” high x 8” deep knee clearance under front lip.<br />

30” wide x 9” high x 17” deep clearance from front of lavatory.<br />

Drain and piping is insulated or configured to prevent contact.<br />

There are no sharp or abrasive elements under lavatory.<br />

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />

5 lb. max. force required to operate controls.<br />

Areas not meeting new construction standards:<br />

18” minimum from center of fixture to side wall or partition. (17-1/2”.)<br />

Recommendation:<br />

Replace/Install accessible lavatory.<br />

324


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-203-1 (originally 1679-400)<br />

325


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

204. Accessories - Unisex Restroom on the Right on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

See Sequence #201 and #202 for additional recommendations.<br />

Areas noted in compliance:<br />

40” maximum height to bottom of reflective surface of mirror.<br />

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.<br />

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.<br />

A maximum of 5 lbs. force is required to operate mechanisms.<br />

Areas not meeting new construction standards:<br />

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste<br />

recepatacles, etc.). (Soap dispenser - 44-1/2” / paper towels - 45” / seat covers - 48” / toilet paper - 42-1/2”.)<br />

height above floor surface is recom-<br />

Coat hooks and shelving are located within appropriate reach ranges (48” max.<br />

mended). (66-1/2”.)<br />

Recommendation:<br />

Install accessible coat hook.<br />

Relocate the paper towel dispenser / hand dryer.<br />

Relocate the soap dispenser.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-204-1 (originally 1680-400)<br />

326


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-204-2 (originally 1681-400)<br />

327


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

205. Electrical Controls & Receptacles/Fire Alarm Boxes - Unisex<br />

Restroom on the Right on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform.<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-205-1 (originally 1682-400)<br />

328


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-205-2 (originally 1683-400)<br />

329


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

206. Corridors - 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

44” minimum width for occupant loads of 10 or more.<br />

Corridors over 200’ must have ONE of: 60” minimum clear width,<br />

and 60” x 60” turning space at central location, or,<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-206-1 (originally 1684-400)<br />

330


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-206-2 (originally 1685-400)<br />

331


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

207. Water Fountains (Drinking) - Corridor on the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

32” minimum wide and 18” minimum deep alcove provided.<br />

18” minimum depth of fountain.<br />

27” high x 8” deep clear knee space under fountain.<br />

9” high x 17” deep toe clearance.<br />

Lever or push bar control is located 6” max. from front edge.<br />

Bubbler outlet is 6” maximum from front.<br />

Bubbler outlet is 36” maximum from floor.<br />

4” minimum height of stream.<br />

Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficulty<br />

bending or stooping.<br />

Areas not meeting new construction standards:<br />

Stream of bubbler is parallel to front edge. (On angle.)<br />

The force required to activate controls does not exceed 5lbf. (7 lbs.)<br />

Recommendation:<br />

Adjust angle of stream.<br />

Reduce force needed to operate fountain controls ( 5 lb. maximum).<br />

332


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-207-1 (originally 1686-400)<br />

333


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

208. Controls, Operating Mechanisms & Vending Machines. - Corridor on<br />

the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fire extinguisher.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-208-1 (originally 1687-400)<br />

334


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

209. Doors - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

15 lb. maximum pressure to operate fire doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-209-1 (originally 1688-400)<br />

335


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-209-2 (originally 1689-400)<br />

336


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

210. Clear Space at Doors - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

One set of double doors.<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-210-1 (originally 1690-400)<br />

337


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-210-2 (originally 1691-400)<br />

338


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

211. Signage - Fire Doors on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (None.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-211-1 (originally 1692-400)<br />

339


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

212. Doors - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (8 - 10 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-212-1 (originally 1693-400)<br />

340


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-212-2 (originally 1694-400)<br />

341


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

213. Clear Space at Doors - Rooms #321 and #318 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-213-1 (originally 1695-400)<br />

342


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-213-2 (originally 1696-400)<br />

343


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

214. Signage - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />

Recommendation:<br />

Relocate existing signage.<br />

344


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-214-1 (originally 1697-400)<br />

345


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

215. Sales and Service Counters - Rooms #321 and #318 on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />

A minimum 30” x 48” clear floor space is provided at the counter and;<br />

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-215-1 (originally 1699-400)<br />

346


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

216. Sinks - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />

Required clear space adjoins or overlaps an accessible route.<br />

34” maximum height of rim or counter above floor surfaces.<br />

Sink is a maximum of 6-1/2” deep.<br />

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />

sink.<br />

Drain and hot water piping is insulated or configured to prevent contact.<br />

There are no sharp or abrasive elements under sink.<br />

Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />

5 lb. maximum force required to activate controls.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

347


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-216-1 (originally 1700-400)<br />

348


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

217. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />

#321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-217-1 (originally 1701-400)<br />

349


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-217-2 (originally 1702-400)<br />

350


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

218. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />

#321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Knob.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-218-1 (originally 1703-400)<br />

351


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-218-2 (originally 1704-400)<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-218-3 (originally 1705-400)<br />

352


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

219. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />

#321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood. See Sequence #220 for recommendation.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (63” high.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-219-1 (originally 1706-400)<br />

353


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

220. Seating, Tables and Work Surfaces - Rooms #321 and #318 on the<br />

3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.<br />

27” high, 30” wide and 19” deep knee clearance provided.<br />

Areas not meeting new construction standards:<br />

28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />

Recommendation:<br />

Replace the fume hood with an accessible fume hood workstation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-220-1 (originally 1707-400)<br />

354


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

221. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Eight fume hoods.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-221-1 (originally 1708-400)<br />

355


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

222. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Two emergency eyewash controls.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-222-1 (originally 1709-400)<br />

356


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

223. Aisles - Rooms #321 and #318 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

36” minimum width of aisles. (32”.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-223-1 (originally 1710-400)<br />

357


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

224. Floors and Levels - Rooms #321 and #318 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Four carpets / mats.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Carpets or carpet tiles are securely attached and do not exceed 1/2” in height. (Not secured.)<br />

Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length. (Not fastened.)<br />

Recommendation:<br />

Secure loose doormat.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-224-1 (originally 1711-400)<br />

358


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

225. Protruding Objects - Rooms #321 and #318 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Shelf on machine.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (9”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-225-1 (originally 1712-400)<br />

359


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

226. Doors - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Three doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (7 - 11 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-226-1 (originally 1713-400)<br />

360


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-226-2 (originally 1714-400)<br />

361


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

227. Clear Space at Doors - Rooms #319 and #317 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-227-1 (originally 1715-400)<br />

362


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-227-2 (originally 1716-400)<br />

363


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

228. Signage - Rooms #319 and #317 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />

Recommendation:<br />

Relocate existing signage.<br />

364


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-228-1 (originally 1717-400)<br />

365


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

229. Doors - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (9 - 10 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-229-1 (originally 1718-400)<br />

366


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-229-2 (originally 1719-400)<br />

367


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

230. Clear Space at Doors - Rooms #307 and #304 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-230-1 (originally 1720-400)<br />

368


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-230-2 (originally 1721-400)<br />

369


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

231. Signage - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />

Recommendation:<br />

Relocate existing signage.<br />

370


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-231-1 (originally 1722-400)<br />

371


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

232. Sales and Service Counters - Rooms #307 and #304 on the 3rd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and;<br />

A minimum 30” x 48” clear floor space is provided at the counter and;<br />

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-232-1 (originally 1724-400)<br />

372


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

233. Sinks - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.<br />

Required clear space adjoins or overlaps an accessible route.<br />

34” maximum height of rim or counter above floor surfaces.<br />

There are no sharp or abrasive elements under sink.<br />

Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.<br />

5 lb. maximum force required to activate controls.<br />

Areas not meeting new construction standards:<br />

Sink is a maximum of 6-1/2” deep. (10” deep.)<br />

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the<br />

sink. (24” high.)<br />

Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)<br />

Recommendation:<br />

Replace/Install accessible sink.<br />

Insulate pipes under lavatory (or sink when applicable).<br />

373


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-233-1 (originally 1725-400)<br />

374


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

234. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />

#307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-234-1 (originally 1726-400)<br />

375


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-234-2 (originally 1727-400)<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-234-3 (originally 1728-400)<br />

376


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

235. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />

#307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Various machines.<br />

Areas noted in compliance:<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate. (Knobs.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-235-1 (originally 1729-400)<br />

377


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-235-2 (originally 1730-400)<br />

378


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

236. Controls, Operating Mechanisms & Vending Machines. - Rooms<br />

#307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood. See Sequence #237 for recommendation.<br />

Areas noted in compliance:<br />

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not<br />

require tight grasping, pinching or twisting of the wrist to operate.<br />

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.<br />

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.<br />

Areas not meeting new construction standards:<br />

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (63”.)<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-236-1 (originally 1731-400)<br />

379


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

237. Seating, Tables and Work Surfaces - Rooms #307 and #304 on the<br />

3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

30” x 48” min. clear floor space is provided.<br />

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor<br />

space.<br />

Areas not meeting new construction standards:<br />

27” high, 30” wide and 19” deep knee clearance provided. (0” deep.)<br />

28” - 34” height of table or work surface that is 36” wide. (35” high.)<br />

Recommendation:<br />

Replace the fume hood with an accessible fume hood workstation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-237-1 (originally 1732-400)<br />

380


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

238. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Fume hood.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (5”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-238-1 (originally 1733-400)<br />

381


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

239. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Two eyewash controls.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (6”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-239-1 (originally 1734-400)<br />

382


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

240. Aisles - Rooms #307 and #304 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

36” minimum width of aisles. (32”.)<br />

Recommendation:<br />

Requires engineering/architectural evaluation.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-240-1 (originally 1736-400)<br />

383


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

241. Protruding Objects - Rooms #307 and #304 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Shelf on machine.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways<br />

or aisles if lower edge of object is above 27” and below 80”. (9”.)<br />

Recommendation:<br />

Install cane detectable barrier below object.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-241-1 (originally 1737-400)<br />

384


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

242. Doors - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Three doors.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (8 - 10 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-242-1 (originally 1738-400)<br />

385


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-242-2 (originally 1739-400)<br />

386


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

243. Clear Space at Doors - Rooms #306 and #305 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-243-1 (originally 1740-400)<br />

387


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-243-2 (originally 1741-400)<br />

388


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

244. Signage - Rooms #306 and #305 on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />

Recommendation:<br />

Relocate existing signage.<br />

389


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-244-1 (originally 1742-400)<br />

390


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

245. Doors - Rooms #323, #324, #303 and #302 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

No access into Room #324 due to radioactivity in progress.<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

5 lb. maximum pressure to operate interior doors.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-245-1 (originally 1748-400)<br />

391


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-245-2 (originally 1749-400)<br />

392


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

246. Clear Space at Doors - Rooms #323, #324, #303 and #302 on the<br />

3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PUSH side of door: 0”.<br />

Areas not meeting new construction standards:<br />

60” min. clear space in direction of door swing. (Varies.)<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (Varies.)<br />

Recommendation:<br />

Relocate furniture to provide clear space.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-246-1 (originally 1750-400)<br />

393


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-246-2 (originally 1751-400)<br />

394


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

247. Signage - Rooms #323, #324, #303 and #302 on the 3rd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille.<br />

Raised characters are 5/8” to 2” high.<br />

Braille dots are 1/10” on center in each cell with 2/10” space between cells.<br />

Braille dots are raised a minimum 1/40” above the background.<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Mounting location allows a person to approach within 3” of the signage without encountering protruding objects or<br />

standing w/in the swing of a door.<br />

Characters and background of sign(s) is eggshell, matte or other non-glare finish.<br />

Characters contrast with their background (light characters on a dark background, or dark characters on a light background).<br />

Areas not meeting new construction standards:<br />

Mounting height is 60” from the finish floor to the centerline of the sign. (58”.)<br />

Recommendation:<br />

Relocate existing signage.<br />

395


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-247-1 (originally 1752-400)<br />

396


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

248. Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

32” minimum clear width of doorway. (31” wide.)<br />

5 lb. maximum pressure to operate interior doors. (9 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Replace door and frame (concrete or block wall).<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-248-1 (originally 1753-400)<br />

397


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-248-2 (originally 1754-400)<br />

398


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

249. Clear Space at Doors - North Stairwell on the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-249-1 (originally 1755-400)<br />

399


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-249-2 (originally 1756-400)<br />

400


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

250. Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (No door sign.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-250-1 (originally 1757-400)<br />

401


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

251. Tactile Exit Signage - North Stairwell on the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactile<br />

exit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, as<br />

appropriate. (Improper wording.)<br />

Recommendation:<br />

Provide compliant sign.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-251-1 (originally 1757-400)<br />

402


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

252. Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate exterior doors. (8 lbs.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-252-1 (originally 1758-400)<br />

403


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-252-2 (originally 1759-400)<br />

404


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

253. Clear Space at Doors - North Entrance on the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Floor or landing is level and clear (2% max. slope).<br />

60” min. clear space in direction of door swing.<br />

44” min. clear space opposite direction of door swing (48” with latch and closer).<br />

Minimum strike side clearance on PULL side of door: 24” exterior doors.<br />

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-253-1 (originally 1760-400)<br />

405


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-253-2 (originally 1761-400)<br />

406


University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

254. Signage - North Entrance on the 3rd Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

No signage.<br />

Areas noted in compliance:<br />

None observed.<br />

Areas not meeting new construction standards:<br />

Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At double<br />

leaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably on<br />

the right. (None.)<br />

Recommendation:<br />

Install permanent ID sign to latch side of door.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-254-1 (originally 1762-400)<br />

407