Report #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong><br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

179-Doors: North<br />

Stairwell on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

32" minimum clear width of doorway. 5 lb.<br />

maximum pressure to operate interior doors.<br />

Adjust door opening pressure<br />

/ closing time unless accepted<br />

by DSA Fire / Life Safety.<br />

Consider issues connected<br />

with building pressure / climate<br />

control. Replace door and<br />

frame (concrete or block wall).<br />

2 $5,573.87<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

181-Signage: North<br />

Stairwell on the 2nd<br />

Floor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

182-Tactile Exit<br />

Signage: North Stairwell<br />

on the 2nd Floor at<br />

<strong>Pierce</strong> <strong>Annex</strong>.<br />

183-Doors: North<br />

Entrance to <strong>Pierce</strong><br />

<strong>Annex</strong> on the 2nd Floor.<br />

[One set of double<br />

doors.]<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each exit door that leads directly to a gradelevel<br />

exterior exit by means of a stairway or<br />

ramp is identified by a tactile exit sign that states<br />

"EXIT STAIR DOWN", "EXIT RAMP DOWN",<br />

"EXIT STAIR UP", or "EXIT RAMP UP", as<br />

appropriate.<br />

5 lb. maximum pressure to operate exterior<br />

doors.<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

Adjust door opening pressure /<br />

closing time unless accepted by<br />

DSA Fire / Life Safety. Consider<br />

issues connected with building<br />

pressure / climate control.<br />

2 $306.26<br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

UCR P5508<br />

<strong>Pierce</strong><br />

<strong>Annex</strong><br />

185-Signage: North<br />

Entrance to <strong>Pierce</strong><br />

<strong>Annex</strong> on the 2nd Floor.<br />

186-Tactile Exit<br />

Signage: North Entrance<br />

to <strong>Pierce</strong> <strong>Annex</strong> on the<br />

2nd Floor.<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall be<br />

placed on the nearest adjacent wall, preferably<br />

on the right.<br />

Each grade-level exterior exit door shall be<br />

identified by a tactile sign with the word "EXIT".<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $183.75<br />

Provide compliant sign. 1 $183.75<br />

6/1/2012 Page 23 of 32