University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

191. Doors - Unisex Restroom on the Left on the 3rd Floor at <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

Opens a min. of 90 degrees.<br />

1/4” maximum vertical threshold or 1/2” beveled at 1:2.<br />

32” minimum clear width of doorway.<br />

Door hardware is operable with a single effort (lever type, panic bar or push pull type).<br />

Hardware is 30” to 44” above floor.<br />

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be<br />

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).<br />

Areas not meeting new construction standards:<br />

5 lb. maximum pressure to operate interior doors. (12 lbs.)<br />

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2.5 seconds.)<br />

Recommendation:<br />

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-191-1 (originally 1658-400)<br />