University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

25. Visual/Audible Alarms - Unisex Restroom to the Right on the 1st<br />

Floor of <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

The alarm is integrated into the building or facility alarm system.<br />

Lamp is a xenon strobe type or equivalent.<br />

The color is clear and nominal white (unfiltered) or clear filtered white light.<br />

The maximum pulse duration is two-tenths of one second (0.2 sec) with a maximum duty cycle of 40 percent.<br />

The intensity is a maximum of 75 candela.<br />

The flash rate is a minimum of 1Hz and a maximum of 3Hz.<br />

The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.<br />

When provided/required, audible emergency alarms meet applicable requirements.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-25-1 (originally 0033-400)<br />