University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

125. Electrical Controls & Receptacles/Fire Alarm Boxes - 2nd Floor<br />

Corridor at <strong>Pierce</strong> <strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”<br />

max. above the floor or working platform.<br />

The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor<br />

or working platform.<br />

The height of the manual fire alarm box is a minimum of 42” and a maximum of 48”, measured vertically, from the<br />

floor level to the highest point of the activating handle or lever of the box.<br />

Areas not meeting new construction standards:<br />

None observed.<br />

Recommendation:<br />

None.<br />

Photo #UCR P5508 <strong>Pierce</strong> <strong>Annex</strong>-125-1 (originally 1553-400)<br />