University of California at Riverside<br />

Site Evaluation Survey<br />

Report: UCR P5508 <strong>Pierce</strong> <strong>Annex</strong> in Riverside, CA<br />

900 University Avenue<br />

23. Lavatories - Unisex Restroom to the Right on the 1st Floor of <strong>Pierce</strong><br />

<strong>Annex</strong>.<br />

Memo:<br />

Areas noted in compliance:<br />

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this<br />

space).<br />

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.<br />

34” max. height to rim or counter above floor surface.<br />

29” min. clearance from bottom of apron to floor surface.<br />

27” high x 8” deep knee clearance under front lip.<br />

30” wide x 9” high x 17” deep clearance from front of lavatory.<br />

Drain and piping is insulated or configured to prevent contact.<br />

There are no sharp or abrasive elements under lavatory.<br />

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).<br />

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.<br />

5 lb. max. force required to operate controls.<br />

Areas not meeting new construction standards:<br />

18” minimum from center of fixture to side wall or partition. (17-1/2”.)<br />

Recommendation:<br />

Replace/Install accessible lavatory.<br />