32 <strong>VRIOGS</strong> <strong>012.2.1</strong> REVISION A<br />

9.8 Transition between Cable Ladder/Cable Ladder/GST/GLT/Buried<br />

Route<br />

a) The transition between different cable ladder sizes shall be made using purpose<br />

built adaptors from the ladder manufacturer’s product range<br />

b) The transition between cable ladder and GST, GLT, pits or buried route including<br />

ULX and URX shall be made using purpose built adaptors fabricated from the same<br />

material as the cable ladder.<br />

c) The adaptor for ULX and URX shall be of sufficient size to accommodate all<br />

conduits from the ULX or URX, including spare conduits and shall extend from the<br />

cable route to within 300 mm of ground level.<br />

d) The void between the adaptor and the conduits shall be sealed.<br />

e) Modifications to the cable ladder to accommodate the adaptor shall not result in<br />

cables in the cable ladder being unsupported over lengths exceeding 600 mm.<br />

9.9 Cable Ladder Arrangements at Connection to Local Cable Route<br />

and Equipment<br />

a) The connection of the main cable ladder route to local cable route and equipment<br />

shall be made using purpose built tee pieces from the ladder manufacturer’s product<br />

range.<br />

9.10 Cable Ladder Covers<br />

a) Cable ladder covers are only required where the bottom of the cable ladder is less<br />

than 2.4 m above the adjacent rail level unless otherwise specified.<br />

b) Covers shall not be fitted until the cables have been inspected and approved.<br />

c) Cable ladder covers shall overlap the adjacent covers by a minimum of 20 mm<br />

(away from the direction of normal train movements) and shall be secured with<br />

stainless steel straps, one 100 mm from each end of each lid plus additional straps<br />

as required to ensure a maximum of 600 mm intervals between straps for 600 mm<br />

wide ladder and a maximum of 800 mm intervals between straps for other ladder<br />

widths.<br />