2. Detailed Specifications<br />

Earth-Leakage Circuit Breakers<br />

Series<br />

Frame size<br />

C series S series C series S series<br />

H series C series<br />

30<br />

32<br />

63<br />

63<br />

63<br />

125<br />

Photo<br />

Type name<br />

Rated current In (Amp.)<br />

Rated ambient temperature (°C)<br />

Number of poles<br />

Rated operational voltage Ue (AC V)<br />

NV30-CS<br />

5 10 15<br />

20 30<br />

40<br />

3<br />

NV32-SW<br />

(5) 6 10 (15) 16<br />

20 25 (30) 32<br />

40<br />

3<br />

NV63-CW<br />

(5) (10) (15) 16 20 25<br />

(30) 32 40 50 (60) 63<br />

40<br />

3<br />

NV63-SW<br />

(5) (10) (15) 16 20 25<br />

(30) 32 40 50 (60) 63<br />

40<br />

3<br />

NV63-HW<br />

(15) 16 20 25 (30)<br />

32 40 50 (60) 63<br />

40<br />

3<br />

NV125-CW<br />

(60) 63 (75) 80<br />

100 125<br />

40<br />

3<br />

✽6<br />

100–230<br />

100–440<br />

100–440<br />

100–440<br />

100–440<br />

100–440<br />

Multi-voltage type Multi-voltage type Multi-voltage type Multi-voltage type Multi-voltage type<br />

30,100 •200 •500 30,100 •200 •500 30,100 •200 •500 30,100 •200 •500 30,100 •200 •500<br />

High-speed type<br />

Rated current sensitivity I∆n (mA)<br />

30<br />

Selectable Selectable Selectable Selectable Selectable<br />

Max. operating time at 5I∆n (s)<br />

Rated current sensitivity I∆n (mA)<br />

0.04<br />

–<br />

0.04<br />

–<br />

0.04<br />

–<br />

0.04<br />

–<br />

0.04<br />

–<br />

0.04<br />

100 •200 •500<br />

Selectable<br />

Time-delay type<br />

Max. operating time at 2I∆n (s)<br />

–<br />

–<br />

–<br />

–<br />

–<br />

0.45 •1.0 •2.0<br />

Selectable<br />

Inertial non-operating time at 2I∆n (s)<br />

Earth-leakage indication system<br />

–<br />

Button<br />

–<br />

Button<br />

–<br />

Button<br />

–<br />

Button<br />

–<br />

Button<br />

(0.1•0.5 •1.0)<br />

Button<br />

AC440V<br />

–<br />

5/2<br />

2.5/1<br />

7.5/4<br />

10/5<br />

10/5<br />

Rated short-circuit breaking capacity (kA)<br />

AC400V<br />

–<br />

5/2<br />

5/2<br />

7.5/4<br />

10/5<br />

10/5<br />

IEC60947-2 (Icu/Ics)<br />

AC230V 2.5/2<br />

10/5<br />

7.5/4<br />

15/8<br />

25/13<br />

30/15<br />

without current<br />

10,000<br />

10,000<br />

10,000<br />

15,000<br />

15,000<br />

10,000<br />

Number of operating cycles<br />

440V-In/2 6,000 (230V) 6,000<br />

6,000<br />

15,000<br />

15,000<br />

6,000<br />

with current<br />

440V-In 6,000 (230V) 6,000<br />

6,000<br />

8,000<br />

8,000<br />

6,000<br />

a ca c<br />

a<br />

67.5<br />

75<br />

75<br />

75<br />

75<br />

90<br />

Overall dimensions (mm)<br />

b<br />

96<br />

130<br />

130<br />

130<br />

130<br />

130<br />

b<br />

c<br />

ca<br />

52<br />

67<br />

68<br />

90<br />

68<br />

90<br />

68<br />

90<br />

68<br />

90<br />

68<br />

90<br />

Mass of front-face type (kg)<br />

0.4<br />

0.6<br />

0.65<br />

0.65<br />

0.65<br />

1.0<br />

Screw terminal<br />

●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Fixed<br />

Front Solderless (box) terminal (SL)<br />

Busbar terminal<br />

–<br />

–<br />

–<br />

●<br />

–<br />

●<br />

–<br />

●<br />

–<br />

●<br />

●<br />

●<br />

Installation and<br />

Rear<br />

(B) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

connections<br />

Rear<br />

(PM) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Plug-in<br />

Rear/front IP20<br />

(PM-IP) –<br />

–<br />

–<br />

–<br />

–<br />

–<br />

IEC 35mm<br />

rail<br />

Mounting hook (option)<br />

Adapter (option)<br />

–<br />

●<br />

●<br />

–<br />

●<br />

–<br />

●<br />

–<br />

●<br />

–<br />

–<br />

●<br />

Alarm switch<br />

(AL) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Cassette-type Auxiliary switch<br />

(AX) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

accessories Shunt trip<br />

(SHT) –<br />

–<br />

–<br />

–<br />

–<br />

–<br />

(option) ✽2<br />

Undervoltage trip (UVT)<br />

Non-synchronous closing (UVT-N) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Synchronous closing (UVT-S) –<br />

–<br />

–<br />

–<br />

–<br />

●<br />

Insulation switch<br />

(MG) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Built-in Earth-leakage trip alarm<br />

(EAL) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

accessories<br />

(option)<br />

Test button module<br />

Pre-alarm-contact output<br />

Cylinder key lock Available soon<br />

(TBM)<br />

(PAL)<br />

–<br />

–<br />

–<br />

●<br />

–<br />

–<br />

●<br />

–<br />

–<br />

●<br />

–<br />

–<br />

●<br />

–<br />

–<br />

●<br />

–<br />

●<br />

Accessorie’s with Lead-wire terminal block<br />

(SLT) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

connection (option) with Flying leads<br />

●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Enclosure<br />

Dustproof<br />

(S) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

( I ) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Waterproof<br />

(W) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Electrical operation device<br />

(MD) –<br />

–<br />

–<br />

–<br />

–<br />

●<br />

Mechanical interlock<br />

(MI) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Handle lock device Handle lock<br />

(HL) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

(HL-S) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Lock cover<br />

(LC) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

External<br />

(V) –<br />

●<br />

●<br />

●<br />

accessories External Door mounting<br />

●<br />

●<br />

(S) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

(option) operating<br />

handle<br />

(R) –<br />

–<br />

–<br />

–<br />

–<br />

●<br />

Mounted on breaker<br />

(F) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Insulating Between phase<br />

(BA-F) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

barrier To ground<br />

(BA-G) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Large<br />

(TC-L) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Small<br />

(TC-S) ●<br />

●<br />

●<br />

●<br />

●<br />

Terminal<br />

●<br />

cover<br />

Transparent<br />

(TTC) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

for rear connection<br />

(BTC) ●<br />

●<br />

●<br />

●<br />

●<br />

●<br />

for plug-in<br />

(PTC) –<br />

●<br />

●<br />

●<br />

●<br />

●<br />

Automatic tripping device<br />

Hydraulicmagnetimagnetimagnetimagnetimagnetimagnetic<br />

Hydraulic-<br />

Hydraulic-<br />

Hydraulic-<br />

Hydraulic-<br />

Thermal-<br />

Trip button<br />

CE marking<br />

✽7<br />

Equipped ✽5<br />

–<br />

Equipped<br />

<br />

Equipped<br />

<br />

Equipped<br />

<br />

Equipped<br />

<br />

Equipped<br />

<br />

Note ✽1: 125A rated current is 3p only.<br />

✽2: Cassette-type aaccessories are not acceptable for NV30-CS.<br />

✽3: Standard type is thus SLT equipped.<br />

✽4: In case of ampere rating 15A and 16A, time-delay type is not available.<br />

✽5: Included in AL (type) only.<br />

✽6: Rated operational voltage of time-delay type is for 200-440V.<br />

✽7: Specify if for CE marking. In case of the CE marking article of 250A Frame or less, outside sizes differ.<br />

Rated operational voltage Available voltage range<br />

100 - 230V<br />

80~253V<br />

100 - 440V<br />

80~484V<br />

200 - 440V 160~484V<br />

21