2. Detailed Specifications<br />

Miniature Circuit Breakers<br />

Type<br />

BH-PS M3 BH-PS M9<br />

Photo<br />

Number<br />

of poles<br />

1 2 3 1 2 3<br />

Rated current (A)<br />

at ambient temperature 40°C<br />

10,15,20,<br />

30,40,50,60<br />

10,15,20,<br />

30,40,50,60<br />

15,20,<br />

30,40,50,60<br />

6,10,16,20,(25),<br />

32,40,50,60<br />

10,16,20,(25),<br />

32,40,50,60<br />

10,16,20,(25),<br />

32,40,50,60<br />

Rated voltage (V)<br />

AC<br />

DC<br />

230/400<br />

400 400 230/400 400 400<br />

— 125<br />

— —<br />

Breaking capacity<br />

(kA) sym.<br />

IEC 60898<br />

AC230/400V<br />

AC400V<br />

3<br />

—<br />

—<br />

3<br />

9<br />

—<br />

—<br />

9<br />

—<br />

DC125V<br />

—<br />

1<br />

—<br />

—<br />

Type of instantaneous operation<br />

Types B,C,D ✳<br />

a 25<br />

50<br />

75<br />

25<br />

50<br />

75<br />

Dimensions<br />

(mm)<br />

a<br />

b<br />

ca<br />

c<br />

b 81.5<br />

c 60.5<br />

81.5<br />

60.5<br />

ca<br />

79<br />

79<br />

Mass (kg) 0.15<br />

0.32<br />

0.50<br />

0.15<br />

0.32<br />

0.50<br />

Plug-in (line)<br />

Clam p (load)<br />

Connection<br />

Automatic<br />

tripping device<br />

Optional<br />

accessories<br />

Terminal cover<br />

Terminal base<br />

Lock cover<br />

Handle lock<br />

Thermal, magnetic<br />

—<br />

●<br />

—<br />

●<br />

A pproved by<br />

— LR<br />

✳ Type B (3 In