2. Detailed Specifications<br />

ELRs and ZCTs<br />

Earth-Leakage relays<br />

Type<br />

Model name of ZCT combined<br />

(Note 5)<br />

Hole diameter mm<br />

15<br />

30<br />

40<br />

60<br />

80<br />

100<br />

Electrical self-hold type<br />

NV-ZBA<br />

ZT15B<br />

ZT30B<br />

ZT40B<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

ZT60B<br />

ZT80B<br />

ZT100B<br />

Mechanical self-hold type<br />

NV-ZSA<br />

ZT15B<br />

ZT30B<br />

ZT40B<br />

–<br />

–<br />

–<br />

Interchangeable leakage relay (Note 1)<br />

–<br />

–<br />

–<br />

ZT60B<br />

ZT80B<br />

ZT100B<br />

Harmonic surge ready<br />

Electrical self-hold type<br />

NV-ZHA<br />

ZT15B<br />

ZT30B<br />

ZT40B<br />

ZT60B<br />

ZT80B<br />

ZT100B<br />

Harmonic surge ready<br />

Mechanical self-hold type<br />

NV-ZLA<br />

ZT15B<br />

ZT30B<br />

ZT40B<br />

ZT60B<br />

ZT80B<br />

ZT100B<br />

Photo<br />

Control voltage AC V<br />

JIS<br />

UL/JIS<br />

UL/CE<br />

Built-in contact<br />

High speed<br />

type<br />

Delay<br />

type<br />

Delay type<br />

JIS<br />

UL/JIS (Note 2)<br />

UL/CE (Note 3)<br />

Rated sensitivity current mA<br />

Max. operating time s<br />

Rated sensitivity current mA<br />

Operating time s (Note 4)<br />

Inertial non-operating time s or longer than s<br />

Rated sensitivity current mA<br />

Max. operating time s<br />

Rated sensitivity current mA<br />

Max. operating time s (Note 4)<br />

Inertial non-operating time s or longer than s<br />

Rated sensitivity current mA<br />

Max. operating time s at5I∆n<br />

Rated sensitivity current mA<br />

Max. operating time s at2I∆n (Note 4)<br />

Inertial non-operating time s at2I∆n<br />

Earth-leakage indication<br />

Resetting method<br />

Configuration<br />

Continuous current capacity A<br />

Contact capacity A<br />

Connection<br />

Front<br />

Rear<br />

Standard attachment (Front connection)<br />

Mass kg<br />

Relay<br />

External<br />

Terminal cover<br />

accessories Mounting hook for IEC 35mm rail (DIN rail) Fixture<br />

Conforming standard<br />

High<br />

speed<br />

type<br />

High speed<br />

• Delay<br />

type<br />

High<br />

speed<br />

type<br />

Phase line type<br />

Max. consumption VA<br />

US UL standard (UR certified)<br />

Canada CSA standard<br />

European CE marking<br />

120VAC<br />

240VAC<br />

24VDC<br />

120 • 240 selectable<br />

30<br />

100 • 200 • 500<br />

selectable<br />

–<br />

cosφ=1<br />

5<br />

5<br />

5<br />

100 • 200 • 500<br />

selectable<br />

0.1<br />

100 • 200 • 500 selectable<br />

0.3 • 0.8 • 1.6 selectable<br />

0.1 • 0.5 • 1.1<br />

–<br />

–<br />

Electric type (LED)<br />

Push button or control power<br />

switch off<br />

1c<br />

5<br />

Clamp terminal<br />

–<br />

0.3<br />

(TC-ZBA)<br />

(DIN-ZBA)<br />

–<br />

–<br />

–<br />

cosφ=0.4<br />

L/R=0.007<br />

2<br />

2<br />

2<br />

120VAC<br />

240VAC<br />

415VAC<br />

30VDC<br />

100VDC<br />

200VDC<br />

120 • 240 selectable<br />

240 • 415 selectable<br />

30<br />

100 • 200 • 500<br />

selectable<br />

–<br />

cosφ=1<br />

5<br />

3<br />

2<br />

4<br />

0.4<br />

0.2<br />

3φ4W, 3φ3W, 1φ3W, 1φ2W<br />

100 • 200 • 500<br />

selectable<br />

0.1<br />

100 • 200 • 500 selectable<br />

(200 • 500 • 1000 selectable)<br />

0.3 • 0.8 • 1.6 selectable<br />

0.1 • 0.5 • 1.1<br />

–<br />

–<br />

Mechanical type (button)<br />

Push button<br />

(conbined with earth-leakage<br />

indicator)<br />

1a1c<br />

5<br />

cosφ=0.4<br />

L/R=0.007<br />

3<br />

2<br />

1<br />

3<br />

0.4<br />

0.2<br />

Clamp terminal<br />

Clamp terminal<br />

Mounting screw<br />

0.4<br />

(TC-ZSA)<br />

–<br />

3<br />

Note (1) Interchargeable leakage relay can be freely combined with relay and our ZCT. However, 30mA sensitivity product<br />

(excluding NV-ZHA/ZLA) can be combined with only ZT15B, ZT30B and ZT40B.<br />

(2) Indicates control voltage of UL. These are products indicating UL, CSA and JIS together. For voltage indication in<br />

JIS, 100-200V changeover for 120-240V changeover, 200-415V changeover for 240-440V changeover, 460V for<br />

480V are described together. When ordering, specify "UL/JIS".<br />

(3) Indicates control voltage of UL. These are products indicating UL, CSA and CE together. For voltage indication in<br />

CE, 120-230V changeover for 120-240V changeover, 230-440V changeover for 240-440V selectable are described<br />

together. When ordering, specify "UL/CE".<br />

(4) When the operating time are 0.3 and 0.45 seconds, 0.8 and 1.0 seconds, and 1.6 seconds, the relay operates<br />

between 0.15 and 0.45, between 0.6 and 1.0 seconds and between 1.2 and 2.0 seconds respectively.<br />

(5) Can be combined with interchangeable ZCT with primary conductor. Refer to the next page for detail.<br />

(6) It's not UL-certified.<br />

–<br />

–<br />

–<br />

–<br />

120 • 240 selectable<br />

240 • 440 selectable<br />

–<br />

30 50<br />

0.1<br />

100 • 200 • 500 selectable<br />

0.1 • 0.45 • 1.0 selectable<br />

– • 0.1 • 0.5<br />

30 • 50 • 100 selectable<br />

0.04<br />

100 • 300 • 500 selectable<br />

300 • 500 • 1000 selectable<br />

0.45 • 1.0 selectable<br />

0.1 • 0.5<br />

Electric type (LED)<br />

Push button or control power<br />

switch off<br />

1a1c<br />

5<br />

cosφ=1<br />

cosφ=0.4<br />

120VAC<br />

240VAC<br />

24VDC<br />

5<br />

5<br />

5<br />

L/R=0.007<br />

2<br />

2<br />

2<br />

Use auxiliary relay for AC415V contact.<br />

Clamp terminal<br />

Clamp terminal<br />

0.4<br />

(TC-ZSA)(Note 6)<br />

–<br />

UL1053<br />

Recognized component<br />

(File No.E196562)<br />

LR103083(Certified No.)<br />

Declaration for conformity<br />

IEC60947-2 AnnexB<br />

EN60947-2 AnnexB<br />

Control voltage<br />

120V<br />

240V<br />

415V<br />

Control voltage<br />

120V<br />

240V<br />

440V<br />

480V<br />

–<br />

120 • 240 selectable<br />

240 • 440 selectable<br />

480<br />

120VAC<br />

240VAC<br />

480VAC<br />

30VDC<br />

Available voltage range<br />

80~126V<br />

160~252V<br />

320~484V<br />

Available voltage range<br />

80~132V<br />

160~264V<br />

304~484V<br />

368~528V<br />

–<br />

30 50<br />

0.1<br />

100 • 200 • 500 selectable<br />

0.1 • 0.45 • 1.0 selectable<br />

– • 0.1 • 0.5<br />

30 • 50 • 100 selectable<br />

0.04<br />

100 • 300 • 500 selectable<br />

300 • 500 • 1000 selectable<br />

0.45 • 1.0 selectable<br />

0.1 • 0.5<br />

Mechanical type (button)<br />

Push button<br />

(conbined with earthleakage<br />

indicator)<br />

1a1c<br />

5<br />

cosφ=1<br />

5<br />

3<br />

1<br />

3<br />

Clamp terminal<br />

Clamp terminal<br />

cosφ=0.4<br />

L/R=0.007<br />

3<br />

2<br />

1<br />

3<br />

0.4<br />

(TC-ZSA)(Note 6)<br />

–<br />

UL1053<br />

Recognized component<br />

(File No.E196562)<br />

LR103083(Certified No.)<br />

Declaration for conformity<br />

IEC60947-2 AnnexB<br />

EN60947-2 AnnexB<br />

Remark (1) Relays with rate shown in the ( ) in the space for rate<br />

are manufactured by your order.<br />

(2) CE marking is for self-statement for the purpose of<br />

interrupting NF when ground-fault occurs by combining<br />

with our NF with CE marking (voltage tripping device).<br />

(3) NV-ZBA/ZSA<br />

(4) NV-ZHA/ZLA<br />

Example of applicable circuit voltage<br />

100 • 110V • 120V<br />

200 • 220 • 240V<br />

400 • 415 • 440V<br />

Example of applicable circuit voltage<br />

100 • 110 • 120V<br />

200 • 220 • 230 • 240V<br />

380 • 400 • 415 • 440V<br />

460 • 480V<br />