18.11.2014 Views

MS4PMUHVT Multi-Stage Electronic Temperature Control with ...

MS4PMUHVT Multi-Stage Electronic Temperature Control with ...

MS4PMUHVT Multi-Stage Electronic Temperature Control with ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Control</strong> Functions<br />

<strong>Temperature</strong> Management Functions<br />

SI (Displays in Mode 4i only) Setpoint is the primary<br />

temperature setting (°F or °C) programmed by the<br />

user. For information on function in each mode, see<br />

Modes of Operation.<br />

S2, S3, S4 Setpoint 2, Setpoint 3, Setpoint 4 depend<br />

on the mode used. For information on function in each<br />

mode, see Modes of Operation.<br />

30 o F<br />

<strong>Temperature</strong><br />

Setpoint<br />

Sensed<br />

<strong>Temperature</strong><br />

HI, H2, H3, H4 Differentials are the difference (F° or<br />

C°) between the value at which an output is switched<br />

Off and the value at which an output is switched On<br />

(relay contacts closing and opening, initiating or<br />

ending an On cycle). For information on function in<br />

each mode, see Modes of Operation.<br />

HL, LL High and Low Setpoint Stops are<br />

temperature values (°F or °C) that define how high or<br />

low the primary Setpoint may be adjusted. Setpoint<br />

stops deter unauthorized or accidental overadjustment<br />

of Setpoint.<br />

On<br />

Off<br />

On<br />

Off<br />

Load Demand<br />

Output Status<br />

20 o F<br />

Output Status<br />

(up to four stages)<br />

Time (Minutes)<br />

2 4 6 8 10 12 14 16 18<br />

Figure 18: Soft Start<br />

Soft Start Example:<br />

<strong>Temperature</strong> = 20°<br />

Setpoint = 30°<br />

Soft start = 2 minutes<br />

Rate of Increase =<br />

Soft start x (setpoint – sensor reading)<br />

20<br />

On<br />

Off<br />

Cycle Delay<br />

Time<br />

Figure 17: Cycle Delay<br />

Cc Cycle Delay, Cooling establishes the minimum<br />

time in minutes between two subsequent On cycles of<br />

cooling (direct) stages. See Figure 17.<br />

CH Cycle Delay, Heating establishes the minimum<br />

time in minutes between two subsequent On cycles of<br />

heating (reverse) stages. See Figure 17.<br />

iS Interstage Time Delay is the minimum amount of<br />

time between two successive stages when multiple<br />

stages are called for in rapid sequence.<br />

rt Soft Start controls the rate at which the controlled<br />

temperature is allowed to approach Setpoint on power<br />

up, both initially and when the binary input is<br />

configured as remote shutoff. The setting is<br />

minutes/temperature units, such as minutes/F°. See<br />

Figure 18.<br />

<strong>Control</strong>led temperature increases by 1° every<br />

two minutes, until the setpoint temperature is<br />

reached. To go from 20° to 30° takes 20 minutes.<br />

So <strong>Temperature</strong> Sensor Offset allows compensation<br />

for temperature differences between actual and<br />

displayed temperature, such as when using long<br />

sensor leads. See Table 1 to determine the<br />

temperature value to compensate for long sensor lead<br />

extensions.<br />

Un <strong>Temperature</strong> Units Used allows selection of<br />

Fahrenheit or Celsius temperature scale.<br />

PU Display Refresh Rate establishes the time delay<br />

(seconds) between updates of the temperature<br />

display.<br />

Lc, Uc Heating Reset and Cooling Reset are<br />

automatic shifts of the setpoint, based on the<br />

temperature at the Auxiliary <strong>Temperature</strong> Sensor<br />

(ATS). See <strong>Temperature</strong> Reset for more information.<br />

NC Non-compensated Band establishes the<br />

temperature range (F° or C°) over which reset does<br />

not take place.<br />

<strong>MS4PMUHVT</strong> <strong>Multi</strong>-<strong>Stage</strong> <strong>Electronic</strong> <strong>Temperature</strong> <strong>Control</strong> <strong>with</strong> Relay Pack Product/Technical Bulletin 11

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!