Table 2: Function Settings in Order of Programming in <strong>Control</strong> Module<br />
Display Code Function Useable Setting Range and Unit Value Factory-Set<br />
Values<br />
4d = Direct<br />
4r = Reverse<br />
4b = Deadband<br />
4i = Independent<br />
setpoints<br />
Modes of Operation<br />
4d = Direct<br />
4r = Reverse<br />
4b = Deadband<br />
4i = Independent setpoints<br />
4d<br />
SI (Mode 4i only) Setpoint 4d, 4r, 4b = -40 to 99°F (-40 to 80°C)<br />
4i = Low Setpoint Stop to High Setpoint Stop<br />
HI Differential 1 1 to 9F° (1 to 9C°) 5 (F°)<br />
S2 ∆ Setpoint 2 4d, 4r = 1 to 40F° (1 to 40C°)<br />
4b = 2 to 40F° (2 to 40C°)<br />
4i = Low Setpoint Stop to High Setpoint Stop<br />
—<br />
5 (F°)<br />
H2 Differential 2 1 to 9F° (1 to 9C°) 5 (F°)<br />
S3 ∆ Setpoint 3 1 to 40F° (1 to 40C°) 5 (F°)<br />
H3 Differential 3 1 to 9F° (1 to 9C°) 5 (F°)<br />
S4 ∆ Setpoint 4 1 to 40F° (1 to 40C°) 5 (F°)<br />
H4 Differential 4 1 to 9F° (1 to 9C°) 5 (F°)<br />
LL Low Setpoint Stop -40°F (-40°C) to High Setpoint Stop 32 (°F)<br />
HL High Setpoint Stop Low Setpoint Stop to 99°F (80°C) 90 (°F)<br />
Cc Cycle Delay, Cooling 0 to 9 minutes 2 (minutes)<br />
CH Cycle Delay, Heating 0 to 9 minutes 0 (minutes)<br />
rt Soft Start 0 to 99 minutes/degrees 10<br />
AH High <strong>Temperature</strong> Alarm 0 to 50F° (0 to 50C°) 15 (F°)<br />
AL Low <strong>Temperature</strong> Alarm -50 to 0F° (-50 to 0C°) -15 (F°)<br />
Ad Alarm Differential 1 to 9F° (1 to 9C°) 5 (F°)<br />
At Alarm Time Delay 0 to 99 minutes 15 (minutes)<br />
So <strong>Temperature</strong> Sensor Offset -20 to 20F° (-20 to 20C°) 0 (F°)<br />
Un <strong>Temperature</strong> Units Used 0 = °C<br />
1 = °F<br />
PU Display Refresh Rate 1 to 99 seconds 1 (second)<br />
iF Binary Input Mode 0 = No Response to Binary Input<br />
1 = Shutoff and Alarm Signaling<br />
2 = Setback Mode<br />
3 = Remote Shutoff<br />
1 (°F)<br />
Sb Setback -20 to 20F° (-20 to 20C°) 10 (F°)<br />
0 (no response)<br />
id Binary Input Time Delay 0 to 99 minutes 0 (minutes)<br />
iS Interstage Time Delay 3 to 90 seconds 3 (seconds)<br />
Lc Heating Reset 0 to 6°/ ° 4<br />
Uc Cooling Reset 0 to 6°/ ° 4<br />
NC Non-Compensated Band 0 to 20F° (0 to 20C°) 8<br />
Note: <strong>Temperature</strong> Reset Functions (Heating Reset, Cooling Reset, Non-compensated Band) are only enabled after the<br />
auxiliary sensor is installed and power is cycled.<br />