Independent Setpoint Mode<br />

Independent Setpoint mode is used for applications<br />

requiring cooling and heating. Where desirable, stages<br />

may overlap or have space between them. See<br />

Figure 16.<br />

Setpoint is the desired heating temperature. It is the<br />

basis for the reverse stages.<br />

In Reverse mode (heating applications), when Setpoint<br />

is reached on a temperature rise, the N.O. relay<br />

contacts open, ending the On cycle.<br />

Setpoint cannot be set higher than Setpoint 2, nor can<br />

Setpoint 2 be set lower than Setpoint. If overlapping<br />

adjustment is attempted, the setting that is not being<br />

adjusted will adopt the value of the setting that is being<br />

adjusted.<br />

Differential is the operational range of <strong>Stage</strong> 1.<br />

Setpoint 2 the desired cooling temperature<br />

programmed by the user. It is the basis for the direct<br />

stages.<br />

In Direct mode (cooling applications), when Setpoint is<br />

reached on a temperature drop, the N.O. relay<br />

contacts open, ending the On cycle.<br />

Differential 2 is the operational range of <strong>Stage</strong> 2.<br />

Setpoint 3 is the offset from Setpoint that activates<br />

<strong>Stage</strong> 3.<br />

Differential 3 is the operational range of <strong>Stage</strong> 3.<br />

Setpoint 4 is the offset from Setpoint 2 that activates<br />

<strong>Stage</strong> 4.<br />

Differential 4 is the operational range of <strong>Stage</strong> 4.<br />

Interstage Time Delay is the minimum amount of time<br />

between two successive stages when multiple stages<br />

are called for in rapid sequence.<br />

<strong>Temperature</strong><br />

Interstage<br />

Time Delay<br />

Cooling<br />

<strong>Stage</strong> 4<br />

Differential 4<br />

<strong>Stage</strong> 2<br />

Differential 2<br />

Setpoint 4<br />

Setpoint<br />

<strong>Stage</strong> 1<br />

Differential<br />

Setpoint 3<br />

<strong>Stage</strong> 3<br />

Differential 3<br />

Heating<br />

Interstage<br />

Time Delay<br />

Time<br />

Figure 16: Independent Setpoint Mode<br />