Deadband Mode<br />

Deadband mode is used for applications requiring<br />

cooling and heating. Where desirable, stages may<br />

overlap or have space between them. See Figure 15.<br />

Setpoint is the desired temperature.<br />

Setpoint 2 is width of the deadband, which is centered<br />

on Setpoint.<br />

In Direct Mode (cooling applications), the N.O. relay<br />

contacts open, ending the On cycle when<br />

Setpoint + (1/2 Setpoint 2) is reached on a<br />

temperature drop.<br />

In Reverse Mode (heating applications), the N.O. relay<br />

contacts open, ending the On cycle when Setpoint -<br />

(1/2 Setpoint 2) is reached on a temperature rise.<br />

Differential is the operational range of <strong>Stage</strong> 1.<br />

Differential 2 is the operational range of <strong>Stage</strong> 2.<br />

Setpoint 3 is the offset from the low end of the<br />

deadband that activates <strong>Stage</strong> 3.<br />

Differential 3 is the operational range of <strong>Stage</strong> 3.<br />

Setpoint 4 is the offset from the high end of the<br />

deadband that activates <strong>Stage</strong> 4.<br />

Differential 4 is the operational range of <strong>Stage</strong> 4.<br />

Interstage Time Delay is the minimum amount of time<br />

between two successive stages when multiple stages<br />

are called for in rapid sequence.<br />

<strong>Temperature</strong><br />

Interstage<br />

Time Delay<br />

On<br />

Cooling<br />

<strong>Stage</strong> 4<br />

Differential 4<br />

On<br />

<strong>Stage</strong> 2<br />

Differential 2<br />

Off<br />

Setpoint 4<br />

(Offset from <strong>Stage</strong> 2)<br />

Off<br />

Setpoint<br />

Off<br />

Setpoint + (1/2 Setpoint 2)<br />

Setpoint - (1/2 Setpoint 2)<br />

Setpoint 2 (Deadband)<br />

(Centered on Setpoint)<br />

<strong>Stage</strong> 1<br />

Differential<br />

Off<br />

Setpoint 3<br />

(Offset from <strong>Stage</strong> 1)<br />

On<br />

<strong>Stage</strong> 3<br />

Differential 3<br />

Heating<br />

On<br />

Interstage<br />

Time Delay<br />

Time<br />

Figure 15: Deadband Mode<br />