14.7 - Fault and Protection Schedule - EDF Hinkley Point
14.7 - Fault and Protection Schedule - EDF Hinkley Point
14.7 - Fault and Protection Schedule - EDF Hinkley Point
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
PRE-CONSTRUCTION SAFETY REPORT<br />
CHAPTER 14: DESIGN BASIS ANALYSIS<br />
SUB-CHAPTER : <strong>14.7</strong><br />
PAGE : 45 / 48<br />
Document ID.No.<br />
UKEPR-0002-149 Issue 02<br />
SUB-CHAPTER <strong>14.7</strong> - FIGURE 2<br />
SG level scale<br />
SG level<br />
MAX2<br />
VIV [MSIV] closure<br />
VDA [MSRT] setpoint increase in SGi<br />
PROTECTION<br />
MAX2<br />
PC → PROTECTION<br />
MAX1<br />
ASG [EFWS] isolation in SGi → PROTECTION<br />
MAX1<br />
RT<br />
ARE/AAD [MFWS/SSS] isolation in SGi<br />
PROTECTION<br />
LCO<br />
Alarm<br />
Nominal<br />
Control<br />
LCO<br />
Alarm<br />
MIN1<br />
RT → PROTECTION<br />
MIN2<br />
ASG [EFWS] actuation in SGi → PROTECTION<br />
MIN2<br />
ASG [EFWS] actuation in SGi → RRC<br />
MIN3<br />
RT → RRC<br />
MIN4<br />
Reactor coolant pumps OFF → RRC