Selection > Calculating the burner length > Burners with burner attachment tube<br />

18<br />

L1<br />

L O<br />

L2 L 1-2<br />

Legend<br />

L1 = Burner tube length<br />

L2 = Position of burner head<br />

LO = Furnace wall thickness<br />

L 1-2 = Attachment tube length (distance<br />

from burner head to burner tube<br />

end)<br />

Calculation example<br />

Attachment tube lengths (L 1-2 ):<br />

<strong>BIO</strong>, <strong>BIO</strong>A, <strong>ZIO</strong><br />

H burner head<br />

R burner head<br />

[mm]<br />

[mm]<br />

50 115 115<br />

65 115 115<br />

80 165 165<br />

100 165 165<br />

125 215 215<br />

140 265 265<br />

165 265 165<br />

200 315 215<br />

Position of the burner head (near the interior furnace wall):<br />

L2 = L O ± 50 mm<br />

The burner tube length (L1) is calculated by adding the position of the burner<br />

head (L2) to the attachment tube length (L 1-2 ):<br />

L1 = L2 + L 1-2<br />

Example<br />

Desired flame shape = H (long) – see [Field of application – p. 13].<br />

Selected burner with 90 kW capacity = <strong>BIO</strong> 65.<br />

Attachment tube length (L 1-2 ) = 115 mm.<br />

Furnace wall thickness L O = 300 mm.<br />

Calculate shortest length L2:<br />

L2 = L O - 50 mm = 300 - 50 mm = 250 mm.<br />

Compare L2 (here 250 mm) with standard lengths (35, 135, 235, 335 mm, etc.).<br />

Select next longest standard length L2: L2 = 335 mm.<br />

Calculate the related burner tube length (L1):<br />

L1 = L2 + L1-2 = 335 mm + 115 mm = 450 mm.<br />

<strong>BIO</strong>, <strong>BIO</strong>A, <strong>ZIO</strong> · Edition 05.10