HVAC Upgrades – International Center AAI #12-154<br />
SECTION 23 09 23<br />
DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC<br />
PART 1 GENERAL<br />
1.1 REFERENCES<br />
A. The latest edition of the following standards and codes in effect and amended as of<br />
supplier's proposal date, and any applicable subsections thereof, shall govern design and<br />
selection of equipment and material supplied:<br />
1. ANSI MC85.1 - Terminology for Automatic Control.<br />
2. American Society of Heating, Refrigerating and Air Conditioning Engineers<br />
(ASHRAE).<br />
3. ANSI/ASHRAE Standard 135-2010, BACnet.<br />
4. International Building Code (IBC), including local amendments, IECC and IMC.<br />
5. UL 916 Underwriters Laboratories Standard for Energy Management Equipment.<br />
Canada and the US.<br />
6. National Electrical Code (NEC).<br />
7. FCC Part 15, Subpart J, Class A<br />
8. EMC Directive 89/336/EEC (European CE Mark)<br />
B. City, county, state, and federal regulations and codes in effect as of contract date.<br />
C. Except as otherwise indicated the system supplier shall secure and pay for all permits,<br />
inspections, and certifications required for his work and arrange for necessary approvals<br />
by the governing authorities.<br />
D. All BAS system components (electronic DDC hardware and all software) shall be of one<br />
manufacturer as indicated in manufacturer’s trade catalog. Hybrid systems assembled<br />
from various manufacturers shall not be acceptable. This requirement does not apply to<br />
field devices.<br />
E. Controls contractor to provide personnel for commissioning as required.<br />
1.2 SYSTEM DESCRIPTION<br />
A. The system shall be a browser based Building Automation System (BAS) accessible with<br />
standard browsers such as Internet Explorer and Google Chrome. Systems requiring<br />
workstation software licenses shall not be acceptable.<br />
B. Systems based on Lonworks shall not be acceptable.<br />
C. General Description:<br />
1. Install the Building Global Controller the 2 nd floor mechanical room.<br />
2. THE DIRECT DIGITAL CONTROL (DDC) SYSTEM SHALL CONTROL<br />
EQUIPMENT AS INDICATED ON THE DRAWINGS.<br />
DIRECT DIGITAL CONTROL FOR HVAC 23 09 23 - 1