HVAC Upgrades – International Center AAI #12-154<br />

of factory mounted controls the manufacturer doing the mounting shall provide control<br />

transformers and coordinate the voltages. Indicate location of all control panels requiring<br />

power on submittal shop drawings for coordination with Electrical Contractor during preinstallation<br />

meeting described in section 1.6 above.<br />

D. Control valves and separable wells for immersion elements and couplings for flow and<br />

pressure switches furnished under this section shall be installed by the Mechanical<br />

Contractor.<br />

E. All automatic dampers furnished under this section shall be installed by the Mechanical<br />

Contractor. It shall be the responsibility of the Mechanical Contractor to provide and install<br />

blank off plates when the control application requires dampers smaller than duct size.<br />

F. All finished painting required for Control piping and equipment shall be done by the General<br />

Contractor.<br />

G. All cutting and patching necessary for the installation of the Control System shall be done by<br />

the General Contractor.<br />

H. All sealing of any penetration of the under floor supply air plenum shall be accomplished by<br />

the trade making the penetration.<br />

I. Enclosures: Equipment room controllers or relay packs shall not be installed in the room’s<br />

ceiling. If the equipmentis in a mechanical room, electrical room, chiller room or other<br />

dedicated room the associated controller and relays shall be mounted in a NEMA-1 fabricated<br />

and hinged metal enclosure with lock within sight of the equipment it controls. Fabricated<br />

panel means built in a shop environment with templates and not constructed on site.<br />

Extensions to controllers for additional controlled or monitored items for a given area shall be<br />

mounted adjacent to the equipment controls.<br />

J. Space Local Indication: Each IDS (Indicating Digital Space) sensor, where specified, shall<br />

display digital readouts of temperature and temperature setpoint. The Operator shall be able<br />

to delete these readouts from the Central Workstation on an individual IDS basis as desired.<br />

K. Local Override Buttons: Shall be integral to the sensor and installed in all areas except<br />

common areas such as lobbies, bathrooms, hallways, etc. Equipment room sensors shall not<br />

be equipped with override buttons.<br />

L. Space Temperature Sensor Local Adjustment: Areas specified to have adjustment shall have<br />

a temperature setpoint adjustment that can be limited in software to plus or minus 2 Deg F<br />

adjustment range from setpoint.<br />

M. Duct Smoke Detectors: Shall be provided, installed and wired for fan shutdown by Division<br />

26 contractor. The Building Automation System or controller shall not be used in the life<br />

safety control or shutdown of the building in any way. A duct smoke detector is to be<br />

mounted at the return air of each air handler unit, over 2,000 CFM which will stop the unit<br />

upon a detection of smoke.<br />

N. Smoke and Fire Dampers: Shall be provided and installed by the Mechanical Contractor with<br />

DIRECT DIGITAL CONTROL FOR HVAC 23 09 23 - 7