22.11.2014 Views

ADDENDUM NO. 2 CITY OF SAN ANTONIO CAPITAL ...

ADDENDUM NO. 2 CITY OF SAN ANTONIO CAPITAL ...

ADDENDUM NO. 2 CITY OF SAN ANTONIO CAPITAL ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

HVAC Upgrades – International Center AAI #12-154<br />

o. Provide computer software and hardware, operator input/output devices,<br />

control units, local area networks (LAN), sensors, control devices,<br />

actuators, control valves, dampers and operators, indicating devices,<br />

interface equipment and other apparatus and accessories to operate<br />

mechanical systems, and to perform functions specified and detailed.<br />

D. SYSTEM REQUIREMENTS<br />

1. A distributed logic control system complete with all software and hardware<br />

functions shall be provided and installed. System shall be based on<br />

ANSI/ASHRAE Standard 135-2010, BACnet. This system is to control all<br />

mechanical equipment, including all unitary equipment, all air handlers and any<br />

other listed equipment using BACnet-compliant components. Non-BACnetcompliant<br />

or proprietary equipment or systems (including gateways) shall not be<br />

acceptable and are specifically prohibited.<br />

2. It shall be the responsibility of the Controls Contractor to coordinate all interface<br />

requirements with the respective equipment vendors to provide a complete and<br />

working system in all respects.<br />

3. The Web Server should be designed to harness the power of the Internet and<br />

provide efficient integration of standard open protocols (i.e. BACnet). The<br />

Network Server creates a powerful network environment with comprehensive<br />

database management and messaging services. In addition, the Web Server shall<br />

provide an engineering environment and graphical user interface.<br />

4. The web server shall provide the interface between the LAN or WAN and the<br />

field control devices, and provide global supervisory control functions over the<br />

control devices connected to the web server. It shall be capable of executing<br />

application control programs to provide:<br />

a. Calendar functions<br />

b. Scheduling<br />

c. Trending<br />

d. Alarm monitoring and routing<br />

e. Time synchronization<br />

f. Integration of controller data for each applicable protocol<br />

g. Network Management function for all network devices<br />

5. All application controllers for every terminal unit (VAV, etc.) air handler, all<br />

central plant equipment, and any other piece of controlled equipment shall be<br />

fully programmable. Application controllers shall be mounted next to controlled<br />

equipment and communicate with building controller via BACnet LAN.<br />

6. Provide installation and calibration, supervision, adjustments, and fine tuning<br />

necessary for complete and fully operational system.<br />

1.3 SUBMITTALS<br />

A. Section 23 05 00 – General Mechanical Requirements: Submittal procedures.<br />

B. Shop Drawings: Indicate the following:<br />

1. Indicate routing of MS/TP networks on floor plans. Indicate location of Global<br />

Building Controllers and servers. Provide IP connection requirements.<br />

2. Provide proposed campus, floor-plan, equipment and summary graphics with<br />

submittal.<br />

DIRECT DIGITAL CONTROL FOR HVAC 23 09 23 - 3