DALI manual - Tridonic
DALI manual - Tridonic
DALI manual - Tridonic
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
.<br />
c<br />
comfortDIM product series in detail<br />
comfortDIM product series in detail<br />
This chapter provides details of the various comfortDIM products. The topics covered here include functions,<br />
connections and programming. For further information on the products please refer to the data sheets and the<br />
installation instructions.<br />
<strong>DALI</strong> power supply<br />
<strong>DALI</strong> PS / PS1/ PS2<br />
<strong>DALI</strong> PS, <strong>DALI</strong> PS1 and <strong>DALI</strong> PS2 are <strong>DALI</strong> power supply modules with a rated current of 200 mA or 240 mA (<strong>DALI</strong><br />
PS2). The modules differ in their casing design; <strong>DALI</strong> PS and <strong>DALI</strong> PS2 are suitable for installation in switching<br />
cabinets; <strong>DALI</strong> PS1 is suitable for installation in suspended ceilings or cavities.<br />
The interface of a <strong>DALI</strong> ballast needs a maximum of 2 mA; for 64 individual addresses this means a current of 128 mA.<br />
The remaining 72 mA (or 112 mA in the case of <strong>DALI</strong> PS2) can be used for supplying <strong>DALI</strong> control modules without<br />
their own power supply (<strong>DALI</strong> GC, <strong>DALI</strong> SC etc.).<br />
<strong>DALI</strong> PS2 Standby<br />
<strong>DALI</strong> PS2 Standby also has a built-in relay contact. To reduce standby losses, the built-in relay disconnects the<br />
ballasts from the power supply as soon as all the luminaires have been switched off.<br />
As soon as the <strong>DALI</strong> PS2 Standby detects that all the luminaires have been switched off it changes to standby mode<br />
after a user-definable delay and controls a built-in relay. With the aid of this relay the connected units can be<br />
disconnected from the power supply via a contactor. Only the <strong>DALI</strong> control modules are then still in the <strong>DALI</strong> circuit.<br />
As soon as a <strong>DALI</strong> control module sends a “Light ON” command the <strong>DALI</strong> PS2 Standby reverts to normal operating<br />
mode and connects the units back to the power supply. The parameters of the <strong>DALI</strong> PS2 Standby, such as delay,<br />
monitoring interval etc. can be set using the masterCONFIGURATOR configuration software (V1.12 or higher) (see<br />
Reference list).<br />
<strong>DALI</strong> Manual | 08-2013 | en<br />
21 / 93