Designing a <strong>DALI</strong> application<br />
Table: Parts list<br />
Pos. Qty Article name<br />
1 1 <strong>DALI</strong> power supply <strong>DALI</strong> PS / PS1<br />
2 2 <strong>DALI</strong> touchpanel <strong>DALI</strong> TOUCHPANEL 02<br />
3 3 <strong>DALI</strong> MSensor 02 <strong>DALI</strong> MSensor 02 (5DPI 41 rc)<br />
4 18 <strong>DALI</strong> control gear for linear luminaires PCA EXCEL one4all xitec II<br />
Table: <strong>DALI</strong> checklist<br />
<strong>DALI</strong> condition Planned / present<br />
Maximum of 64 <strong>DALI</strong> ECGs<br />
Maximum of 16 groups<br />
18 <strong>DALI</strong> devices<br />
4 groups<br />
Maximum of 16 scenes<br />
<strong>DALI</strong> circuit current < Rated power supply current<br />
Line length < 300 m (for 1.5mm²)<br />
66 mA<br />
approx. 50 m<br />
5 wires to each luminaire 5 x 1.5mm²<br />
<strong>DALI</strong> ECG in luminaire<br />
<strong>Tridonic</strong> PCA EXCEL one4all xitec II<br />
Figure: Installation for open-plan office with wiring<br />
Grouping<br />
The luminaires can be grouped in either of two ways. With the <strong>DALI</strong> RC (see <strong>DALI</strong> MSensor 02 operating instructions)<br />
or with the masterCONFIGURATOR software (see Reference list).<br />