23.11.2014 Views

DALI manual - Tridonic

DALI manual - Tridonic

DALI manual - Tridonic

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

.<br />

c<br />

Designing a <strong>DALI</strong> application<br />

Table: Parts list<br />

Pos. Qty Article name<br />

1 1 <strong>DALI</strong> power supply <strong>DALI</strong> PS / PS1<br />

2 2 <strong>DALI</strong> touchpanel <strong>DALI</strong> TOUCHPANEL 02<br />

3 3 <strong>DALI</strong> MSensor 02 <strong>DALI</strong> MSensor 02 (5DPI 41 rc)<br />

4 18 <strong>DALI</strong> control gear for linear luminaires PCA EXCEL one4all xitec II<br />

Table: <strong>DALI</strong> checklist<br />

<strong>DALI</strong> condition Planned / present<br />

Maximum of 64 <strong>DALI</strong> ECGs<br />

Maximum of 16 groups<br />

18 <strong>DALI</strong> devices<br />

4 groups<br />

Maximum of 16 scenes<br />

<strong>DALI</strong> circuit current < Rated power supply current<br />

Line length < 300 m (for 1.5mm²)<br />

66 mA<br />

approx. 50 m<br />

5 wires to each luminaire 5 x 1.5mm²<br />

<strong>DALI</strong> ECG in luminaire<br />

<strong>Tridonic</strong> PCA EXCEL one4all xitec II<br />

Figure: Installation for open-plan office with wiring<br />

Grouping<br />

The luminaires can be grouped in either of two ways. With the <strong>DALI</strong> RC (see <strong>DALI</strong> MSensor 02 operating instructions)<br />

or with the masterCONFIGURATOR software (see Reference list).<br />

<strong>DALI</strong> Manual | 08-2013 | en<br />

68 / 93