23.11.2014 Views

DALI manual - Tridonic

DALI manual - Tridonic

DALI manual - Tridonic

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

.<br />

c<br />

Annex<br />

Annex<br />

Technical features of a <strong>DALI</strong> circuit<br />

Maximum no. of <strong>DALI</strong> units: 64<br />

Maximum no. of <strong>DALI</strong> groups: 16<br />

Maximum no. of <strong>DALI</strong> scenes:16<br />

<strong>DALI</strong> voltage: 9.5 V – 22.5 V, typically 16 V<br />

<strong>DALI</strong> system current: Max. 250 mA (depending on the installed <strong>DALI</strong> power supply)<br />

Data transfer rate: 1200 baud<br />

Maximum cable length: The maximum cable length depends on the maximum permitted voltage drop along the<br />

<strong>DALI</strong> cable; this is defined as 2 V max. This corresponds to a maximum cable length of 300 m for a line<br />

cross-section of 1.5 mm².<br />

½ CAUTION!<br />

When calculating the maximum cable length the contact resistance must also be taken into account.<br />

A voltage drop of 2V must not be exceeded.<br />

...<br />